Multi-pole Power Relay for Contactor Current Range Capable of Carrying and Switching 40 A at 440 VAC

Ratings
Coil
Item
Rated
current

(
mA)
Coil
resistance

(Ω)
Must operate
voltage
Must release
voltage
Maximum
voltage
Power
consumption

(W)
Rated voltage
Percentage of rated voltage
12 VDC
308
39
75% max.
10% min.
110%
Approx. 3.7
24 VDC
154
156
Note: 1. Rated current and coil resistance were measured at a coil temperature of 23°C with coil resistance of ±15%.
         2. Operating characteristics were measured at a coil temperature of 23°C.

         3. The maximum allowable voltage is the maximum value of the fluctuation range for the Relay coil operating power supply and was measured at an ambient temperature of 23°C.

There is, however, no continuous allowance.
Contacts
Relay, Relay with Auxiliary Contact Block
Model
G7Z-4A-[]Z-R, G7Z-3A1B-[]Z-R, G7Z-2A2B-[]Z-R
Load
Resistive load
Inductive load cosφ = 0.3
Resistive load L/R = 1 ms
Contact structure
Double break
Contact material
Ag alloy
Rated load
NO
40 A at 440 VAC
22 A at 440 VAC
5 A at 110 VDC
NC
25 A at 440 VAC
10 A at 440 VAC
5 A at 110 VDC
Rated carry current
NO
40 A *
NC
25 A
Maximum contact voltage
480 VAC
125 VDC
Maximum contact current
NO
40 A
22 A
5 A
NC
25 A
10 A
5 A
Maximum switching capacity
NO
17,600 VA
9,680 VA
550 W
NC
11,000 VA
4,400 VA
550 W
Failure rate P value (reference value)
2 A at 24 VDC
Note: The ratings for the auxiliary contact block mounted on the G7Z are the same as those for the G73Z auxiliary contact block.
* Set of Relay and Auxiliary Contact Block: 45 to 60°C; for the continuous carry current, reduce 40 A by 0.7 A/°C. (See Fig. 1.)
Auxiliary Contact Block
Item
G73Z-20Z-R, G73Z-11Z-R, G73Z-02Z-R
Resistive load
Inductive load cosφ = 0.3
Resistive load L/R = 1 ms
Contact structure
Single break
Contact material
Au clad + AgNi
Rated load
1 A at 440 VAC
0.5 A at 440 VAC
0.5 A at 110 VDC
Rated carry current
1A
Maximum contact voltage
480 VAC
125 VDC
Maximum contact current
1A
0.5 A
Maximum switching capacity
440 VA
220 VA
55 W
Failure rate P value
(reference value)
1 mA at 1 VDC
Characteristics
Classification
Relay with auxiliary contact block *5
Auxiliary contact block
Model
G7Z-4A-[]Z-R,
G7Z-3A1B-[]Z-R,

G7Z-2A2B-[]Z-R
G73Z-20Z-R,
G73Z-11Z-R,

G73Z-02Z-R
Contact resistance *1
400 max.
100 max.
Operating time *2
50 ms max.
Release time *2
50 ms max.
Maximum
operating

frequency
Mechanical
1,800 operations/h
Rated load
1,200 operations/h
Insulation resistance *3
1,000 MΩ min.
Dielectric
strength
Between coil and contacts
4,000 VAC, 50/60 Hz for 1 min
---
Between contacts of
different polarity
4,000 VAC, 50/60 Hz for 1 min
Between contacts of the
same polarity
2,000 VAC, 50/60 Hz for 1 min
Impulse
withstand

voltage
Between coil and contacts
10 kV, 1.2 × 50 μs
---
Between contacts of
different polarity
10 kV, 1.2 × 50 μs
Between contacts of the
same polarity
4.5 kV, 1.2 × 50 μs
3.0 kV, 1.2 × 50 μs
Vibration
resistance
Destruction
10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Malfunction
NO: 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
NC: 10 to 32 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Shock
resistance
Destruction
Screw mounting: 700 m/s2, DIN Track mounting: 500 m/s2
Malfunction
NO: 100 m/s2
NC: 25 m/s
2
Durability
Mechanical
1,000,000 operations min. (at 1,800 operations/h, contact no load)
Electrical *4
AC resistive load: 80,000 operations
AC inductive load: 80,000 operations

DC resistive load: 100,000 operations

(at 1,200 operations/h, rated load)
Failure rate (P level)
(reference value) *6
2 A at 24 VDC
1 mA at 1 VDC
Ambient operating temperature
-25 to 60°C (with no icing or condensation)
Ambient operating humidity
5% to 85%
Weight
Approx. 330 g
Approx. 18 g
Note: The above values are initial values.
*1. The contact resistance for the Relay (G7Z) was measured with 1 A at 5 VDC using the voltage drop method. The contact resistance for the auxiliary contact block (G73Z) was measured with 0.1 A at 5 VDC using the voltage drop
method.
*2. The operate time was measured with the rated voltage imposed with any contact bounce ignored at the ambient temperature of 23
.
*3. The insulation resistance was measured with a 1,000-VDC
megohmmeter applied to the same places as those used for checking the dielectric strength.
*4. The electrical endurance was measured at an ambient temperature of 23
.
*5. The specifications for the auxiliary contact block mounted on the G7Z are the same as those for the G73Z auxiliary contact block.

*6. The failure rate is based on an operating frequency
of 1,800 operations/h.
Approved Standards
UL Standard: (File No. E41643)
Classifi-cation
Con-tact
Mecha-nism
of

Auxi-liary
Con-
tacts
Model
Num-ber
of

poles
Contact ratings
Number
of

test

opera-
tions
Coil
ratings
Category
Listed/
Recog-nized
Relay
with

Auxiliary

Contact

Block
Single-break
models
G7Z-4A-20Z-R
G7Z-4A-11Z-R

G7Z-4A-02Z-R

G7Z-3A1B-20Z-R

G7Z-3A1B-11Z-R

G7Z-3A1B-02Z-R

G7Z-2A2B-20Z-R

G7Z-2A2B-11Z-R

G7Z-2A2B-02Z-R
4 poles
+

2 poles

(Relay

unit +

auxi-liary
con-tact)
NO
contact
Relay
40 A,
480 VAC,

60 Hz

(Resistive)
80,000
12, 24
VDC
NLDX2,
NLDX8
Recog-nized
5 A,
120 VDC (Resistive)
100,000
22 A,
480 VAC,

60 Hz

(General

Use)
100,000
Auxiliary
Contact
D300
(1-A

current

applied)
---
NC
contact
Relay
25 A,
480 VAC,

60 Hz

(Resistive)

5 A,

120 VDC

(Resistive)

10 A,

480 VAC,

60 Hz

(General Use)
100,000
Auxiliary
Contact
D300
(1-A

current

applied)
---
Relay
---
G7Z-4A
G7Z-3A1B

G7Z-2A2B
4 poles
(Relay)
NO
contact
(Relay)
40 A,
480 VAC,

60 Hz

(Resistive)
80,000
12, 24
VDC
NLDX2,
NLDX8
Recog-nized
5 A,
120 VDC

(Resistive)
100,000
22 A,
480 VAC,

60 Hz

(General Use)
100,000
NC
contact
25 A,
480 VAC,

60 Hz

(General Use)
100,000
5 A,
120 VDC

(Resistive)
10 A,
480 VAC,

60 Hz

(General

Use)
Auxiliary
Contact

Block
Single-break
models
G73Z-20Z-R
G73Z-11Z-R

G73Z-02Z-R
2 poles
(
Auxi-liary
Con-tact

Block)
NO
contact
(Auxiliary
Contact)
D300
(1-A

current

applied)
---
---
NLDX2,
NLDX8
Recog-nized
NC
contact
D300
(1-A

current

applied)
CSA Standard: CSA Certification by cUL
EN Standard/TÜV Certification: EN 60947-4-1 (Certification No. R50079155)
Category
Contact
Mechanism

of Auxiliary

Contacts
Model
Number of
poles
Contact ratings
Relay with
Auxiliary

Contact

Block
Single-break
models
G7Z-4A-20Z-R
G7Z-4A-11Z-R

G7Z-4A-02Z-R

G7Z-3A1B-20Z-R

G7Z-3A1B-11Z-R

G7Z-3A1B-02Z-R

G7Z-2A2B-20Z-R

G7Z-2A2B-11Z-R

G7Z-2A2B-02Z-R
4 poles + 2 poles
(Relay unit +

auxiliary contact)
NO contact
Relay
AC-1: 40 A 440 V 50/60 Hz
AC-3: 16 A 440 V 50/60 Hz

DC-1: 5 A 110 V
Auxiliary
Contact
AC-15: 0.3 A 440 V 50/60 Hz
DC-13: 0.3 A 110 V
NC contact
Relay
AC-1: 25 A 440 V 50/60 Hz
DC-1: 5 A 110 V
Auxiliary
Contact
AC-15: 0.3 A 440 V 50/60 Hz
DC-13: 0.3 A 110 V
Relay
---
G7Z-4A
G7Z-3A1B

G7Z-2A2B
4 poles
(Relay)
NO contact
(Relay)
AC-1: 40 A 440 V 50/60 Hz
AC-3: 16 A 440 V 50/60 Hz

DC-1: 5 A 110 V
NC contact
AC-1: 25 A 440 V 50/60 Hz
DC-1: 5 A 110 V
Auxiliary
Contact

Block
Single-break
models
G73Z-20Z-R
G73Z-11Z-R

G73Z-02Z-R
2 poles
(Auxiliary Contact

Block)
NO contact
(Auxiliary
Contact)
AC-15: 0.3 A 440 V 50/60 Hz
DC-13: 0.3 A 110 V
NC contact
AC-15: 0.3 A 440 V 50/60 Hz
DC-13: 0.3 A 110 V
CCC Certification
Classification
Contact Mechanism
of Auxiliary Contacts
Model
Standard No.
Certification No.
Relay with Auxiliary
Contact Block
Single-break models
G7Z-4A-20Z-R
G7Z-4A-11Z-R

G7Z-4A-02Z-R

G7Z-3A1B-20Z-R

G7Z-3A1B-11Z-R

G7Z-3A1B-02Z-R

G7Z-2A2B-20Z-R

G7Z-2A2B-11Z-R

G7Z-2A2B-02Z-R
GB/T 14048.4
2009010304361493
Relay
---
G7Z-4A
G7Z-3A1B

G7Z-2A2B
GB/T 14048.4