Product Category

Relays with Forcibly Guided Contacts

G7SA

Compact, Slim Relays Conforming to EN Standards

Ratings
Safety Relay Unit
Coil (4 poles)
Item
Rated current (mA)
Coil resistance (Ω)
Max. voltage (V)
Power consumption (mW)
Rated voltage
12 VDC
30
400
110%
Approx. 360
18 VDC
20
900
21 VDC
17.1
1,225
24 VDC
15
1,600
48 VDC
7.5
6,400
110 VDC
3.8
28,810
Approx. 420
Coil (6 poles)
Item
Rated current (mA)
Coil resistance (Ω)
Max. voltage (V)
Power consumption (mW)
Rated voltage
12 VDC
41.7
288
110%
Approx. 500
18 VDC
27.8
648
21 VDC
23.8
882
24 VDC
20.8
1,152
48 VDC
10.4
4,606
110 VDC
5.3
20,862
Approx. 580
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of ±15%.
           2. The maximum voltage is based on an ambient operating temperature of 23°C maximum.
Contacts
Load
Resistive load
Rated load
6 A at 250 VAC, 6 A at 30 VDC
Rated carry current
6 A
Max. switching voltage
250 VAC, 125 VDC
Max. switching current
6 A
Contact materials
Au plating + Ag alloy
Characteristics
Safety Relay Unit
Contact resistance *1
100 max.
Operating time *2
20 ms max.
Response time *3
10 ms max.
Release time *2
20 ms max.
Must operate voltage
75% max.
Must release voltage
10% min.
Maximum
operating

frequency
Mechanical
36,000 operations/h
Rated load
1,800 operations/h
Insulation resistance *4
1,000 MΩ min.
Dielectric
Strength

*5 *6
Between coil
and contacts
4,000 VAC, 50/60 Hz for 1 min.
Between
contacts of

different
olarity
4,000 VAC, 50/60 Hz for 1 min. (except for followings)
4 poles (for poles 3-4 in 4-pole Relays),

6 poles (for poles 3-5, 4-6, and 5-6 in 6-pole Relays): 2,500 VAC, 50/60 Hz for 1 min.
Between
contacts of the

same polarity
1,500 VAC, 50/60 Hz for 1 min.
Vibration resistance
10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude)
Shock
resistance
Destruction
1,000 m/s2
Malfunction
100 m/s2
Durability
*7
Mechanical
10,000,000 operations min. (at approx. 36,000 operations/h)
Electrical
100,000 operations min. (at the rated load)
Inductive load switching
capability *8

(IEC60947-5-1)
AC15 240 VAC, 2 A
DC13 24 VDC, 1 A/48 VDC, 0.5 A/110 VDC, 0.2 A
Failure rate (P level)
(reference value *9)
5 VDC, 1 mA
Ambient operating
temperature *10
12 to 48 VDC: -40 to 85°C (with no icing or condensation)
110 VDC: -40 to 60°C (with no icing or condensation)
Ambient operating humidity
5% to 85%
Weight
4 poles: Approx. 22 g
6 poles: Approx. 25 g
Note: 1. The above values are initial values.
           2. Performance characteristics are based on coil
temparature of 23°C.
*1. The contact resistance was measured with 1 A at 5 VDC using the voltage-drop method.

*2. These times were measured at the rated voltage and an ambient temperature of 23°C. Contact bounce time is not included.

*3. The response time is the time it takes for the normally open contacts to open after the coil voltage is turned OFF. Contact bounce time is included. Measurement conditions: Rated voltage operation,
Ambient temperature: 23°C
*4. The insulation resistance was measured with a 500-VDC
megohmmeter at the same locations as the dielectric strength was measured.
*5. Pole 3 refers to terminals 31-32 or 33-34, pole 4 refers to terminals 43-44, pole 5 refers to terminals 53-54, and pole 6 refers to terminals 63-64.

*6. When using a P7SA Socket, the dielectric strength between coil contacts/different poles is 2,500 VAC, 50/60 Hz for 1 min. When using Push-In Plus terminal sockets (P7SA-[
]F-ND-PU), the dielectric strength between coil contacts as well as between different poles is 4,000 VAC, 50/60 Hz for 1 min.
*7. The durability is for an ambient temperature of 15 to 35°C and an ambient humidity of 25% to 75%. For the durability performance to the load, refer to the Durability Curve.

*8. AC15:
cosφ = 0.3, DC13: L/R = 48-ms.
*9. The failure rate is based on an operating frequency of 300 operations/min.

*10. 12 to 48 VDC: When operating between 70 and 85°C, reduce the rated carry current of 6 A by 0.1 A for each degree above 70°C. (See Fig. 1.)110 VDC:

       When operating between 40 and 60°C, reduce the rated carry current of 6 A by 0.27 A for each degree above 40°C.  (See Fig. 1.)
Options (order separately)
Sockets
Model
Push-In Plus terminals
Screw terminals
PCB terminals
4 poles
6 poles
4 poles
6 poles
4 poles
6 poles
P7SA-10F-ND-PU
P7SA-14F-ND-PU
P7SA-10F(-ND)
P7SA-14F(-ND)
P7SA-10P
P7SA-14P
Ambient operating temperature
• With operation indicator LED/built-in diode
 P7SA-[]F-ND(-PU): -20 to +70°C
• Without operation indicator LED/built-in diode

 P7SA-[]F: -40 to +85°C
(with no icing or condensation)
-40 to +85°C
(with no icing or condensation)
Ambient operating humidity
25% to 85%
5% to 85%
Continuous carry current
6 A *1
Dielectric
strength
Between coil
and contact

terminals
4,000 VAC for 1 min.
2,500 VAC for 1 min.
Between contact
terminals of

different polarity
2,500 VAC for 1 min.
Between contact
terminals of

same polarity
1,500 VAC for 1 min.
Insulation resistance
1,000 MΩ min. *2
Weight
Approx. 58 g
Approx. 70 g
Approx. 44 g
Approx. 59 g
Approx. 9 g
Approx. 10 g
*1. When operating the P7SA-[]F-ND-PU at a temperature between 50 and 70°C, reduce the continuous current (6 A at 50°C or less) by 0.25 A for each degree above 50°C.
       When operating the P7SA-[
]F-ND at a temperature between 50 and 70°C, reduce the continuous current (6 A at 50°C or less) by 0.3 A for each degree above 50°C.
       When operating the P7SA-[
]F at a temperature between 50 and 85°C, reduce the continuous current (6 A at 50°C or less) by 0.1 A for each degree above 50°C.
*2. Measurement conditions: For 500 VDC applied to the same location as for dielectric strength measurement.
Short Bars (for P7SA-[]F-ND-PU)
Application
Applicable
sockets
Models
Maximum
carry current
Ambient operating
temperature
Ambient operating
humidity
Crossover wiring of
contact terminals

(bottom)
P7SA-[]F-ND-PU
XW5S-P2.5-2[]
24 A
-40 to 55°C
5% to 95%
XW5S-P2.5-3[]
XW5S-P2.5-4[]
XW5S-P2.5-5[]
Certified Standards
Safety Relay Unit
EN Standards, VDE Certified
Models
Ratings
Standard number
Certification No.
Operating coil
Contact ratings
G7SA-2A2B
12, 18, 21, 24, 48, 110 VDC
EN/IEC 61810-1
Electromagnetic relay EN 61810-3

Relays with forcibly guided contacts
125547
12, 18, 21, 24, 48, 110 VDC
6 A, 240 VAC (Resistive)
6 A, 30 VDC (Resistive)
G7SA-3A1B
G7SA-3A3B
G7SA-4A2B
G7SA-5A1B
UL Standards Certification (File No. E41515) Industrial Control Devices
Models
Category
Listed/Recognized
Contact ratings
Operating Coil ratings
G7SA-2A2B
E41515
Recognized
6 A, 250 VAC (Resistive)
6 A, 30 VDC (Resistive)
12, 18, 21, 24, 48, 110 VDC
G7SA-3A1B
G7SA-3A3B
G7SA-4A2B
G7SA-5A1B
CSA standard CSA C22.2 No.14 Industrial Control Devices
Models
Class number
File No.
Contact ratings
Operating Coil ratings
G7SA-2A2B
3211-07
LR35535
6 A, 250 VAC (Resistive)
6 A, 30 VDC (Resistive)
12, 18, 21, 24, 48, 110 VDC
G7SA-3A1B
G7SA-4A2B
G7SA-5A1B
South Korea S-mark certified (Rated voltage 24VDC only)
Models
Applicable standard number
G7SA-2A2B DC24
KS C IEC 61810-1
G7SA-3A1B DC24
G7SA-3A3B DC24
G7SA-4A2B DC24
G7SA-5A1B DC24
CQC
Models
Standard number
Certification No.
G7SA
GB/T, 21711.1
CQC14002119869
Sockets
CE Marking Compliance
Models
EMC Directive
Low Voltage Directive
Machinery Directive
P7SA (Excluding -P type)
Not applicable
Applicable
Not applicable
P7SA-PU
Not applicable
Applicable
Not applicable
The CE compliance declaration was made in combination with the Safety Relay.
EN Standards, VDE Certified
Models
Ratings
Standard number
Certification No.
P7SA
---
EN61984
40007586
EN Standards, TÜV Certified
Models
Ratings
Standard number
Certification No.
P7SA-PU
---
EN61984
R50356981
UL Standards Certification (File No. E87929) Industrial Control Devices
Models
Category
Listed/Recognized
P7SA
SWIV2
Recognized
P7SA-PU
SWIV2, SWIV8
Recognized
CSA standard CSA C22.2 No.14 Industrial Control Devices
Models
Class number
File No.
P7SA
3211-07, 3211-87
LR35535
P7SA-PU
3211-07, 3211-87
LR35535