Solid State Relays for Heaters

G3PE (Single-phase)

Compact, Slim-profile SSRs with Heat Sinks. Models with No Zero Cross for a Wide Range of Applications.

Certification
UL508, CSA22.2 No.14, and EN60947-4-3
Ratings
Input (at an Ambient Temperature of 25°C)
Model
Rated voltage
Operating
voltage range
Rated input
current
Voltage level
Must operate voltage
Must release voltage
G3PE-[][][]B
12 to 24 VDC
9.6 to 30 VDC
7 mA max.
9.6 VDC max.
1.0 VDC max.
G3PE-[][][]BL
15 mA max.
Output
Model
G3PE-
215B(L)
G3PE-
225B(L)
G3PE-
235B(L)
G3PE-
245B(L)
G3PE-
515B(L)
G3PE-
525B(L)
G3PE-
535B(L)
G3PE-
545B(L)
Rated load
voltage
100 to 240 VAC (50/60 Hz)
200 to 480 VAC (50/60 Hz)
Load voltage
range
75 to 264 VAC (50/60 Hz)
180 to 528 VAC (50/60 Hz)
Applicable
load current *
0.1 to 15 A
(at 40 °C)
0.1 to 25 A
(at 40 °C)
0.5 to 35 A
(at 25 °C)
0.5 to 45 A
(at 25 °C)
0.1 to 15 A
(at 40 °C)
0.1 to 25 A
(at 40 °C)
0.5 to 35 A
(at 25 °C)
0.5 to 45 A
(at 25 °C)
Inrush current
resistance
150 A
(60 Hz,

1 cycle)
220 A
(60 Hz,

1 cycle)
440 A
(60 Hz, 1 cycle)
150 A
(60 Hz,

1 cycle)
220 A
(60 Hz,

1 cycle)
440 A
(60 Hz, 1 cycle)
Permissible I2t
(reference value)
121A2s
260A2s
1,260A2s
128A2s
1,350A2s
6,600A2s
Applicable load
(resistive load)
3 kW
(at 200

VAC)
5 kW
(at 200

VAC)
7 kW
(at 200

VAC)
9 kW
(at 200

VAC)
6 kW
(at 400

VAC)
10 kW
(at 400

VAC)
14 kW
(at 400

VAC)
18 kW
(at 400

VAC)
* The applicable load current depends on the ambient temperature. For details, refer to Load Current vs. Ambient
   Temperature in Engineering Data on Data Sheet.
Characteristics
Model
G3PE
-215B
G3PE
-225B
G3PE
-235B
G3PE
-245B
G3PE
-215BL
G3PE
-225BL
G3PE
-235BL
G3PE
-245BL
Operate time
1/2 of load power source cycle + 1 ms max.
1 ms max.
Release time
1/2 of load power source cycle + 1 ms max.
Output ON voltage drop
1.6 V (RMS) max.
Leakage current
10 mA max. (at 200 VAC)
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,500 VAC, 50/60 Hz for 1 min
Vibration resistance
10 to 55 to10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)
(Mounted to DIN track)
Shock resistance
Destruction: 294 m/s2 (Mounted to DIN track)
Ambient storage
temperature
- 30 to 100 °C (with no icing or condensation)
Ambient operating
temperature
- 30 to 80 °C (with no icing or condensation)
Ambient operating
humidity
45% to 85%
Weight
Approx. 240 g
Approx. 400 g
Approx. 240 g
Approx. 400 g
Model
G3PE
-515B
G3PE
-525B
G3PE
-535B
G3PE
-545B
G3PE
-515BL
G3PE
-525BL
G3PE
-535BL
G3PE
-545BL
Operate time
1/2 of load power source cycle + 1 ms max.
1 ms max.
Release time
1/2 of load power source cycle + 1 ms max.
Output ON voltage drop
1.8 V (RMS) max.
Leakage current
20 mA max. (at 480 VAC)
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,500 VAC, 50/60 Hz for 1 min
Vibration resistance
10 to 55 to10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)
(Mounted to DIN track)
Shock resistance
Destruction: 294 m/s2 (Mounted to DIN track)
Ambient storage
temperature
- 30 to 100 °C (with no icing or condensation)
Ambient operating
temperature
- 30 to 80 °C (with no icing or condensation)
Ambient operating
humidity
45% to 85%
Weight
Approx. 240 g
Approx. 400 g