Solid State Relays for Heaters
G3PJ
Our Value Design Products Increase the Value of Your Control Panels. Single-phase SSR for low heat generation enables carrying 25 A (G3PJ-[]25B(-PU)) even for close mounting of three SSRs to contribute to downsizing of control panels. Models available with push-in input terminals.
Ratings
Input (at an Ambient Temperature of 25°C)
Model | Rated voltage | Operating voltage range | Current | Must operate voltage | Must release voltage |
G3PJ-2[][]B(-PU)/ G3PJ-5[][]B(-PU) | 12 to 24 VDC | 9.6 to 30 VDC | 7 mA max. | 9.6 VDC max. | 1.0 VDC min. |
Output
Model | Rated load voltage | Load voltage range | Load current | Inrush current resistance | I2t (Reference value) |
G3PJ-215B(-PU) | 24 to 240 VAC 50/60 Hz | 19 to 264 VAC 50/60 Hz | Close mounting *: 0.1 to 15 A, Separate mounting: 0.1 to 18 A | 150 A (60 Hz, 1 cycle) | 260A2s |
G3PJ-225B(-PU) | Close mounting *: 0.1 to 25 A, Separate mounting: 0.1 to 27 A | 220 A (60 Hz, 1 cycle) | 1,260A2s | ||
G3PJ-515B(-PU) | 100 to 480 VAC 50/60 Hz | 75 to 528 VAC 50/60 Hz | Close mounting *: 0.1 to 15 A, Separate mounting: 0.1 to 23 A | 150 A (60 Hz, 1 cycle) | 1,350A2s |
G3PJ-525B(-PU) | Close mounting *: 0.1 to 25 A, Separate mounting: 0.1 to 27 A | 220 A (60 Hz, 1 cycle) | 6,600A2s |
* For close mounting of three SSRs.
Characteristics
Item | G3PJ-2[][]B(-PU) | G3PJ-5[][]B(-PU) |
Operate time | 1/2 of load power source cycle + 1 ms max. | |
Release time | 1/2 of load power source cycle + 1 ms max. | |
Output ON voltage drop | 1.6 V (RMS) max. | 1.8 V (RMS) max. |
Leakage current | 10 mA max. (at 240 VAC) | 20 mA max. (at 480 VAC) |
Insulation resistance | 100 MΩ min. (at 500 VDC) | |
Dielectric strength | 2,500 VAC 50/60 Hz for 1 min | 4,000 VAC 50/60 Hz for 1 min |
Vibration resistance | 10 to 55 to10 Hz, 0.35 mm single amplitude (0.7 mm double amplitude) (Mounted to DIN track) | |
Shock resistance | Destruction: 300 m/s2 (Mounted to DIN track) | |
Ambient storage temperature | -30 to 100°C (with no icing or condensation) | |
Ambient operating temperature | -30 to 80°C (with no icing or condensation) | |
Ambient operating humidity | 45% to 85% | |
Weight | Approx. 240 g | |
SCCR (UL508) * | 5 kA | 10 kA |
* Obtained through coordination with a 30 A (Class CC/Class J) fuse. Refer to Precautions for Correct Use for details.
Applicable Standards
cULus and TÜV (EN 60947-4-3)
Pollution category 2
RoHS compliant
Pollution category 2
RoHS compliant