Solid State Contactors for Heaters

G3PE (Three-phase)

Compact, Slim-profile SSRs with Heat Sinks. Solid State Contactors for Three-phase Heaters Reduced Installation Work with DIN Track Mounting.

Certification
UL508, CSA22.2 No.14, and EN60947-4-3
Ratings (at an Ambient Temperature of 25°C)
Operating Circuit (All Models)
Model
Same for all models
Rated operating voltage
12 to 24 VDC
Operating voltage range
9.6 to 30 VDC
Rated input current (impedance)
10 mA max. (24 VDC)
Must-operate voltage
9.6 VDC max.
Must-release voltage
1 VDC min.
Insulation method
Phototriac
Operation indicator
Yellow LED
Main Circuit of Models with Built-in Heat Sinks
Model
G3PE-
215B-

3(N)
G3PE-
215B-

2(N)
G3PE-
225B-

3(N)
G3PE-
225B-

2(N)
G3PE-
235B-

3(N)
G3PE-
235B-

2(N)
G3PE-
245B-

3(N)
G3PE-
245B-

2(N)
Rated load voltage
100 to 240 VAC
Operating voltage range
75 to 264 VAC
Rated load current *1
15 A (at 40 ° C)
25 A (at 40 ° C)
35 A (at 25 ° C)
45 A (at 25 ° C)
Minimum load current
0.2 A
0.5 A
Inrush current resistance
(peak value)
150 A
(60 Hz, 1 cycle)
220 A
(60 Hz, 1 cycle)
440 A
(60 Hz, 1 cycle)
Permissible I2t (reference value)
121A2s
260A2s
1,260A2s
Applicable load (resistive load:
AC1 class) *2
5.1 kW
(at 200 VAC)
8.6 kW
(at 200 VAC)
12.1 kW
(at 200 VAC)
15.5 kW
(at 200 VAC)
Model
G3PE-
515B-

3(N)
G3PE-
515B-

2(N)
G3PE-
525B-

3(N)
G3PE-
525B-

2(N)
G3PE-
535B-

3(N)
G3PE-
535B-

2(N)
G3PE-
545B-

3(N)
G3PE-
545B-

2(N)
Rated load voltage
200 to 480 VAC
Operating voltage range
180 to 528 VAC
Rated load current *1
15 A (at 40 ° C)
25 A (at 40 ° C)
35 A (at 25 ° C)
45 A (at 25 ° C)
Minimum load current
0.5 A
Inrush current resistance
(peak value)
220 A
(60 Hz, 1 cycle)
440 A
(60 Hz, 1 cycle)
Permissible I2t (reference value)
260A2s
1,260A2s
Applicable load (resistive load:
AC1 class) *2
12.5 kW
(at 480 VAC)
20.7 kW
(at 480 VAC)
29.0 kW
(at 480 VAC)
37.4 kW
(at 480 VAC)
*1. The applicable load current depends on the ambient temperature. For details, refer to Load Current vs. Ambient Temperature in Engineering Data on Data Sheet.
*2. Applicable Load Use the following formula to calculate the maximum total capacity of a heater load for a three-phase balanced load

       with delta connections.
Main Circuit of Models with Externally Attached Heat Sinks
Model
G3PE-
215B-

3H
G3PE-
215B-

2H
G3PE-
225B-

3HH
G3PE-
225B-

2H
G3PE-
235B-

3H
G3PE-
235B-

2H
G3PE-
245B-

3H
G3PE-
245B-

2H
Rated load voltage
100 to 240 VAC
Operating voltage range
75 to 264 VAC
Rated load current *
15 A (at 40 ° C)
25 A (at 40 ° C)
35 A (at 25 ° C)
45 A (at 25 ° C)
Minimum load current
0.2 A
0.5 A
Inrush current resistance
(peak value)
150 A
(60 Hz, 1 cycle)
220 A
(60 Hz, 1 cycle)
440 A
(60 Hz, 1 cycle)
Permissible I2t (reference value)
121A2s
260A2s
1,260A2s
Applicable load (resistive load:
AC1 class)
Refer to Engineering Data on Data Sheet.
Model
G3PE-
515B-

3H
G3PE-
515B-

2H
G3PE-
525B-

3H
G3PE-
525B-

2H
G3PE-
535B-

3H
G3PE-
535B-

2H
G3PE-
545B-

3H
G3PE-
545B-

2H
Rated load voltage
200 to 480 VAC
Operating voltage range
180 to 528 VAC
Rated load current *
15 A (at 40 ° C)
25 A (at 40 ° C)
35 A (at 25 ° C)
45 A (at 25 ° C)
Minimum load current
0.5 A
Inrush current resistance
(peak value)
220 A
(60 Hz, 1 cycle)
440 A
(60 Hz, 1 cycle)
Permissible I2t (reference value)
260A2s
1,260A2s
Applicable load (resistive load:
AC1 class)
Refer to Engineering Data on Data Sheet.
* The rated load current depends on the heat sink or radiator that is mounted. It also depends on the ambient temperature.
  For details, refer to Load Current vs. Ambient Temperature in Engineering Data on Data Sheet.
Characteristics
Models with Built-in Heat Sinks
Model
G3PE-
215B-

3(N)
G3PE-
215B-

2(N)
G3PE-
225B-

3(N)
G3PE-
225B-

2(N)
G3PE-
235B-

3(N)
G3PE-
235B-

2(N)
G3PE-
245B-

3(N)
G3PE-
245B-

2(N)
Operate time
1/2 of load power source cycle + 1 ms max.
Release time
1/2 of load power source cycle + 1 ms max.
Output ON voltage
drop
1.6 V (RMS) max.
Leakage current *
10 mA max. (at 200 VAC)
Insulation
resistance
100 M Ω min. (at 500 VDC)
Dielectric strength
2,500 VAC, 50/60 Hz for 1 min
Vibration
resistance
DIN Track mounting: 10 to 55 to 10 Hz, 0.175-mm single amplitude (0.35-mm double amplitude)
Screw mounting: 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)
Shock resistance
294 m/s2 (reverse mounting: 98 m/s2)
Ambient storage
temperature
- 30 to 100 ° C (with no icing or condensation)
Ambient operating
temperature
- 30 to 80 ° C (with no icing or condensation)
Ambient operating
humidity
45% to 85%
Weight
Approx. 1.25 kg
Approx.
1.45 kg
Approx.
1.25 kg
Approx.
1.65 kg
Approx.
1.45 kg
Approx.
2.0 kg
Approx.
1.65 kg
Model
G3PE-
515B-

3(N)
G3PE-
515B-

2(N)
G3PE-
525B-

3(N)
G3PE-
525B-

2(N)
G3PE-
535B-

3(N)
G3PE-
535B-

2(N)
G3PE-
545B-

3(N)
G3PE-
545B-

2(N)
Operate time
1/2 of load power source cycle + 1 ms max.
Release time
1/2 of load power source cycle + 1 ms max.
Output ON voltage
drop
1.8 V (RMS) max.
Leakage current *
20 mA max. (at 480 VAC)
Insulation
resistance
100 M Ω min. (at 500 VDC)
Dielectric strength
2,500 VAC, 50/60 Hz for 1 min
Vibration
resistance
DIN Track mounting: 10 to 55 to 10 Hz, 0.175-mm single amplitude (0.35-mm double amplitude)
Screw mounting: 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)
Shock resistance
294 m/s2 (reverse mounting: 98 m/s2)
Ambient storage
temperature
- 30 to 100 ° C (with no icing or condensation)
Ambient operating
temperature
- 30 to 80 ° C (with no icing or condensation)
Ambient operating
humidity
45% to 85%
Weight
Approx. 1.25 kg
Approx.
1.45 kg
Approx.
1.25 kg
Approx.
1.65 kg
Approx.
1.45 kg
Approx.
2.0 kg
Approx.
1.65 kg
* The leakage current of phase S will be approximately √3 times larger if the 2-element model is used.
Models with Externally Attached Heat Sinks
Model
G3PE-
215B-

3H
G3PE-
215B-

2H
G3PE-
225B-

3H
G3PE-
225B-

2H
G3PE-
235B-

3H
G3PE-
235B-

2H
G3PE-
245B-

3H
G3PE-
245B-

2H
Operate time
1/2 of load power source cycle + 1 ms max.
Release time
1/2 of load power source cycle + 1 ms max.
Output ON voltage drop
1.6 V (RMS) max.
Leakage current *
10 mA max. (at 200 VAC)
Insulation resistance
100 M Ω min. (at 500 VDC)
Dielectric strength
2,500 VAC, 50/60 Hz for 1 min
Vibration resistance
10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)
Shock resistance
Destruction: 294 m/s2
Ambient storage temperature
- 30 to 100 ° C (with no icing or condensation)
Ambient operating temperature
- 30 to 80 ° C (with no icing or condensation)
Ambient operating humidity
45% to 85%
Weight
Approx. 300 g
Model
G3PE-
515B-

3H
G3PE-
515B-

2H
G3PE-
525B-

3H
G3PE-
525B-

2H
G3PE-
535B-

3H
G3PE-
535B-

2H
G3PE-
545B-

3H
G3PE-
545B-

2H
Operate time
1/2 of load power source cycle + 1 ms max.
Release time
1/2 of load power source cycle + 1 ms max.
Output ON voltage drop
1.8 V (RMS) max.
Leakage current *
20 mA max. (at 480 VAC)
Insulation resistance
100 M Ω min. (at 500 VDC)
Dielectric strength
2,500 VAC, 50/60 Hz for 1 min
Vibration resistance
10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)
Shock resistance
Destruction: 294 m/s2
Ambient storage temperature
- 30 to 100 ° C (with no icing or condensation)
Ambient operating temperature
- 30 to 80 ° C (with no icing or condensation)
Ambient operating humidity
45% to 85%
Weight
Approx. 300 g
* The leakage current of phase S will be approximately √3 times larger if the 2-element model is used.
Heat Sinks
Model
Weight
Y92B-P50
Approx. 450 g
Y92B-P100
Approx. 450 g
Y92B-P150
Approx. 600 g
Y92B-P200
Approx. 850 g
Y92B-P250
Approx. 1,200 g