Rotary paddle level switch

Rotonivo® - RN 3003

Application area

The rotating paddle detector Rotonivo® RN 3003 is used in storage and process vessels as a full, demand and empty detector in all bulk solids. It can be configured for process temperatures up to +250°C and process overpressure up to 10 bar and is mechanically extremely resilient. Buildup or a dust-intensive process environment does not in any way affect the accuracy of the measurement results of the level indicator

Technical Data

Measurement principleRotary Paddle
Measuring taskPoint level measurement
Version
  • Angled extension
  • Angled extension with angled flange
  • Strengthened rope version
MediumSolids
Mounting position
  • horizontal
  • horizontal (in the cone)
Ambient temperature-40°C … +60°C (-40°F … +140°F)
Process temperature-40°C … +250°C (-40°F … +482°F)
Process pressure-0,9 bar … +10 bar (-13.1 psi … +145 psi)
Minimum sensitivity> 15 g/l (> 0.9 lbs/ft3)
Housing typestandard
Housing material
  • Aluminium
  • Plastics (PA6)
Housing protection ratingIP66
Threaded connection
Flange connection
  • ≥ DN100
  • ≥ 4″
Hygienic fittings
Wetted materials
  • Aluminium
  • Stainless steel 1.4301 (304)
  • Stainless steel 1.4305 (303)
  • Stainless steel 1.4541 (321L)
  • NBR
  • FPM
  • PTFE
Mechanical load
  • aluminium: 250 Nm
  • stainless steel: 600 Nm
Accuracy
Min. immersion length125 mm (4.92″)
Max. immersion length600 mm (2′)
Power supply
  • 24V AC
  • 48V AC
  • 115V AC
  • 230V AC
  • 24V DC
  • universal voltage (24V DC / 22…230V AC)
Signal output
  • Microswitch
  • Relay SPDT
  • Transistor PNP
Approvals
  • CE
  • ATEX
  • IEC-Ex
  • TR-CU
  • INMETRO
Explosion protectionDust Ignitionproof (Ex t)
Hygienic / Pharma
Ship approval
Overfill protection
SIL qualification
Further approvals
User Interface
  • Jumper
  • Potentiometer
Optical indicatorLED
Adjustment possibility
  • adjutable sensitivity
  • adjustable output delay
  • switchable logic (Fail Safe High – Fail Safe Low)
  • Fail safe alarm (rotation control)