Ratings
Input (at an Ambient Temperature of 25°C)
Model | Rated voltage | Operating voltage range | Rated input current | Voltage level | |
Must operate voltage | Must release voltage | ||||
G3PE-[][][]B | 12 to 24 VDC | 9.6 to 30 VDC | 7 mA max. | 9.6 VDC max. | 1.0 VDC max. |
G3PE-[][][]BL | 15 mA max. |
Output
Model | G3PE- 215B(L) | G3PE- 225B(L) | G3PE- 235B(L) | G3PE- 245B(L) | G3PE- 515B(L) | G3PE- 525B(L) | G3PE- 535B(L) | G3PE- 545B(L) |
Rated load voltage | 100 to 240 VAC (50/60 Hz) | 200 to 480 VAC (50/60 Hz) | ||||||
Load voltage range | 75 to 264 VAC (50/60 Hz) | 180 to 528 VAC (50/60 Hz) | ||||||
Applicable load current * | 0.1 to 15 A (at 40 °C) | 0.1 to 25 A (at 40 °C) | 0.5 to 35 A (at 25 °C) | 0.5 to 45 A (at 25 °C) | 0.1 to 15 A (at 40 °C) | 0.1 to 25 A (at 40 °C) | 0.5 to 35 A (at 25 °C) | 0.5 to 45 A (at 25 °C) |
Inrush current resistance | 150 A (60 Hz, 1 cycle) | 220 A (60 Hz, 1 cycle) | 440 A (60 Hz, 1 cycle) | 150 A (60 Hz, 1 cycle) | 220 A (60 Hz, 1 cycle) | 440 A (60 Hz, 1 cycle) | ||
Permissible I2t (reference value) | 121A2s | 260A2s | 1,260A2s | 128A2s | 1,350A2s | 6,600A2s | ||
Applicable load (resistive load) | 3 kW (at 200 VAC) | 5 kW (at 200 VAC) | 7 kW (at 200 VAC) | 9 kW (at 200 VAC) | 6 kW (at 400 VAC) | 10 kW (at 400 VAC) | 14 kW (at 400 VAC) | 18 kW (at 400 VAC) |
* The applicable load current depends on the ambient temperature. For details, refer to Load Current vs. Ambient
Temperature in Engineering Data on Data Sheet.
Temperature in Engineering Data on Data Sheet.
Characteristics
Model | G3PE -215B | G3PE -225B | G3PE -235B | G3PE -245B | G3PE -215BL | G3PE -225BL | G3PE -235BL | G3PE -245BL |
Operate time | 1/2 of load power source cycle + 1 ms max. | 1 ms max. | ||||||
Release time | 1/2 of load power source cycle + 1 ms max. | |||||||
Output ON voltage drop | 1.6 V (RMS) max. | |||||||
Leakage current | 10 mA max. (at 200 VAC) | |||||||
Insulation resistance | 100 MΩ min. (at 500 VDC) | |||||||
Dielectric strength | 2,500 VAC, 50/60 Hz for 1 min | |||||||
Vibration resistance | 10 to 55 to10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) (Mounted to DIN track) | |||||||
Shock resistance | Destruction: 294 m/s2 (Mounted to DIN track) | |||||||
Ambient storage temperature | - 30 to 100 °C (with no icing or condensation) | |||||||
Ambient operating temperature | - 30 to 80 °C (with no icing or condensation) | |||||||
Ambient operating humidity | 45% to 85% | |||||||
Weight | Approx. 240 g | Approx. 400 g | Approx. 240 g | Approx. 400 g | ||||
Model | G3PE -515B | G3PE -525B | G3PE -535B | G3PE -545B | G3PE -515BL | G3PE -525BL | G3PE -535BL | G3PE -545BL |
Operate time | 1/2 of load power source cycle + 1 ms max. | 1 ms max. | ||||||
Release time | 1/2 of load power source cycle + 1 ms max. | |||||||
Output ON voltage drop | 1.8 V (RMS) max. | |||||||
Leakage current | 20 mA max. (at 480 VAC) | |||||||
Insulation resistance | 100 MΩ min. (at 500 VDC) | |||||||
Dielectric strength | 2,500 VAC, 50/60 Hz for 1 min | |||||||
Vibration resistance | 10 to 55 to10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) (Mounted to DIN track) | |||||||
Shock resistance | Destruction: 294 m/s2 (Mounted to DIN track) | |||||||
Ambient storage temperature | - 30 to 100 °C (with no icing or condensation) | |||||||
Ambient operating temperature | - 30 to 80 °C (with no icing or condensation) | |||||||
Ambient operating humidity | 45% to 85% | |||||||
Weight | Approx. 240 g | Approx. 400 g | Approx. 240 g | Approx. 400 g |