Solid State Relays for Heaters

G3PJ

Our Value Design Products Increase the Value of Your Control Panels. Single-phase SSR for low heat generation enables carrying 25 A (G3PJ-[]25B(-PU)) even for close mounting of three SSRs to contribute to downsizing of control panels. Models available with push-in input terminals.

Ratings
Input (at an Ambient Temperature of 25°C)
Model
Rated voltage
Operating voltage
range
Current
Must operate
voltage
Must release
voltage
G3PJ-2[][]B(-PU)/
G3PJ-5[][]B(-PU)
12 to 24 VDC
9.6 to 30 VDC
7 mA max.
9.6 VDC max.
1.0 VDC min.
Output
Model
Rated load
voltage
Load voltage
range
Load current
Inrush current
resistance
I2t
(Reference

value)
G3PJ-215B(-PU)
24 to 240
VAC

50/60 Hz
19 to 264
VAC

50/60 Hz
Close mounting *: 0.1 to 15 A,
Separate mounting: 0.1 to 18 A
150 A
(60 Hz, 1 cycle)
260A2s
G3PJ-225B(-PU)
Close mounting *: 0.1 to 25 A,
Separate mounting: 0.1 to 27 A
220 A
(60 Hz, 1 cycle)
1,260A2s
G3PJ-515B(-PU)
100 to 480
VAC

50/60 Hz
75 to 528
VAC

50/60 Hz
Close mounting *: 0.1 to 15 A,
Separate mounting: 0.1 to 23 A
150 A
(60 Hz, 1 cycle)
1,350A2s
G3PJ-525B(-PU)
Close mounting *: 0.1 to 25 A,
Separate mounting: 0.1 to 27 A
220 A
(60 Hz, 1 cycle)
6,600A2s
* For close mounting of three SSRs.
Characteristics
Item
G3PJ-2[][]B(-PU)
G3PJ-5[][]B(-PU)
Operate time
1/2 of load power source cycle + 1 ms max.
Release time
1/2 of load power source cycle + 1 ms max.
Output ON voltage drop
1.6 V (RMS) max.
1.8 V (RMS) max.
Leakage current
10 mA max. (at 240 VAC)
20 mA max. (at 480 VAC)
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,500 VAC 50/60 Hz for 1 min
4,000 VAC 50/60 Hz for 1 min
Vibration resistance
10 to 55 to10 Hz, 0.35 mm single amplitude
(0.7 mm double amplitude) (Mounted to DIN track)
Shock resistance
Destruction: 300 m/s2 (Mounted to DIN track)
Ambient storage temperature
-30 to 100°C (with no icing or condensation)
Ambient operating temperature
-30 to 80°C (with no icing or condensation)
Ambient operating humidity
45% to 85%
Weight
Approx. 240 g
SCCR (UL508) *
5 kA
10 kA
* Obtained through coordination with a 30 A (Class CC/Class J) fuse. Refer to Precautions for Correct Use for details.
Applicable Standards
cULus and TÜV (EN 60947-4-3)
Pollution category 2

RoHS compliant