Ratings
Input (at an Ambient Temperature of 25°C)
Model | Rated voltage | Operating voltage | Impedance (See note 1.) Input current | Voltage level | |
Must operate voltage | Must release voltage | ||||
G3NA-2[][]B-UTU(-2) G3NA-475B-UTU-2 G3NA-490B-UTU-2 | 5 to 24 VDC | 4 to 32 VDC | 7 mA max. (See note 2.) | 4 VDC max. | 1 VDC min. |
100 to 240 VAC | 75 to 264 VAC | 72 kΩ±20% | 75 VAC max. | 20 VAC min. | |
G3NA-410B-UTU G3NA-420B-UTU G3NA-425B-UTU-2 G3NA-440B-UTU-2 G3NA-450B-UTU-2 G3NA-D210B-UTU | 5 to 24 VDC | 4 to 32 VDC | 5 mA max. (See note 2.) | 4 VDC max. | 1 VDC min. |
100 to 240 VAC | 75 to 264 VAC | 72 kΩ±20% | 75 VAC max. | 20 VAC min. |
Note: 1. The input impedance is measured at the maximum value of the rated supply voltage (for example, with the model rated at 100 to 240 VAC, the input impedance is measured at 240 VAC).
2. With constant current input circuit system.
2. With constant current input circuit system.
Output
Model | Applicable load | |||||
Rated load voltage | Load voltage range | Load current (See note 1.) | Inrush current | VDRM, VCEO (reference value) | ||
With heat sink (See note 2.) | Without heat sink | |||||
G3NA-205B-UTU | 24 to 240 VAC | 19 to 264 VAC | 0.1 to 5 A (at 40°C) | 0.1 to 3 A (at 40°C) | 60 A (60 Hz, 1 cycle) | 600 V (VDRM) |
G3NA-210B-UTU | 0.1 to 10 A (at 40°C) | 0.1 to 4 A (at 40°C) | 150 A (60 Hz, 1 cycle) | |||
G3NA-220B-UTU | 0.1 to 20 A (at 40°C) | 0.1 to 4 A (at 40°C) | 220 A (60 Hz, 1 cycle) | |||
G3NA-225B-UTU | 0.1 to 25 A (at 40°C) | 0.1 to 4 A (at 40°C) | 220 A (60 Hz, 1 cycle) | |||
G3NA-240B-UTU | 0.1 to 40 A (at 40°C) | 0.1 to 6 A (at 40°C) | 440 A (60 Hz, 1 cycle) | |||
G3NA-250B-UTU | 0.1 to 50 A (at 40°C) | 0.1 to 6 A (at 40°C) | 440 A (60 Hz, 1 cycle) | |||
G3NA-275B-UTU-2 | 1 to 75 A (at 40°C) | 1 to 7 A (at 40°C) | 800 A (60 Hz, 1 cycle) | |||
G3NA-290B-UTU-2 | 1 to 90 A (at 40°C) | 1 to 7 A (at 40°C) | 1,000 A (60 Hz, 1 cycle) | |||
G3NA-410B-UTU | 200 to 480 VAC | 180 to 528 VAC | 0.2 to 10 A (at 40°C) | 0.2 to 4 A (at 40°C) | 150 A (60 Hz, 1 cycle) | 1,200 V (VDRM) |
G3NA-420B-UTU | 0.2 to 20 A (at 40°C) | 0.2 to 4 A (at 40°C) | 220 A (60 Hz, 1 cycle) | |||
G3NA-425B-UTU-2 | 0.2 to 25 A (at 40°C) | 0.2 to 4 A (at 40°C) | 220 A (60 Hz, 1 cycle) | |||
G3NA-440B-UTU-2 | 0.2 to 40 A (at 40°C) | 0.2 to 6 A (at 40°C) | 440 A (60 Hz, 1 cycle) | |||
G3NA-450B-UTU-2 | 0.2 to 50 A (at 40°C) | 0.2 to 6 A (at 40°C) | 440 A (60 Hz, 1 cycle) | |||
G3NA-475B-UTU-2 | 1 to 75 A (at 40°C) | 1 to 7 A (at 40°C) | 800 A (60 Hz, 1 cycle) | |||
G3NA-490B-UTU-2 | 1 to 90 A (at 40°C) | 1 to 7 A (at 40°C) | 1,000 A (60 Hz, 1 cycle) | |||
G3NA-D210B-UTU | 5 to 200 VDC | 4 to 220 VDC | 0.1 to 10 A (at 40°C) | 0.1 to 4 A (at 40°C) | 20 A (10 ms) | 400 V (VCEO) |
Note: 1. The load current varies depending on the ambient temperature. Refer to Load Current vs. Ambient Temperature
under Engineering Data on Data Sheet.
2. When an OMRON Heat Sink (refer to Options (Order Separately)) or a heat sink of the specified size is used.
under Engineering Data on Data Sheet.
2. When an OMRON Heat Sink (refer to Options (Order Separately)) or a heat sink of the specified size is used.
Characteristics
Item | G3NA- 205B- UTU | G3NA- 210B- UTU | G3NA- 220B- UTU | G3NA- 225B- UTU | G3NA- 240B- UTU | G3NA- 250B- UTU | G3NA- 275B- UTU-2 | G3NA- 290B- UTU-2 | |
Operate time | 1/2 of load power source cycle + 1 ms max. (DC input) 3/2 of load power source cycle + 1 ms max. (AC input) | ||||||||
Release time | 1/2 of load power source cycle + 1 ms max. (DC input) 3/2 of load power source cycle + 1 ms max. (AC input) | ||||||||
Output ON voltage drop | 1.6 V (RMS) max. | ||||||||
Leakage current | 5 mA max. (at 100 VAC) 10 mA max. (at 200 VAC) | ||||||||
Insulation resistance | 100 MΩ min. (at 500 VDC) | ||||||||
Dielectric strength | 2,500 VAC, 50/60 Hz for 1 min | ||||||||
Vibration resistance | Destruction: 10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude) | ||||||||
Shock resistance | Destruction: 1,000 m/s2 | ||||||||
Ambient temperature | Operating:-30°C to 80°C (with no icing or condensation) Storage:-30°C to 100°C (with no icing or condensation) | ||||||||
Ambient humidity | Operating: 45% to 85% | ||||||||
Weight | Approx. 60 g | Approx. 70 g | Approx. 120 g | ||||||
Item | G3NA- 410B- UTU | G3NA- 420B- UTU | G3NA- 425B- UTU-2 | G3NA- 440B- UTU-2 | G3NA- 450B- UTU-2 | G3NA- 475B- UTU-2 | G3NA- 490B- UTU-2 | G3NA- D210B-UTU | |
Operate time | 1/2 of load power source cycle + 1 ms max. (DC input) 3/2 of load power source cycle + 1 ms max. (AC input) | 1 ms max. (DC input) 30 ms max. (AC input) | |||||||
Release time | 1/2 of load power source cycle + 1 ms max. (DC input) 3/2 of load power source cycle + 1 ms max. (AC input) | 5 ms max. (DC input) 30 ms max. (AC input) | |||||||
Output ON voltage drop | 1.8 V (RMS) max. | 1.5 V max. | |||||||
Leakage current | 10 mA max. (at 200 VAC) 20 mA max. (at 400 VAC) | 5 mA max. (at 200 VDC) | |||||||
Insulation resistance | 100 MΩ min. (at 500 VDC) | ||||||||
Dielectric strength | 4,000 VAC, 50/60 Hz for 1 min | 2,500 VAC, 50/60 Hz for 1 min | |||||||
Vibration resistance | Destruction: 10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude) | ||||||||
Shock resistance | Destruction: 1,000 m/s2 | ||||||||
Ambient temperature | Operating:-30°C to 80°C (with no icing or condensation) Storage:-30°C to 100°C (with no icing or condensation) | ||||||||
Ambient humidity | Operating: 45% to 85% | ||||||||
Weight | Approx. 80 g | Approx. 120 g | Approx. 70 g |