Product Category

Emergency Stop Pushbutton Switches (22-dia. or 25-dia.)

A22NE-PD / A22NE-P / A22E

Install in 22-dia. or 25-dia. Panel Cutout (When Using a Ring)

A22NE-PD Push-in Plus Terminal Block Models

Certified Standard Ratings

• UL508 (File No. E76675), CSA C22.2 No.14
    5 A at 125 VAC, 3 A at 250 VAC B300
 • TÜV (EN60947-5-1) - Certified direct opening -
          (EN60947-5-5)
    AC-15 3 A at 125 VAC
    DC-13 1 A at 30 VDC
 • CCC (GB/T14048.5)
    AC-15 3 A at 125 VAC
    DC-13 1 A at 30 VDC

Applicable Standards

UL1059, UL486E
 
 Note: Use a 10 A fuse type gI or gG that conforms to IEC60269 as a short-circuit protection device.
          This fuse is not provided in the main unit.

Certified Standards

Certification body

Standards

File No.

UL *

UL508, C22.2 No.14

E76675

TÜV SÜD

EN60947-5-1(Certified direct opening),
 EN60947-5-5

Consult your OMRON representative for details.

CQC (CCC)

GB/T14048.5

Consult your OMRON representative for details.

Note: Only models with NC contacts have a direct opening mechanism.
 * UL-certification for CSA C22.2 No. 14 has been obtained. 

Ratings

Contacts (Standard Load)

Rated
 insulation
 voltage (V)

Rated carry
 current (A)

Rated
 voltage
 (V)

Rated current (A)

AC15
 (Inductive load)

AC12
 (Resistive load)

DC13
 (Inductive load)

DC12
 (Resistive load)

250

5

30 VAC

---

---

---

---

125 VAC

3 A

5 A

---

---

250 VAC

1.5 A

3 A

---

---

30 VDC

---

---

1 A

2 A

125 VDC

---

---

0.22 A

0.4 A

250 VDC

---

---

0.1 A

0.2 A

Note: 1. The above ratings were obtained by conducting tests under the following conditions.
 (1) Ambient temperature: 20°±2°C
 (2) Ambient humidity: 65±5%
 (3) Operating frequency: 20 operations/minute
 Note: 2. Minimum applicable load: 1 mA at 5 VDC (Resistive load)
         The operating range may vary depending on the usage conditions and type of load. 

LED Lamp (A22NZ-L-RC)

Rated voltage

Operating voltage

Current value

24 VAC/VDC

24 VAC/VDC ± 10%

Approx. 12 mA

Characteristics

Operation

Turn-reset

Pull-reset

Non-lighted model

Lighted Model

Non-lighted model

Non-lighted model
 (Models with IP69K)

A22NE-[]-PD[][]-N-[]

A22NE-M-PD[][]-C-[]

A22NE-MP-PD[][]-N-[]

A22NE-MP-PD[][]-N-69K

Allowable
 operating
 frequency

Mechanical

30 operations/minute or less (One operation consists of set and reset operations.)

Electrical

30 operations/minute or less (One operation consists of set and reset operations.)

Insulation resistance *1

100 MΩ min. (at 500 VDC)

Contact resistance

100 mΩ max. (initial value)

Dielectric
 strength

Between
 terminals of
 same polarity*1

2,000 VAC, 50/60 Hz 1 minute (initial value)

Between
 terminals of
 different polarity

2,000 VAC, 50/60 Hz 1 minute (initial value)

Between each
 terminal and
 ground

2,000 VAC, 50/60 Hz 1 minute (initial value)

Vibration
 resistance

Malfunction

10 to 55 Hz, 1.5 mm double amplitude (contact separation within 1 ms)

Shock
 resistance

Malfunction

250 m/s2 max. (contact separation within 1 ms)

Durability

Mechanical

300,000 operations min. (One operation consists of set and reset operations.)

100,000 operations min.
 (One operation consists of
 set and reset operations.)

Electrical
 (100 mA at 24
 VAC (Resistive
 load))

250,000 operations min. (One operation consists of set and reset operations.)

100,000 operations min.
 (One operation consists of
 set and reset operations.)

Electrical
 (3 mA at 250
 VAC (Resistive
 load))

100,000 operations min. (One operation consists of set and reset operations.)

Ambient operating temperature *2

-20 to +70°C

-20 to +55°C

-20 to +70°C

-20 to +70°C *3

Ambient operating humidity

35 to 85% RH

Ambient storage temperature *2

-40 to +70°C

Degree of protection *4

IP65 oil-resistant models

IP65

IP65 oil-resistant models

IP69K

Electric shock protection class

Class II

PTI (tracking characteristic)

175

Degree of contamination

3 (EN 60947-5-1)

Minimum direct opening stroke

11 mm

Minimum direct opening force

45 N

Conditional short-circuit current

100 A (EN 60947-5-1)

Wight (for a 40-dia. head
 2NC/2NO Operation Unit)

Approx. 95 g

Approx. 95 g

Approx. 125 g

Approx. 135 g

*1. State when an LED is not added between terminals of the same polarity on a lighting unit.
 *2. With no icing or condensation.
 *3. Capable of operation at up to 80°C under IP[]9K testing conditions per JIS D 5020.
 *4. The degree of protection from the front of the panel. 

Operating Characteristics

Item

Turn-reset

Pull-reset

Lighted / non-lighted models

Non-lighted model

Non-lighted model
 (Models with IP69K)

Total travel force (TTF)

45 N max.

60 N max.

70 N max.

Return force (RF)

0.25N·m max. *

60 N max.

70 N max.

Total travel (TT)

10 ±1 mm

5.5 ±1 mm

* Rotation torque value. 

Terminal Arrangement (BOTTOM VIEW)

Terminal Arrangement

 image

A22NE-P Push-in Plus Terminal Block Models

Certified Standard Ratings

• UL508 (File No. E76675), CSA C22.2 No.14
    6 A at 240 VAC, 10 A at 120 VAC
 • TÜV (EN60947-5-1) - Certified direct opening -
          (EN60947-5-5)
    AC-15 3 A at 240 VAC
    DC-13 4 A at 24 VDC
 • CCC (GB/T14048.5)
    AC-15 3 A at 240 VAC
    DC-13 4 A at 24 VDC

Applicable Standards

UL1059, UL486E (Push-in Plus Terminal Block Types)
 
 Note: Use a 10 A fuse type gI or gG that conforms to IEC60269 as a short-circuit protection device. This fuse is not
          provided in the main unit.

Certified Standards

Certification body

Standards

File No.

UL *

UL508, C22.2 No.14

E76675

TÜV SÜD

EN60947-5-1 (Certified direct opening),
 EN60947-5-5

Consult your OMRON representative for details.

CQC (CCC)

GB/T14048.5

Consult your OMRON representative for details.

Note: Only models with NC contacts have a direct opening mechanism.
 * UL-certification for CSA C22.2 No. 14 has been obtained. 

Ratings

Contacts (Standard Load)

Rated
 insulation
 voltage (V)

Rated carry
 current (A)

Rated
 voltage
 (V)

Rated current (A)

AC15
 (Inductive load)

AC12
 (Resistive load)

DC13
 (Inductive load)

DC12
 (Resistive load)

600

10

24 VAC

10

10

---

---

120 VAC

6

10

240 VAC

3

6

380 VAC

1.9

2

440 VAC

1.6

2

24 VDC

---

---

4

8

120 VDC

1.1

2.2

240 VDC

0.55

1.1

Note: 1. The above ratings were obtained by conducting tests under the following conditions.
              (1) Ambient temperature: 20°±2°C
              (2) Ambient humidity: 65±5%
              (3)Operating frequency: 20 operations/minute
          2. Minimum applicable load: 10 mA at 5 VDC (Resistive load)
              The operating range may vary depending on the usage conditions and type of load.

LED Lamp

Rated voltage

Operating voltage

Current value

6 VAC/VDC

6 VAC/VDC ± 10%

Approx. 11 mA

12 VAC/VDC

12 VAC/VDC ± 10%

Approx. 12 mA

24 VAC/VDC

24 VAC/VDC ± 10%

Approx. 12 mA

100 VAC

100 VAC ± 10%

Approx. 12 mA

110 VAC

110 VAC ± 10%

120 VAC

100 VAC to 130 VAC

200 VAC

200 VAC ± 10%

Approx. 12 mA

220 VAC

220 VAC ± 10%

230 VAC

230 VAC ± 10%

240 VAC

220 VAC to 250 VAC

Characteristics

Operation

Turn-reset

Pull-reset

Non-lighted model

Lighted Model

Non-lighted model

A22NE-[]-P[][][]-N

A22NE-M-P[][][]-[]

A22NE-MP-P[][][]-N

A22NE-MP-P[][][]-N-69K

Allowable
 operating
 frequency

Mechanical

30 operations/minute or less
 (One operation consists of set and reset operations.)

Electrical

30 operations/minute or less
 (One operation consists of set and reset operations.)

Insulation resistance *1

100 MΩ min. (at 500 VDC)

Contact resistance

100 mΩ max. (initial value)

Dielectric
 strength

Between
 terminals of
 same polarity
 *1

2,500 VAC, 50/60 Hz 1 minute (initial value)

Between each
 terminal and
 ground

2,500 VAC, 50/60 Hz 1 minute (initial value)

Vibration
 resistance

Malfunction

10 to 55 Hz, 1.5 mm double amplitude (contact separation within 1 ms)

Shock
 resistance

Malfunction

250 m/s2 max. (contact separation within 1 ms)

Durability

Mechanical

300,000 operations min.
 (One operation consists of set and reset operations.)

100,000 operations min.
 (One operation consists of
 set and reset operations.)

Electrical

300,000 operations min.
 (One operation consists of set and reset operations.)

100,000 operations min.
 (One operation consists of
 set and reset operations.)

Ambient operating
 temperature *2

-20 to +70°C

-20 to +55°C

-20 to +70°C

-20 to +70°C *3

Ambient operating
 humidity

35 to 85% RH

Ambient storage
 temperature *2

-40 to +70°C

Degree of protection*4

IP65 oil-resistant models *5

IP65

IP65 oil-resistant models *5

IP69K

Electric shock
 protection class

Class II

PTI
 (tracking characteristic)

175

Degree of contamination

3 (EN 60947-5-1)

Minimum direct
 opening stroke

11 mm

Minimum direct
 opening force

45 N

Conditional
 short-circuit current

100 A (EN 60947-5-1)

Wight (for a 40-dia. Head
 1NC/1NO Operation Unit)

Approx. 55 g

Approx. 60 g

Approx. 85 g

Approx. 115 g

*1. State when an LED is not added between terminals of the same polarity on a lighting unit. Does not apply to
       lighted-type 100 to 200 V lighting units.
 *2. With no icing or condensation.
 *3. Capable of operation at up to 80°C under IP[]9K testing conditions per JIS D 5020.
 *4. The degree of protection from the front of the panel.
 *5. The degree of protection is IP65 even with an integrated control box, but the system is not oil resistant.

Operating Characteristics

Item

Turn-reset

Pull-reset

Lighted /
 non-lighted models

Non-lighted model

Non-lighted model
 (Models with IP69K)

Total travel force (TTF)

45 N max.

60 N max.

70 N max.

Return force (RF)

0.25N·m * max.

60 N max.

70 N max.

Total travel (TT)

10 ±1 mm

5.5 ±1 mm

5.5 ±1 mm

* Rotation torque value. 

Terminal Arrangement (BOTTOM VIEW)

image

Terminal connection

image

Terminal wiring drawings of two-contact Switch Units

image

A22E Screw Terminal Block types

Certified Standard Ratings

• UL, cUL (File No. E41515)
    6 A at 220 VAC, 10 A at 110 VAC
 • TÜV (EN60947-5-1) (Low Voltage Directive)
    3 A at 220 VAC
 • CCC (GB14048.5)
    3 A at 240 VAC, 1.5 A at 24 VDC

Certified Standards

Certification body

Standards

File No.

UL *1

UL508, C22.2 No.14

E41515

TÜV SÜD

EN60947-5-1 (Certified direct opening),
 EN60947-5-5

Consult your OMRON representative for details.

CQC (CCC)

GB/T14048.5

2003010303070635

KOSHA *2

EN60947-5-1

Consult your OMRON representative for details.

Note: 1. Only models with NC contacts have a direct opening mechanism.
          2. A fuse is not provided.
 *1. UL-certification for CSA C22.2 No. 14 has been obtained.
       Certification has been obtained for individual Switch Blocks and Lighting Units.
 *2. Some models have been certified. 

Ratings

Contacts (Standard Load)

Rated carry
 current (A)

Rated
 voltage (V)

Rated current (A)

AC15
 (Inductive load)

AC12
 (Resistive load)

DC13
 (Inductive load)

DC12
 (Resistive load)

10

24 VAC

10

10

---

---

110 VAC

5

10

220 VAC

3

6

380 VAC

2

3

440 VAC

1

2

24 VDC

---

---

1.5

10

110 VDC

0.5

2

220 VDC

0.2

0.6

380 VDC

0.1

0.2

Note: 1. Rated current values are determined according to the testing conditions. The above ratings were obtained by
             conducting tests under the following conditions.
             (1) Ambient temperature: 20°±2°C
             (2) Ambient humidity: 65±5%
             (3)Operating frequency: 20 operations/minute
          2. Minimum applicable load: 10 mA at 5 VDC

Contacts (Microload)

Rated applicable load

100 mA at 30 VDC (Resistive load)

Minimum applicable load

1 mA at 5 VDC

LED Lamp

Rated voltage

Operating voltage

Current value

6 VAC/VDC

6 VAC/VDC ± 5%

Approx. 8 mA

12 VAC/VDC

12 VAC/VDC ± 5%

24 VAC/VDC

24 VAC/VDC ± 5%

Voltage-reduction lighting

Rated voltage

Operating voltage

Rated current

Applicable lamp
 (BA9S/Base: 13)

110 VAC

100 VAC
 (95 to 115 V)

Approx. 8 mA

LED lamp
 A22-24A[]

220 VAC

200 VAC
 (190 to 230 V)

Characteristics

Type 

Turn-reset

Pull-reset

Non-lighted model

Lighted model

Non-lighted model

Allowable
 operating
 frequency 

Mechanical 

30 operations/minute (One operation consists of set and reset operations.)

Electrical 

30 operations/minute (One operation consists of set and reset operations.)

Insulation resistance 

100 MΩ min. (at 500 VDC)

Contact resistance 

100 mΩ max. (initial value)

Dielectric
 strength 

Between terminals
 of same polarity 

2,500 VAC, 50/60 Hz for 1 min.

Between each
 terminal and ground 

2,500 VAC, 50/60 Hz for 1 min.

Vibration resistance 

10 to 55 Hz, 1.5-mm double amplitude (contact separation within 1 ms)

Shock
 resistance 

Destruction 

1000 m/s2

Malfunction 

250 m/s2 max. (contact separation within 1 ms)

Durability 

Mechanical 

300,000 operations min. (One operation consists of set and reset operations.)

Electrical 

300,000 operations min. (One operation consists of set and reset operations.)

Ambient operating temperature *1 

-20 to +70°C

-20 to +55°C

-20 to +70°C

Ambient operating humidity 

35 to 85% RH

Ambient storage temperature 

-40 to +70°C

Degree of protection 

IP65 oil-resistant models *2 *3

IP65 *2

IP65 oil-resistant models *2 *3

Electric shock protection class 

Class II

PTI (tracking characteristic) 

175

Degree of contamination 

3 (EN60947-5-1)

Minimum direct opening stroke 

11 mm

Minimum direct opening force 

45 N

Conditional short-circuit current 

100 A (EN 60947-5-1)

Weight (for a 40-dia. head 1NC/1NO
 Operation Unit) 

Approx. 65 g

Approx. 80 g

Approx. 100 g

*1. With no icing or condensation.
 *2. The degree of protection from the front of the panel.
 *3. The degree of protection is IP65 even with an integrated control box, but the system is not oil resistant. 

Operating Characteristics

Item

Turn-reset

Pull-reset

Total travel force (TTF)

44.1 N max.

58.8 N max.

Return force (RF)

0.25 N·m max. *

58.8 N max.

Total travel (TT)

10 ±1 mm

5.5 ±1 mm

* Rotation torque value. 

Terminal Arrangement (BOTTOM VIEW)

image

Terminal connection

image

Terminal wiring drawings of two-contact Switch Units

image