Ratings (at an Ambient Temperature of 25°C)
Input
Rated
voltage
Operating voltage
Voltage level
Input impedance
Must operate
Must release
With zero cross
function
Without zero cross
function
5 VDC
4 to 6 VDC
4 VDC max.
1 VDC min.
250 Ω±20%
300 Ω±20%
12 VDC
9.6 to 14.4 VDC
9.6 VDC max.
600 Ω±20%
800 Ω±20%
24 VDC
19.2 to 28.8 VDC
19.2 VDC max.
1.6 kΩ±20%
Note: Each model has 5-VDC, 12-VDC, and 24-VDC input versions.
Output
Model
Applicable load
Rated load
voltage
Load voltage
range
Load current
(See note 1.)
Inrush current
With heat sink
Without heat sink
G3NE-205T(L)(-2)-US
100 to 240 VAC
75 to 264 VAC
0.1 to 5 A
at 40 ° C
0.1 to 5 A
at 40 ° C
60 A
(60 Hz, 1 cycle)
G3NE-210T(L)(-2)-US
0.1 to 10 A
at 40 ° C

(See note 2.)
0.1 to 5 A
at 40 ° C
150 A
(60 Hz, 1 cycle)
G3NE-220T(L)(-2)-US
0.1 to 20 A
at 40 ° C

(See note 2.)
0.1 to 5 A
at 40 ° C
220 A
(60 Hz, 1 cycle)
Note: 1. The load current varies depending on the ambient temperature. Refer to Load Current vs. Ambient Temperature
              under Engineering Data for details on Data Sheet.

          2. These values apply when using a dedicated heat sink or a radiation plate of specified size.
Characteristics
Item
G3NE-2[][]T(-2)-US
G3NE-2[][]TL(-2)-US
Operate time
1/2 of load power source cycle + 1 ms max.
1 ms max.
Release time
1/2 of load power source cycle + 1 ms max.
Output ON voltage drop
1.6 V (RMS) max.
Leakage current
2 mA max. (at 100 VAC)
5 mA max. (at 200 VAC)
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min
Vibration resistance
Destruction: 10 to 55 to 10 Hz, 0.75-mm single amplitude
Shock resistance
Destruction: 1,000 m/s2
Ambient temperature
Operating: -30°C to 80°C (with no icing or condensation)
Storage: -30°C to 100°C (with no icing or condensation)
Ambient humidity
Operating: 45% to 85%
Certified standards
UL508 File No.E64562/CSA C22.2 (No.0, No.14) File No. LR35535
TÜV R9051064 (VDE0435) (EN60950)
EMC
Emission: EN55011 Group 1 Class B
Immunity: EN61000-6-2
Weight
Approx. 37 g