Water Leak Detector
61F-WL
Set Sensitivity Freely to Suit the Liquid to Detect
Ratings
61F-WL-CP[]-NRA |
|
Supply voltage/frequency |
100 VAC - 240 VAC 50/60 Hz |
Operating voltage range |
85% to 110% of rated voltage |
Operating frequency range |
±5 Hz of the rated frequency |
Power consumption |
3.2 VA max. |
Contact ratings |
3 A at 250 VAC (Resistive load (cosφ = 1)) |
Ambient temperature |
-10 to +55°C |
Ambient humidity |
25 to 85% RH |
Ambient storage temperature |
-10 to +55°C |
Ambient storage humidity |
25 to 85% RH |
Weight |
Approx. 100 g |
Accessories |
PFC-N8 |
Characteristics
61F-WL-CP[]-NRA |
|
Operation resistance |
Variable (0 to 50 kΩ) |
Operation resistance error |
Scale 0: 0 to 10 kΩ *1 |
Release resistance |
Operation resistance + 50 kΩ or less |
Interelectrode voltage |
5 VAC |
Response time |
Operate: 80 ms max. |
Startup lock time |
3 s after turning on the power supply (The LED blinks during the startup lock time) |
Insulation resistance *2 |
100 MΩ min. (at 500 VDC) |
Dielectric strength *2 |
2000 VAC, 50/60 Hz for 1 min. |
Life expectancy |
Electrical: 100,000 operations min. |
Approved standards |
UL61010-1, CAN/CSA C22.2 No.61010-1 |
1. The Detector may not operate around the setting value of “0”. Adjust the sensitivity depending on the actual application.
2. The insulation resistance and dielectric strength indicate values between power terminals and Electrode terminals, between power terminals and contact terminals, and between Electrode terminals and contact terminals. Refer to Safety Precautions on Data Sheet.