Product Category

Safety Relay Unit

G9SE

Complete line-up of compact units, including OFF-delayed safety output models

Ratings
Power Input
Model
G9SE-201
G9SE-401
G9SE-221-T[]
Rated supply voltage
24 VDC
Operating voltage range
-15% to 10% of rated supply voltage
Rated power consumption *1
3 W max.
4 W max.
Outputs
Model
G9SE-201
G9SE-401
G9SE-221-T[]
Safety output
OFF-delayed Safety output
Contact output
250 VAC 5 A 30 VDC 5 A (resistive load)
Auxiliary output
PNP transistor output Load current: 100 mA DC max.
Characteristics
Model
G9SE-201
G9SE-401
G9SE-221-T[]
Operating time (OFF to ON state) *2
100 ms Max. *3
Response time (ON to OFF state) *4
15 ms Max.
Accuracy of OFF-delay time
-
Within plus or minus
10% of the set value
Inputs
Input current
5 mA Min.
ON voltage
11 VDC Min.
OFF voltage
5 VDC Max.
OFF current
1 mA Max.
Maximum cable length
100 m Max.
Reset input time
250 ms Min.
Contact
outputs
Contact resistance *5
100
Mechanical durability
5,000,000 operations Min.
Electrical durability
50,000 operations Min.
Switching specification Inductive
load (IEC/EN60947-5-1)
AC15: 240 VAC 2 A
DC13: 24 VDC 1.5 A
Minimum applicable load
24 VDC 4 mA
Conditional short-circuit current
(IEC/EN60947-5-1)
100 A *6
Pollution degree
2
Over voltage category (IEC/EN60664-1)
Safety output: Class III, the others: Class II
Insulation
specification
Isolation voltage (Ui)
250 VAC
Impulse
withstand
voltage
(IEC/
EN60947-5-1)
Between input and
output
6 kV
Between different
poles of output
6 kV (between 13-14/23-24 and 33-34/43-44 (37-38/47-48))
4 kV (between 13-14 and 23-24, between 33-34 (37-38) and

43-44 (47-48))
Dielectric
strength
Between input and
output
2,200 VDC
Between different
poles of output
1,500 VAC
Insulation resistance
100 MΩ
Vibration resistance *7
Frequency: 10 to 55 to 10 Hz
Amplitude: 0.35 mm half amplitude (0.7 mm double amplitude)
Mechanical
shock re-
sistance *7
Destruction
300 m/s2
Malfunction
100 m/s2
Surrounding Air Temperature
-10 to 55°C (No freezing or condensation)
Ambient humidity
25% to 85%RH
Degree of protection
IP20
Weight
approx. 150 g
approx. 180 g
*1 Power consumption of loads not included.
*2
The operating time is the time it takes for the safety contact to close after the safety inputs and feedback-reset input are turned ON. Not includes bounce time.
*3
This is in normal operation. When executing non-regular self-diagnosis for Safety output circuit, G9SE operating time become 500 ms max..
*4
The response time is the time it takes for the safety main contact to open after the safety input is turned OFF. Includes bouncetime.
*5
This is initial value using the voltage-drop method with 1A at 5VDC.
*6 Use for each contact output an 8A fuse that conforms to IEC 60127 as a short-circuit prote
ction device. This fuse is not included with the G9SE.
*7 Condition: G9SE is mounted to mounting surface with screw and the screw mounting
attachment. In the case of DIN rail mounting, mount DIN rail with G9SE to the place without big vibration. (Amplitude guideline: Less than 0.15 mm half amplitude (0.3 mm double amplitude))