Ratings
Power Input
Model
G9SB-200[]-[]
G9SB-3010
G9SB-301[]-[]
Power supply voltage
24 VAC/24 VDC
24 VDC
24 VAC/24 VDC
Operating voltage range
85% to 110% of rated power supply voltage
Power consumption
2.9 VA/1.4 W max.
1.7 W max.
3.6 VA/1.7 W max.
Inputs
Model
G9SB-200[]-[]
G9SB-3010
G9SB-301[]-[]
Input current
25 mA max.
60 mA max. *
30 mA max.
* Indicates the current between terminals A1 and A2.
Contacts
Model
Load
G9SB-200[]-[]
G9SB-3010
G9SB-301[]-[]
Resistive load
Rated load
250 VAC, 5 A
30 VDC, 5 A
Rated carry current
5 A
Characteristics
Model
G9SB-200[]-[]
G9SB-3010
G9SB-301[]-[]
Contact resistance *1
100
Operating time *2
30 ms max.
Response time *3
10 ms max.
Isolation voltage (Ui)
250 V/AC
Impulse withstand voltage (Uimp)
4 kV
Insulation
resistance *4
Between inputs
and outputs
100 MΩ min. (at 500 VDC)
Between different
poles of output
Dielectric
strength
Between inputs and
outputs
2,500 VAC 1 min.
Between different
poles of output
Vibration resistance
10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)
Shock
resistance
Destruction
300 m/s2
Malfunction
100 m/s2
Durability *5
Mechanical
5,000,000 operations min. (at approx. 7,200 operations/hr)
Electrical
100,000 operations min. (at approx. 1,800 operations/hr)
Failure rate (P level) (reference value)
5 VDC, 1 mA
Ambient operating temperature
-25 to 55°C (with no icing or condensation)
Ambient operating humidity
35% to 85%
Pollution degree
2
Protection class
IP20
Terminal tightening torque
0.5 N·m
Weight
Approx. 115 g
Approx. 135 g
Approx. 120 g
*1. The contact resistance was measured with 1 A at 5 VDC using the voltage-drop method.
*2. Not including bounce time.

*3. The response time is the time it takes for the main contact to open after the input is turned OFF. Includes bounce time.

*4. The insulation resistance was measured with 500 VDC at the same places that the dielectric strength was checked.

*5. The durability is for an ambient temperature of 15 to 35°C and an ambient humidity of 25% to 75%.