Key-type Selector Switches
A30NK
30-mm dia. Key-type Selector Switches Control panel miniaturization through a more compact design and modified wiring direction. Addition of Push-In Plus terminal blocks for easy wiring. Workability and safety improvements.
Specifications
Certified Safety Standard Ratings
UL 508 (File No. E76675), CSA C22.2 No.14
E76675), CSA C22.2 No.14
TÜV (EN60947-5-1)
AC-15 3 A 240 VAC
DC-13 4 A 24 VDC
CCC (GB/T14048.5)
AC-15 3 A 240 VAC
DC-13 4 A 24 VDC
Application Standards
UL1059 and UL486E (Push-In Plus terminal block type)
Ratings
Contacts (Standard Load)
Rated insulation voltage |
600 V |
|||||
Rated carry current |
10 A |
|||||
Rated voltage |
24 V |
120 V |
240 V |
380 V |
440 V |
|
AC at 50/60 Hz |
Resistive load (AC-12) |
10 A |
10 A |
6 A |
2A |
2 A |
Inductive load (AC-15) |
10 A |
6 A |
3 A |
1.9 A |
1.6 A |
|
DC |
Resistive load (DC-12) |
8 A |
2.2 A |
1.1 A |
--- |
--- |
Inductive load (DC-13) |
4 A |
1.1 A |
0.55 A |
--- |
--- |
Note: 1. The above ratings were obtained by conducting tests under the following conditions.
(1) Ambient temperature: 20 ±2°C
(2) Ambient humidity: 65% ±5% RH
(3) Operating frequency: 30 operations/minute
2. Minimum applicable load: 10 mA at 5 VDC.
Specifications (When Operation Unit, Mounting Collar, and Contact Blocks Are Combined)
Characteristics
Item |
Key-type Selector Switches |
|
Allowable operating |
Mechanical |
30 operations/minute max. |
Electrical |
30 operations/minute max. |
|
Insulation resistance |
100 MΩ min. (at 500 VDC) |
|
Contact resistance |
100 mΩ max. (initial value) |
|
Dielectric strength |
Between terminals |
2,500 VAC at 50/60 Hz for 1 min. (initial value) |
Between each terminal |
2,500 VAC at 50/60 Hz for 1 min. (initial value) |
|
Vibration resistance |
Malfunction |
10 to 55 Hz, 1.5-mm double amplitude (malfunction within 1 ms) |
Shock resistance |
Malfunction |
1,000 m/s2 max. (malfunction within 1 ms) |
Durability |
Mechanical |
500,000 operations min. (Switches with 3 positions: 300,000 operations min.) |
Electrical |
500,000 operations min. (Switches with 3 positions: 300,000 operations min.) |
|
Ambient operating temperature*1 |
-25 to 70°C |
|
Ambient operating humidity |
35% to 85% RH |
|
Ambient storage temperature*1 |
-40 to 80°C |
|
Degree of protection*2 |
Conforming to IP66 |
|
Electric shock protection class |
Class II |
|
PTI (tracking characteristic) |
175 |
|
Degree of contamination |
3 (EN 60947-5-1) |
|
Weight |
Approx. 75 g (for 1NC/1NO) |
*1. With no icing or condensation.
*2.Degree of protection from the front of the panel.
Operating Characteristics (for SPST-NO/ SPST-NC)
Item |
Key-type Selector Switches |
|
Manual reset |
Automatic reset |
|
Total travel force (torque) (maximum TTF) |
0.6 N·m |
0.6 N·m |
Total travel (TT) |
2 positions: Approx. 90°, 3 positions: Approx. 45° |
|
Resetting force (torque) (RF) |
0.5 N·m max. |
--- |
Examples of Linked Contact Blocks (Screw terminal block type)
Key-type Selector Switches |
||
2 positions |
3 positions |
|
Linking example |
|
|
Note: If you increase the number of Contact Blocks, evaluate the Switch under actual working conditions before permanent
installation and use the Switch within a number of switching operations that will not adversely affect the Switch’s
performance.