Liquid Leakage Sensor Amplifiers for Long-distance Wiring
K7L-U[] / UD[][]
Ultra-miniature Liquid Leakage Sensor Amplifier Enables Longest Liquid Leakage Monitoring Distance in Industry. K7L-UB and K7L-UDB are our Value Design products which increase the value of your control panels.
Characteristics
|
Ambient temperature |
Operating: -10 to 55°C |
|
Ambient humidity |
Operating: 45% to 85% |
|
Insulation resistance |
10 MΩ at 100 VDC between case and current-carrying parts |
|
Dielectric strength |
1,000 VAC at 50/60 Hz for 1 min between case and current-carrying parts |
|
Power consumption |
1 W max. |
|
Response time |
Operate: 800 ms max. |
|
Weight |
Approx. 14 g |
Ratings
|
Rated power supply |
12 to 24 VDC (Allowable voltage fluctuation range: 10 to 30 VDC) |
|||
|
Operate resistance |
0 to 1 MΩ variable |
|||
|
Disconnection |
Detection signal: 10 VDC max., 200 ms |
|||
|
Release resistance |
105% min. of operate resistance |
|||
|
Output |
Open-collector transistor output with 100 mA at 30 VDC max. for both liquid leakage detection |
|||
|
Vibration resistance |
10 to 150 Hz, 0.1-mm single amplitude with 15-m/s2 acceleration for 8 minutes 10 times each |
|||
|
Shock resistance |
150 m/s2 3 times each in six directions on 3 axes |
|||
|
Wiring distance |
Wiring cable, Sensing Band: Total: 400 m max. |
|||
|
Accessories |
Product Name |
Terminal Block |
Screwdriver for ADJUST |
Terminator |
|
Model |
F03-20 |
--- |
F03-20T |
|
|
K7L-U/UB |
1 |
1 |
--- |
|
|
K7L-UD/UDB/UDP/UDPB |
1 |
1 |
1 |
|
* For the K7L-UD[][].