Multi-function Compact Inverter
3G3MX2-V1
Born to drive machines
Performance Specifications
Inverter MX2-series V1 type
3-phase 200 V Class
Function name | 3-phase 200 V | ||||||||||||||
Model name (3G3MX2-) | A2001-V1 | A2002-V1 | A2004-V1 | A2007-V1 | A2015-V1 | A2022-V1 | |||||||||
Applicable motor capacity | kW | CT | 0.1 | 0.2 | 0.4 | 0.75 | 1.5 | 2.2 | |||||||
VT | 0.2 | 0.4 | 0.75 | 1.1 | 2.2 | 3.0 | |||||||||
HP | CT | 1/8 | 1/4 | 1/2 | 1 | 2 | 3 | ||||||||
VT | 1/4 | 1/2 | 1 | 1 1/2 | 3 | 4 | |||||||||
Rated output capacity [kVA] | 200 V | CT | 0.2 | 0.5 | 1.0 | 1.7 | 2.7 | 3.8 | |||||||
VT | 0.4 | 0.6 | 1.2 | 2.0 | 3.3 | 4.1 | |||||||||
240 V | CT | 0.3 | 0.6 | 1.2 | 2.0 | 3.3 | 4.5 | ||||||||
VT | 0.4 | 0.7 | 1.4 | 2.4 | 3.9 | 4.9 | |||||||||
Rated input voltage | 3-phase 200 V - 15% to 240 V + 10%, 50/60 Hz ± 5% | ||||||||||||||
Rated input current [A] | CT | 1.0 | 1.6 | 3.3 | 6 | 9 | 12.7 | ||||||||
VT | 1.2 | 1.9 | 3.9 | 7.2 | 10.8 | 13.9 | |||||||||
Rated output voltage | 3-phase 200 to 240 V (The output cannot exceed the incoming voltage). | ||||||||||||||
Rated output current [A] | CT | 1.0 | 1.6 | 3.0 | 5.0 | 8.0 | 11.0 | ||||||||
VT | 1.2 | 1.9 | 3.5 | 6.0 | 9.6 | 12.0 | |||||||||
Short-time deceleration braking torque (%) (Discharge Resistor not connected) | 50 | 50 | 50 | 50 | 50 | 20 | |||||||||
Braking Resistor circuit * | Regenerative braking | Built-in Braking Resistor circuit (separate Discharge Resistor) | |||||||||||||
Min. connectable resistance [Ω] | 100 | 100 | 100 | 50 | 50 | 35 | |||||||||
Weight [kg] | 1.0 | 1.0 | 1.1 | 1.2 | 1.6 | 1.8 | |||||||||
Dimensions (width × height) [mm] | 68 × 128 | 108 × 128 | |||||||||||||
Dimensions (depth) [mm] | 109 | 122.5 | 145.5 | 170.5 | |||||||||||
Function name | 3-phase 200 V | ||||||||||||||
Model name (3G3MX2-) | A2037-V1 | A2055-V1 | A2075-V1 | A2110-V1 | A2150-V1 | ||||||||||
Applicable motor capacity | kW | CT | 3.7 | 5.5 | 7.5 | 11 | 15 | ||||||||
VT | 5.5 | 7.5 | 11 | 15 | 18.5 | ||||||||||
HP | CT | 5 | 7 1/2 | 10 | 15 | 20 | |||||||||
VT | 7 1/2 | 10 | 15 | 20 | 25 | ||||||||||
Rated output capacity [kVA] | 200 V | CT | 6.0 | 8.6 | 11.4 | 16.2 | 20.7 | ||||||||
VT | 6.7 | 10.3 | 13.8 | 19.3 | 23.9 | ||||||||||
240 V | CT | 7.2 | 10.3 | 13.7 | 19.5 | 24.9 | |||||||||
VT | 8.1 | 12.4 | 16.6 | 23.2 | 28.6 | ||||||||||
Rated input voltage | 3-phase 200 V - 15% to 240 V + 10%, 50/60 Hz ± 5% | ||||||||||||||
Rated input current [A] | CT | 20.5 | 30.8 | 39.6 | 57.1 | 62.6 | |||||||||
VT | 23.0 | 37.0 | 48.0 | 68.0 | 72.0 | ||||||||||
Rated output voltage | 3-phase 200 to 240 V (The output cannot exceed the incoming voltage). | ||||||||||||||
Rated output current [A] | CT | 17.5 | 25.0 | 33.0 | 47.0 | 60.0 | |||||||||
VT | 19.6 | 30.0 | 40.0 | 56.0 | 69.0 | ||||||||||
Short-time deceleration braking torque (%) (Discharge Resistor not connected) | 20 | 20 | 20 | 10 | 10 | ||||||||||
Braking Resistor circuit * | Regenerative braking | Built-in Braking Resistor circuit (separate Discharge Resistor) | |||||||||||||
Min. connectable resistance [Ω] | 35 | 20 | 17 | 17 | 10 | ||||||||||
Weight [kg] | 2.0 | 3.3 | 3.4 | 5.1 | 7.4 | ||||||||||
Dimensions (width × height) [mm] | 140 × 128 | 140 × 260 | 180 × 296 | 220 × 350 | |||||||||||
Dimensions (depth) [mm] | 170.5 | 155 | 175 |
* The BRD usage is 10%.
3-phase 400 V Class
Function name | 3-phase 400 V | ||||||
Model name (3G3MX2-) | A4004-V1 | A4007-V1 | A4015-V1 | A4022-V1 | A4030-V1 | ||
Applicable motor capacity | kW | CT | 0.4 | 0.75 | 1.5 | 2.2 | 3.0 |
VT | 0.75 | 1.5 | 2.2 | 3.0 | 4.0 | ||
HP | CT | 1/2 | 1 | 2 | 3 | 4 | |
VT | 1 | 2 | 3 | 4 | 5 | ||
Rated output capacity [kVA] | 380 V | CT | 1.1 | 2.2 | 3.1 | 3.6 | 4.7 |
VT | 1.3 | 2.6 | 3.5 | 4.5 | 5.7 | ||
480 V | CT | 1.4 | 2.8 | 3.9 | 4.5 | 5.9 | |
VT | 1.7 | 3.4 | 4.4 | 5.7 | 7.3 | ||
Rated input voltage | 3-phase 380 V - 15% to 480 V + 10%, 50/60 Hz ± 5% | ||||||
Rated input current [A] | CT | 1.8 | 3.6 | 5.2 | 6.5 | 7.7 | |
VT | 2.1 | 4.3 | 5.9 | 8.1 | 9.4 | ||
Rated output voltage | 3-phase 380 to 480 V (The output cannot exceed the incoming voltage). | ||||||
Rated output current [A] | CT | 1.8 | 3.4 | 4.8 | 5.5 | 7.2 | |
VT | 2.1 | 4.1 | 5.4 | 6.9 | 8.8 | ||
Short-time deceleration braking torque (%) (Discharge Resistor not connected) | 50 | 50 | 50 | 20 | 20 | ||
Braking Resistor circuit * | Regenerative braking | Built-in Braking Resistor circuit (separate Discharge Resistor) | |||||
Min. connectable resistance [Ω] | 180 | 180 | 180 | 100 | 100 | ||
Weight [kg] | 1.5 | 1.6 | 1.8 | 1.9 | 1.9 | ||
Dimensions (width × height) [mm] | 108 × 128 | ||||||
Dimensions (depth) [mm] | 143.5 | 170.5 | |||||
Function name | 3-phase 400 V | ||||||
Model name (3G3MX2-) | A4040-V1 | A4055-V1 | A4075-V1 | A4110-V1 | A4150-V1 | ||
Applicable motor capacity | kW | CT | 4.0 | 5.5 | 7.5 | 11 | 15 |
VT | 5.5 | 7.5 | 11 | 15 | 18.5 | ||
HP | CT | 5 | 7 1/2 | 10 | 15 | 20 | |
VT | 7 1/2 | 10 | 15 | 20 | 25 | ||
Rated output capacity [kVA] | 380 V | CT | 6.0 | 9.7 | 11.8 | 15.7 | 20.4 |
VT | 7.3 | 11.5 | 15.1 | 20.4 | 25.0 | ||
480 V | CT | 7.6 | 12.3 | 14.9 | 19.9 | 25.7 | |
VT | 9.2 | 14.5 | 19.1 | 25.7 | 31.5 | ||
Rated input voltage | 3-phase 380 V - 15% to 480 V + 10%, 50/60 Hz ± 5% | ||||||
Rated input current [A] | CT | 11.0 | 16.9 | 18.8 | 29.4 | 35.9 | |
VT | 13.3 | 20.0 | 24.0 | 38.0 | 44.0 | ||
Rated output voltage | 3-phase 380 to 480 V (The output cannot exceed the incoming voltage). | ||||||
Rated output current [A] | CT | 9.2 | 14.8 | 18.0 | 24.0 | 31.0 | |
VT | 11.1 | 17.5 | 23.0 | 31.0 | 38.0 | ||
Short-time deceleration braking torque (%) (Discharge Resistor not connected) | 20 | 20 | 20 | 10 | 10 | ||
Braking Resistor circuit * | Regenerative braking | Built-in Braking Resistor circuit (separate Discharge Resistor) | |||||
Min. connectable resistance [Ω] | 100 | 70 | 70 | 70 | 35 | ||
Weight [kg] | 2.1 | 3.5 | 3.5 | 4.7 | 5.2 | ||
Dimensions (width × height) [mm] | 140 × 128 | 140 × 260 | 180 × 296 | ||||
Dimensions (depth) [mm] | 170.5 | 155 | 175 |
* The BRD usage is 10%.
1-phase 200 V Class
Function name | 1-phase 200 V | |||||||
Model name (3G3MX2-) | AB001-V1 | AB002-V1 | AB004-V1 | AB007-V1 | AB015-V1 | AB022-V1 | ||
Applicable motor capacity | kW | CT | 0.1 | 0.2 | 0.4 | 0.75 | 1.5 | 2.2 |
VT | 0.2 | 0.4 | 0.55 | 1.1 | 2.2 | 3.0 | ||
HP | CT | 1/8 | 1/4 | 1/2 | 1 | 2 | 3 | |
VT | 1/4 | 1/2 | 3/4 | 1 1/2 | 3 | 4 | ||
Rated output capacity [kVA] | 200 V | CT | 0.2 | 0.5 | 1.0 | 1.7 | 2.7 | 3.8 |
VT | 0.4 | 0.6 | 1.2 | 2.0 | 3.3 | 4.1 | ||
240 V | CT | 0.3 | 0.6 | 1.2 | 2.0 | 3.3 | 4.5 | |
VT | 0.4 | 0.7 | 1.4 | 2.4 | 3.9 | 4.9 | ||
Rated input voltage | 1-phase 200 V - 15% to 240 V + 10%, 50/60 Hz ± 5% | |||||||
Rated input current [A] | CT | 1.3 | 3.0 | 6.3 | 11.5 | 16.8 | 22.0 | |
VT | 2.0 | 3.6 | 7.3 | 13.8 | 20.2 | 24.0 | ||
Rated output voltage | 3-phase 200 to 240 V (The output cannot exceed the incoming voltage). | |||||||
Rated output current [A] | CT | 1.0 | 1.6 | 3.0 | 5.0 | 8.0 | 11.0 | |
VT | 1.2 | 1.9 | 3.5 | 6.0 | 9.6 | 12.0 | ||
Short-time deceleration braking torque (%) (Discharge Resistor not connected) | 50 | 50 | 50 | 50 | 50 | 20 | ||
Braking Resistor circuit * | Regenerative braking | Built-in Braking Resistor circuit (separate Discharge Resistor) | ||||||
Min. connectable resistance [ Ω ] | 100 | 100 | 100 | 50 | 50 | 35 | ||
Weight [kg] | 1.0 | 1.0 | 1.1 | 1.6 | 1.8 | 1.8 | ||
Dimensions (width × height) [mm] | 68 × 128 | 108 × 128 | ||||||
Dimensions (depth) [mm] | 109 | 122.5 | 170.5 |
* The BRD usage is 10%.
Function Specifications
Function name | Specifications | ||
Enclosure ratings *1 | Open type (IP20) | ||
Control | Control method | Phase-to-phase sinusoidal modulation PWM | |
Output frequency range *2 | 0.10 to 400 Hz (or 580 Hz in the high-frequency mode; restrictions apply) | ||
Frequency precision *3 | Digital command: ±0.01% of the max. frequency, Analog command: ±0.2% of the max. frequency (25±10 °C) | ||
Frequency setting resolution | Digital setting: 0.01 Hz, Analog setting: One-thousandth of the maximum frequency | ||
Voltage/Frequency characteristics | V/f characteristics (constant/reduced torque) Sensorless vector control, V/f control with speed feedback | ||
Overload current rating | Heavy load rating (CT): 150%/60 s Light load rating (VT): 120%/60 s | ||
Instantaneous overcurrent protection | 200% of the value of heavy load rating (CT) | ||
Acceleration/ Deceleration time | 0.01 to 3600 s (linear/curve selection), acceleration/deceleration 2 setting vailable | ||
Carrier frequency adjustment range | 2 to 15 kHz (with derating) | ||
Starting torque | 200%/0.5 Hz (sensorless vector control) | ||
External DC injection braking | Starts at a frequency lower than that in deceleration via the STOP command, at a value set lower than that during operation, or via an external input. (Level and time settable). | ||
Protective functions | Overcurrent, overvoltage, undervoltage, electronic thermal, temperature error, ground fault overcurrent at power-on status, rush current prevention circuit, overload limit, incoming overvoltage, external trip, memory error, CPU error, USP error, communication error, overvoltage suppression during deceleration, protection upon momentary power outage, emergency cutoff, etc. | ||
Input signal | Frequency settings | Digital Operator External analog input signal: 0 to 10 VDC/4 to 20 mA, Modbus communication (Modbus-RTU) | |
RUN/STOP command | Digital Operator External digital input signal (3-wire input supported), Modbus communication (Modbus-RTU) | ||
Multi-function input *4 | 7 points (Functions can be selected from among 68) | ||
Analog input *5 | 2 points (Voltage FV terminal: 10 bits/0 to 10 V, Current FI terminal: 10 bits/4 to 20 mA) | ||
Pulse input | 1 point (RP terminal: 32 kHz max., 5 to 24 VDC) | ||
Output signal | Multi-function output *4 | 2 points (P1 and P2, Functions can be selected from among 47) | |
Relay output *4 | 1 point (SPDT contact (MC, MA, MB), Functions can be selected from among 47) | ||
Analog output (Frequency monitor) *6 | 1 point (AM terminal: Voltage 10 bits/0 to 10 V) (Frequency, current selectable) | ||
Pulse output | 1 point (MP terminal: 32 kHz max., 0 to 10 V) | ||
Communi- cations | RS-422 | RJ45 connector (for Digital Operator) | |
RS-485 | Control circuit terminal block, Modbus communication (Modbus-RTU) | ||
USB | USB1.1, mini-B connector | ||
Other functions | AVR function, V/f characteristics switching, upper/lower limit, 16-step speeds, starting frequency adjustment, jogging operation, carrier frequency adjustment, PID control, frequency jump, analog gain/bias adjustment, S shape acceleration/deceleration, electronic thermal characteristics, level adjustment, restart function, torque boost function, fault monitor, soft lock function, frequency conversion display, USP function, motor 2 control function, UP/DWN, overcurrent control function, etc. | ||
Operating environ- ment | Ambient operating temperature *7 | -10 to 50 °C (However, derating is required). | |
Ambient storage temperature | -20 °C to 65 °C | ||
Ambient operating humidity | 20% to 90% RH (with no condensation) | ||
Vibration resistance | 5.9 m/s2 (0.6G), 10 to 55 Hz | ||
Application environment | At a maximum altitude of 1,000 m; indoors (without corrosive gases or dust) | ||
Options | EtherCAT Communication Unit | 3G3AX-MX2-ECT | |
CompoNet Communication Unit | 3G3AX-MX2-CRT-E | ||
DeviceNet Communication Unit | 3G3AX-MX2-DRT-E | ||
Other option | DC reactor, AC reactor, radio noise filter, input noise filter, output noise filter, regenerative braking unit, Braking Resistor, etc. | ||
Interna- tional standard | EU Directives and UK legislation | Machinery | EN ISO 13849-1: 2008 Pld EN 61800-5-2 EN 60204-1 |
EMC | EN 61800-3: 2004 | ||
Low-voltage | EN 61800-5-1: 2007 | ||
UL/cUL | UL508C |
*1 Protection method complies with JEM 1030.
*2 To operate the motor at over 50/60 Hz, contact the motor manufacturer to find out the maximum allowable speed of revolution.
*3 For the stable control of the motor, the output frequency may exceed the maximum frequency set in A004 (A204) by 2 Hz max.
*4 In the VT (light load) mode and the PM motor mode, the available functions are limited compared with the CV (heavy load) mode. For some parameters, the default data and setting range also differ.
*5 By default, the maximum frequency is adjusted to 9.8 V for a voltage input of 0 to 10 VDC and to 19.8 mA for a current input of 4 to 20 mA, respectively. If necessary, adjust the default parameter settings.
*6 The analog voltage and current values for the multi-function monitor output terminals show values that can only be used as a guide for analog meter connection. The maximum output value may differ from 10 V or 20 mA due to the variability of the analog output circuit. If necessary, adjust the default parameter settings.
*7 Derating of the rated output current of the inverter may be required depending on the heavy/light load mode selection, operating ambient temperature, side-by-side installation, and carrier frequency setting. Use the inverter in an
appropriate environment according to USER’S MANUAL (Cat.No.I585).
Note: 1. The applicable motor is a 3-phase standard motor. For using any other type, be sure that the rated current does not exceed that of the Inverter.
2. Output voltage decreases according to the level of the power supply voltage.
3. The braking torque at the time of capacitor feedback is an average deceleration torque at the shortest deceleration (when it stops from 50 Hz). It is not a continuous regeneration torque. Also, the average deceleration torque varies depending on the motor loss. The value is reduced in operation over 50 Hz.
*2 To operate the motor at over 50/60 Hz, contact the motor manufacturer to find out the maximum allowable speed of revolution.
*3 For the stable control of the motor, the output frequency may exceed the maximum frequency set in A004 (A204) by 2 Hz max.
*4 In the VT (light load) mode and the PM motor mode, the available functions are limited compared with the CV (heavy load) mode. For some parameters, the default data and setting range also differ.
*5 By default, the maximum frequency is adjusted to 9.8 V for a voltage input of 0 to 10 VDC and to 19.8 mA for a current input of 4 to 20 mA, respectively. If necessary, adjust the default parameter settings.
*6 The analog voltage and current values for the multi-function monitor output terminals show values that can only be used as a guide for analog meter connection. The maximum output value may differ from 10 V or 20 mA due to the variability of the analog output circuit. If necessary, adjust the default parameter settings.
*7 Derating of the rated output current of the inverter may be required depending on the heavy/light load mode selection, operating ambient temperature, side-by-side installation, and carrier frequency setting. Use the inverter in an
appropriate environment according to USER’S MANUAL (Cat.No.I585).
Note: 1. The applicable motor is a 3-phase standard motor. For using any other type, be sure that the rated current does not exceed that of the Inverter.
2. Output voltage decreases according to the level of the power supply voltage.
3. The braking torque at the time of capacitor feedback is an average deceleration torque at the shortest deceleration (when it stops from 50 Hz). It is not a continuous regeneration torque. Also, the average deceleration torque varies depending on the motor loss. The value is reduced in operation over 50 Hz.
Communication Unit
MX2-Series EtherCAT Communication Unit 3G3AX-MX2-ECT
This is the communication unit to connect the Multi-function Compact Inverter MX2 to EtherCAT network.
This communication unit passed the conformance test of EtherCAT.
This communication unit passed the conformance test of EtherCAT.
Common Specifications
Item | Specifications | |
Power supply | Supplied from the inverter | |
Protective structure | Open type (IP20) | |
Ambient operating temperature | - 10 to +50 °C | |
Ambient storage temperature | - 20 to +65 °C | |
Ambient operating humidity | 20% to 90% RH (with no condensation) | |
Vibration resistance | 5.9 m/s2 (0.6 G), 10 to 55 Hz | |
Application environment | At a maximum altitude of 1,000 m; indoors (without corrosive gases or dust) | |
Weight | 100 g max. | |
International standard | UL/cUL | UL508C |
EU Directives and UK legislation | EMC:EN61800-3: 2004 Low Voltage:EN61800-5-1: 2003 |
EtherCAT Communications Specifications
Item | Specifications |
Communications standard | IEC 61158 Type12, IEC 61800-7 CiA 402 drive profile |
Physical layer | 100BASE-TX (IEEE802.3) |
Connector | RJ45 × 2 (shielded type) ECAT IN: EtherCAT input ECAT OUT: EtherCAT output |
Communications media | Category 5 or higher (cable with double, aluminum tape and braided shielding) is recommended. |
Communications distance | Distance between nodes: 100 m max. |
Process data | Fixed PDO mapping PDO mapping |
Mailbox (CoE) | Emergency messages, SDO, SDO responses, and information |
Distributed clock | FreeRun mode (asynchronous) |
LED display | L/A IN (Link/Activity IN) × 1 L/A OUT (Link/Activity OUT) × 1 RUN × 1 ERR × 1 |
CiA402 drive profile | Velocity mode |
MX2-Series CompoNet Communication Unit 3G3AX-MX2-CRT-E
This is the communication unit to connect the Multi-function Compact Inverter MX2 to CompoNet network.
Common Specification
Item | Specification | |
Power supply | Supplied from the inverter | |
Protective structure | IP20 | |
Ambient operating temperature | - 10 to 50 °C | |
Ambient storage temperature | - 20 to 65 °C | |
Ambient operating humidity | 20 to 90%RH (with no condensation) | |
Vibration resistance | 5.9m/s2 (0.6G), 10 to 55Hz | |
Application environment | At a maximum altitude of 1,000 m; indoors (without corrosive gases or dust) | |
Insulation resistance | 500VAC (between isolated circuits) | |
Weight | Approx. 170g | |
International standard | UL/cUL | UL508 |
EU Directives and UK legislation | EN61800-3: 2004 (2004/108/EC) Second environment, Category C3 | |
EN61800-5-1: 2007 (2006/95/EC) SELV |
CompoNet Communications Specifications
Item | Specification |
Slave type | Word Slave Unit (Mixed) |
Certification | CompoNet Conformance Tested |
CompoNet Profile | AC Drive (0x02) |
Node Address | 0 to 63, set with inverter parameter P190 or the rotary switches. |
Communication power supply | - (External power not required) |
Baud rates supported | 4 Mbps, 3 Mbps, 1.5 Mbps, 93.75 kbps. Automatically detecting baud rate of Master Unit |
Default Connection path | Supported, set with inverter parameter P046 |
Supported Assemblies | Basic Remote IO (Output assembly 20, Input assembly 70) Extended Speed IO (21, 71) Extended Speed and Torque Control (123, 173) Special IO (100, 150) Extended Control IO (101, 151) Extended Control IO and Multi function IO monitor (101, 153) Flexible Format (139, 159) Extended Speed and Acceleration Control (110, 111) |
EDS file | Depending on the MX2 inverter model |
MX2-Series DeviceNet Communication Unit 3G3AX-MX2-DRT-E
This is the communication unit to connect the Multi-function Compact Inverter MX2 to DeviceNet network.
Common Specification
Item | Specification | |
Power supply | Supplied from the inverter | |
Protective structure | IP20 | |
Ambient operating temperature | - 10 to 50 °C | |
Ambient storage temperature | - 20 to 65 °C | |
Ambient operating humidity | 20 to 90%RH (with no condensation) | |
Vibration resistance | 5.9m/s2 (0.6G), 10 to 55Hz | |
Application environment | At a maximum altitude of 1,000 m; indoors (without corrosive gases or dust) | |
Insulation resistance | 500VAC (between isolated circuits) | |
Weight | Approx. 170g | |
International standard | UL/cUL | UL508 |
EU Directives and UK legislation | EN61800-3: 2004 (2004/108/EC) Second environment, Category C3 | |
EN61800-5-1: 2007 (2006/95/EC) SELV |
DeviceNet Communications Specifications
Item | Specification |
Certification | DeviceNet Conformance Tested |
DeviceNet Profile | AC Drive (0x02) |
Supported connections | Remote I/O: Master-Slave connection Poll Bit-Strobe COS Cyclic Explicit Messages Conform to DeviceNet specifications |
Communication power supply | 11 to 25VDC (MAX 50 mA, type 20 mA) |
Unit device address range | MAC ID 0 to 63, set with inverter parameter P192 |
Baud rates supported | 125, 250, or 500kbps. Automatically detects baud rate of Master Unit. |
Default Connection path | Supported, set with inverter parameter P046 |
Supported Assemblies | Basic Remote IO (Output assembly 20, Input assembly 70) Extended Speed IO (21, 71) Extended Speed and Torque Control (123, 173) Special IO (100, 150) Extended Control IO (101, 151) Extended Control IO and Multi function IO monitor (101, 153) Flexible Format (139, 159) Extended Speed and Acceleration Control (110, 111) In case the DeviceNet master is configured using user allocation, only the input/ output pairs can be configured. |
EDS file | Depending on the MX2 Inverter model |
Options
Regenerative Braking Unit 3G3AX-RBU[][]
Used with a Braking Resistor when the deceleration time of the motor is needed to be reduced in the MX2.
Built-in Resistance Type (3G3AX-RBU21/-RBU22/-RBU41)
Class | 3-phase 200-V class | 3-phase 400-V class | ||
Model name (3G3AX-) | RBU21 | RBU22 | RBU41 *1 | |
Connection resistance | 17 Ω min. | 17 Ω min. | 34 Ω min. | |
Operating voltage ON/OFF | ON: 362.5 ± 5 V OFF: 355 ± 5 V (-5% or -10% setting available) | ON: 725 ± 5 V OFF: 710 ± 5 V (-5% or -10% setting available) | ||
Operation indication | LED ON (Lit) | |||
Parallel interlocking operation function *2 | 5 units max. | |||
Built-in resistor | Internal resistance | 120 W, 180 W | 120 W, 20 W | 120 W, 180 W × 2 in series |
Allowable consecutive ON time | 10 s max. | 0.5 s max. | 10 s max. | |
Allowable operation cycle | Cycle 1/10 (ON for 10 s, OFF for 90 s) | Cycle 1/80 (ON for 0.5 s, OFF for 40 s) | Cycle 1/10 (ON for 10 s, OFF for 90 s) | |
Power consumption | Instantaneous 0.73 kW Short-time rating 120 W | Instantaneous 6.6 kW Short-time rating 120 W | Instantaneous 1.46 kW Short-time rating 240 W | |
Protective function | Built-in resistor overheat protection | • Cooling fin temperatureRelay operates at approximately 200°C or higher. Recovers at approximately 170°C or lower. • Built-in temperature fuse (recovery impossible) *3 • Rating of contact250 V AC 200mA (R load) 12 V DC 500mA (R load) 42 V DC 200mA (R load) • Minimum load1mA (R load) | ||
Operating environ- ment | Ambient temperature | -10 to 50°C | ||
Ambient storage temperature | -20 to 65°C | |||
Ambient operating humidity | 20% to 90% (with no condensation) | |||
Vibration | 5.9 m/s2 (0.6G) 10 to 55 Hz | |||
Location | At a maximum altitude of 1,000 m (without corrosive gases or dust) | |||
Paint color | Munselle 5Y7/1 (cooling fan: aluminum ground color) |
*1 To use the braking resistor (Model: 3G3AX-RAB/RBB/RBC) for the 400-V class regenerative braking unit, be sure to remove the built-in resistor and connect two resistors of the same model in series. Using a 400-V class regenerative braking unit with only a single braking resistor connected may cause damage to the braking resistor.
*2 Use DIP switches to set the number of connected units.
*3 The built-in resistor has a thermal fuse. If the alarm terminals are not connected, the fuse may blow out in order to prevent the resistor from burning due to overheating. If the fuse blows out, the built-in resistor must be replaced.
*2 Use DIP switches to set the number of connected units.
*3 The built-in resistor has a thermal fuse. If the alarm terminals are not connected, the fuse may blow out in order to prevent the resistor from burning due to overheating. If the fuse blows out, the built-in resistor must be replaced.
Braking Resistor 3G3AX-RBA/-RBB/-RBC[][][][]
Consumes the regenerative motor energy with a resistor to reduce deceleration time.
Model | Compact type (3G3AX-RBA[][][][]) | Standard type (3G3AX-RBB[][][][]) | Medium capacity type (3G3AX-RBC[][][][]) | |||||||||
1201 | 1202 | 1203 | 1204 | 2001 | 2002 | 3001 | 4001 | 4001 | 6001 | 12001 | ||
Resistance | Capacity | 120 W | 200 W | 300 W | 400 W | 400 W | 600 W | 1200 W | ||||
Resistance (Ω) | 180 | 100 | 50 | 35 | 180 | 100 | 50 | 35 | 50 | 35 | 17 | |
Allowable brakingfrequency (%) | 5 | 2.5 | 1.5 | 1.0 | 10 | 7.5 | 7.5 | 7.5 | 10 | |||
Allowable continuousbraking time (s) | 20 | 12 | 5 | 3 | 30 | 20 | 10 | |||||
Weight (kg) | 0.27 | 0.97 | 1.68 | 2.85 | 2.5 | 3.6 | 6.5 | |||||
Fault detection function | Built-in thermal (Contact capacity: 240 V AC 2 A max.) Minimum current: 5 mA, Normally ON (NC contact) Built-in temperature fuse (recovery impossible) * | Built-in temperature relay, Normally ON (NC contact) Contact capacity: 240 V AC 3 A (R load), 0.2 A (L load), 36 V DC 2 A (R load) | ||||||||||
General specifi- cations | Ambient operating temperature | -10 to 50°C | ||||||||||
Ambient storage temperature | -20 to 65°C | |||||||||||
Ambient operating humidity | 20% to 90% (RH) with no condensation | |||||||||||
Vibration | 5.9 m/s (0.6 G) 10 to 55 Hz Complies with JISC0911 | |||||||||||
Location | At a maximum altitude of 1,000 m (without corrosive gases or dust) | |||||||||||
Cooling method | Self-cooling |
* Built-in resistors are equipped with thermal fuses. If the alarm is not connected, the fuse may blow to prevent burnout
due to overheating. If the fuse blows, the built-in resistor will need to be replaced.
due to overheating. If the fuse blows, the built-in resistor will need to be replaced.
Radio Noise Filter 3G3AX-ZCL[]
Connected to the inverter input/output cables to reduce noise coming into the inverter from the power supply line and noise flowing from the inverter into the power supply line.
3G3AX-ZCL1
Note: Select options by the maximum applicable motor capacity of heavy and light load rating.
3G3AX-ZCL2
Note: Select options by the maximum applicable motor capacity of heavy and light load rating.
Input Noise Filter 3G3AX-NFI[][]
Reduces noise coming into the inverter from the power supply line and noise flowing from the inverter into the power supply line. Connect as close to the Inverter as possible.
Power supply | Model | Inverter model | Rated input current In (A) at an ambient temperature of 50°C | Power loss (W) | Leakage current (mA/phase) at 60 Hz |
3-phase 200 VAC | 3G3AX-NFI21 | 3G3MX2-A2001-V1 | 3 × 6 A | 3 | < 1.5 (250 V) |
3G3AX-NFI21 | 3G3MX2-A2002-V1 | 3 × 6 A | 3 | < 1.5 (250 V) | |
3G3AX-NFI21 | 3G3MX2-A2004-V1 | 3 × 6 A | 3 | < 1.5 (250 V) | |
3G3AX-NFI22 | 3G3MX2-A2007-V1 | 3 × 10 A | 4 | < 1.5 (250 V) | |
3G3AX-NFI23 | 3G3MX2-A2015-V1 | 3 × 20 A | 6 | < 1.5 (250 V) | |
3G3AX-NFI23 | 3G3MX2-A2022-V1 | 3 × 20 A | 6 | < 1.5 (250 V) | |
3G3AX-NFI24 | 3G3MX2-A2037-V1 | 3 × 30 A | 9 | < 1.5 (250 V) | |
3G3AX-NFI25 | 3G3MX2-A2055-V1 | 3 × 40 A | 12 | < 1.5 (250 V) | |
3G3AX-NFI26 | 3G3MX2-A2075-V1 | 3 × 60 A | 17 | < 1.5 (250 V) | |
3G3AX-NFI27 | 3G3MX2-A2110-V1 | 3 × 80 A | 21 | < 1.5 (250 V) | |
1-phase 200 VAC | 3G3AX-NFI21 | 3G3MX2-AB001-V1 | 3 × 6 A | 3 | < 1.5 (250 V) |
3G3AX-NFI21 | 3G3MX2-AB002-V1 | 3 × 6 A | 3 | < 1.5 (250 V) | |
3G3AX-NFI22 | 3G3MX2-AB004-V1 | 3 × 10 A | 4 | < 1.5 (250 V) | |
3G3AX-NFI23 | 3G3MX2-AB007-V1 | 3 × 20 A | 6 | < 1.5 (250 V) | |
3G3AX-NFI24 3G3AX-NFI23 * | 3G3MX2-AB015-V1 | 3 × 30 A 3 × 20 A | 9 6 | < 1.5 (250 V) | |
3G3AX-NFI24 | 3G3MX2-AB022-V1 | 3 × 30 A | 9 | < 1.5 (250 V) | |
3-phase 400 VAC | 3G3AX-NFI41 | 3G3MX2-A4004-V1 | 3 × 7 A | 2 | < 7.5 (480 V) |
3G3AX-NFI41 | 3G3MX2-A4007-V1 | 3 × 7 A | 2 | < 7.5 (480 V) | |
3G3AX-NFI41 | 3G3MX2-A4015-V1 | 3 × 7 A | 2 | < 7.5 (480 V) | |
3G3AX-NFI42 | 3G3MX2-A4022-V1 | 3 × 10 A | 4 | < 7.5 (480 V) | |
3G3AX-NFI42 | 3G3MX2-A4030-V1 | 3 × 10 A | 4 | < 7.5 (480 V) | |
3G3AX-NFI43 | 3G3MX2-A4040-V1 | 3 × 20 A | 6 | < 7.5 (480 V) | |
3G3AX-NFI43 | 3G3MX2-A4055-V1 | 3 × 20 A | 6 | < 7.5 (480 V) | |
3G3AX-NFI44 | 3G3MX2-A4075-V1 | 3 × 30 A | 9 | < 7.5 (480 V) | |
3G3AX-NFI45 | 3G3MX2-A4110-V1 | 3 × 40 A | 12 | < 7.5 (480 V) | |
3G3AX-NFI46 | 3G3MX2-A4150-V1 | 3 × 50 A | 15 | < 7.5 (480 V) |
* With the 3G3AX-NFI23, only the CT rating is supported.
Model | Case enclosure rating | Terminal size | Wire dia. | Weight (kg) |
3G3AX-NFI21 | Plastic, IP00 | M4 | 1.25 mm2 | 0.5 |
3G3AX-NFI22 | Plastic, IP00 | M4 | 2 mm2 | 0.6 |
3G3AX-NFI23 | Plastic, IP00 | M4 | 2 mm2, 3.5 mm2 | 0.7 |
3G3AX-NFI24 | Plastic, IP00 | M4 | 5.5 mm2 | 0.8 |
3G3AX-NFI25 | Plastic, IP00 | M5 | 8 mm2 | 1.4 |
3G3AX-NFI26 | Plastic, IP00 | M5 | 14 mm2 | 1.8 |
3G3AX-NFI27 | Metal, IP00 | M6 | 22 mm2 | 3.6 |
3G3AX-NFI41 | Plastic, IP00 | M4 | 1.25 mm2, 2 mm2 | 0.7 |
3G3AX-NFI42 | Plastic, IP00 | M4 | 2 mm2 | 0.7 |
3G3AX-NFI43 | Plastic, IP00 | M4 | 2 mm2, 3.5 mm2 | 0.7 |
3G3AX-NFI44 | Plastic, IP00 | M4 | 5.5 mm2 | 0.8 |
3G3AX-NFI45 | Plastic, IP00 | M5 | 8 mm2 | 1.4 |
3G3AX-NFI46 | Plastic, IP00 | M5 | 14 mm2 | 1.6 |
Note: Select options by the maximum applicable motor capacity of heavy and light load rating.
Output Noise Filter 3G3AX-NFO[][]
Reduces noise generated by the Inverter. Connect as close to the Inverter as possible.
Power supply | Model | Rated current (A) | Inverter model | Weight (kg) | ||
3-phase AC 200 V class | 1-phase AC 200 V class | 3-phase AC 400 V class | ||||
3-phase, 3-wire Rated voltage 500 VAC | 3G3AX-NFO01 | 6 | 3G3MX2-A2001-V1/ -A2002-V1/ -A2004-V1 | 3G3MX2-AB001-V1 /-AB002-V1 /-AB004-V1 | 3G3MX2-A4004-V1/ -A4007-V1 | 0.7 |
3G3AX-NFO02 | 12 | 3G3MX2-A2007-V1/ -A2015-V1 | 3G3MX2-AB007-V1 /-AB015-V1 | 3G3MX2-A4015-V1/ -A4022-V1/-A4030-V1 | 0.9 | |
3G3AX-NFO03 | 25 | 3G3MX2-A2022-V1/ -A2037-V1 | 3G3MX2-AB022-V1 | 3G3MX2-A4040-V1/ -A4055-V1/-A4075-V1 | 2.1 | |
3G3AX-NFO04 | 50 | 3G3MX2-A2055-V1/ -A2075-V1 | - | 3G3MX2-A4110-V1/ -A4150-V1 | 3.7 | |
3G3AX-NFO05 | 75 | 3G3MX2-A2110-V1 /-A2150-V1 | - | - | 5.7 |
Note: Select options by the maximum applicable motor capacity of heavy and light load rating.
DC Reactor 3G3AX-DL[][][][]
Used to suppress harmonic current generated from the Inverter.
Suppresses harmonic current better than the AC Reactor and can be used with the AC Reactor.
Suppresses harmonic current better than the AC Reactor and can be used with the AC Reactor.
Inverter | DC reactor specifications | |||||||||
Voltage class | Max. applicable motor capacity (kW) | Model | Heavy load: CT, Light load: VT mode | Max. appli-cable motor capacity (kW) | Rated input current (A) | Model | Induc-tance (mH) | Heat gene-ration (W) | Operating ambient temperature/ humidity | Location |
3-phase 200-V class | 0.1 | 3G3MX2- A2001-V1 | Heavy load * | 0.1 | 1.0 | 3G3AX- DL2002 | 21.4 | 8 | -10 to 50°C 20% to 90% | At an altitude of 1,000 m max.; indoors (without corrosive gases or dust) |
Light load | 0.2 | 1.2 | ||||||||
0.2 | 3G3MX2- A2002-V1 | Heavy load * | 0.2 | 1.6 | ||||||
Light load | 0.4 | 1.9 | 3G3AX- DL2004 | 10.7 | ||||||
0.4 | 3G3MX2- A2004-V1 | Heavy load * | 0.4 | 3.3 | ||||||
Light load | 0.75 | 3.9 | 3G3AX- DL2007 | 6.75 | 10 | |||||
0.75 | 3G3MX2- A2007-V1 | Heavy load * | 0.75 | 6.0 | ||||||
Light load | 1.1 | 7.2 | 3G3AX- DL2015 | 3.51 | ||||||
1.5 | 3G3MX2- A2015-V1 | Heavy load * | 1.5 | 9.0 | ||||||
Light load | 2.2 | 10.8 | 3G3AX- DL2022 | 2.51 | 13 | |||||
2.2 | 3G3MX2- A2022-V1 | Heavy load * | 2.2 | 12.7 | ||||||
Light load | 3.0 | 13.9 | 3G3AX- DL2037 | 1.60 | 20 | |||||
3.7 | 3G3MX2- A2037-V1 | Heavy load * | 3.7 | 20.5 | ||||||
Light load | 5.5 | 23.0 | 3G3AX- DL2055 | 1.11 | 26 | |||||
5.5 | 3G3MX2- A2055-V1 | Heavy load * | 5.5 | 30.8 | 3G3AX- DL2075 | 0.84 | 36 | |||
Light load | 7.5 | 37.0 | ||||||||
7.5 | 3G3MX2- A2075-V1 | Heavy load * | 7.5 | 39.6 | ||||||
Light load | 11 | 48.0 | 3G3AX- DL2110 | 0.59 | 52 | |||||
11 | 3G3MX2- A2110-V1 | Heavy load * | 11 | 57.1 | ||||||
Light load | 15 | 68.0 | 3G3AX- DL2150 | 0.44 | 60 | |||||
15 | 3G3MX2- A2150-V1 | Heavy load * | 15 | 62.6 | ||||||
Light load | 18.5 | 72.0 | 3G3AX- DL2220 | 0.30 | 63 | |||||
Single-phase 200-V Class | 0.1 | 3G3MX2- AB001-V1 | Heavy load * | 0.1 | 1.3 | 3G3AX- DL2002 | 21.4 | 8 | -10 to 50°C 20% to 90% | At an altitude of 1,000 m max.; indoors (without corrosive gases or dust) |
Light load | 0.2 | 2.0 | ||||||||
0.2 | 3G3MX2- AB002-V1 | Heavy load * | 0.2 | 3.0 | ||||||
Light load | 0.4 | 3.6 | 3G3AX- DL2004 | 10.7 | ||||||
0.4 | 3G3MX2- AB004-V1 | Heavy load * | 0.4 | 6.3 | ||||||
Light load | 0.55 | 7.3 | 3G3AX- DL2007 | 6.75 | 10 | |||||
0.75 | 3G3MX2- AB007-V1 | Heavy load * | 0.75 | 11.5 | ||||||
Light load | 1.1 | 13.8 | 3G3AX- DL2015 | 3.51 | ||||||
1.5 | 3G3MX2- AB015-V1 | Heavy load * | 1.5 | 16.8 | ||||||
Light load | 2.2 | 20.2 | 3G3AX- DL2022 | 2.51 | 13 | |||||
2.2 | 3G3MX2- AB022-V1 | Heavy load * | 2.2 | 22.0 | ||||||
Light load | 3.0 | 24.0 | 3G3AX- DL2037 | 1.60 | 20 | |||||
3-phase 400-V class | 0.4 | 3G3MX2- A4004-V1 | Heavy load * | 0.4 | 1.8 | 3G3AX- DL4004 | 43.0 | 10 | -10 to 50°C 20% to 90% | At an altitude of 1,000 m max.; indoors (without corrosive gases or dust) |
Light load | 0.75 | 2.1 | 3G3AX- DL4007 | 27.0 | ||||||
0.75 | 3G3MX2- A4007-V1 | Heavy load * | 0.75 | 3.6 | ||||||
Light load | 1.5 | 4.3 | 3G3AX- DL4015 | 14.0 | ||||||
1.5 | 3G3MX2- A4015-V1 | Heavy load * | 1.5 | 5.2 | ||||||
Light load | 2.2 | 5.9 | 3G3AX- DL4022 | 10.1 | 13 | |||||
2.2 | 3G3MX2- A4022-V1 | Heavy load * | 2.2 | 6.5 | ||||||
Light load | 3.0 | 8.1 | 3G3AX- DL4037 | 6.4 | 20 | |||||
3.0 | 3G3MX2- A4030-V1 | Heavy load * | 3.0 | 7.7 | ||||||
Light load | 4.0 | 9.4 | ||||||||
4.0 | 3G3MX2- A4040-V1 | Heavy load * | 4.0 | 11.0 | ||||||
Light load | 5.5 | 13.3 | 3G3AX- DL4055 | 4.41 | 26 | |||||
5.5 | 3G3MX2- A4055-V1 | Heavy load * | 5.5 | 16.9 | ||||||
Light load | 7.5 | 20.0 | 3G3AX- DL4075 | 3.35 | 36 | |||||
7.5 | 3G3MX2- A4075-V1 | Heavy load * | 7.5 | 18.8 | ||||||
Light load | 11 | 24.0 | 3G3AX- DL4110 | 2.33 | 52 | |||||
11 | 3G3MX2- A4110-V1 | Heavy load * | 11 | 29.4 | ||||||
Light load | 15 | 38.0 | 3G3AX- DL4150 | 1.75 | 60 | |||||
15 | 3G3MX2- A4150-V1 | Heavy load * | 15 | 35.9 | ||||||
Light load | 18.5 | 44.0 | 3G3AX- DL4220 | 1.2 | 67 |
* The DC reactor model for the heavy-load mode is selected with reference to the rated current value of a general-purpose motor, which is 85% of the rated output current of the inverter. If you intend to constantly drive a motor whose rated current value exceeds 85% of the rated output current of the inverter, use the DC reactor model selected for the light-load mode.
AC Reactor 3G3AX-AL[][][][]
Connect the AC Reactor if the capacity of the power supply is much larger than that of the Inverter or the power factor is required to be improved.
Inverter | DC reactor specifications | |||||||||
Voltage class | Max. applicable motor capacity (kW) | Model | Heavy load: CT, Light load: VT mode | Max. appli-cable motor capacity (kW) | Rated input current (A) | Model | Induc-tance (mH) | Heat gene-ration (W) | Operating ambient temperature/ humidity | Location |
3-phase 200-V class | 0.1 | 3G3MX2- A2001-V1 | Heavy load | 0.1 | 1.0 | 3G3AX- AL2025 | 2.8 | 12 | -10 to 50°C 20% to 90% | At an altitude of 1,000 m max.; indoors (without corrosive gases or dust) |
Light load | 0.2 | 1.2 | ||||||||
0.2 | 3G3MX2- A2002-V1 | Heavy load | 0.2 | 1.6 | ||||||
Light load | 0.4 | 1.9 | ||||||||
0.4 | 3G3MX2- A2004-V1 | Heavy load | 0.4 | 3.3 | ||||||
Light load | 0.75 | 3.9 | ||||||||
0.75 | 3G3MX2- A2007-V1 | Heavy load | 0.75 | 6.0 | ||||||
Light load | 1.1 | 7.2 | ||||||||
1.5 | 3G3MX2- A2015-V1 | Heavy load | 1.5 | 9.0 | ||||||
Light load | 2.2 | 10.8 | 3G3AX- AL2055 | 0.88 | 25 | |||||
2.2 | 3G3MX2- A2022-V1 | Heavy load | 2.2 | 12.7 | ||||||
Light load | 3.0 | 13.9 | ||||||||
3.7 | 3G3MX2- A2037-V1 | Heavy load | 3.7 | 20.5 | 3G3AX- AL2110 | 0.35 | 50 | |||
Light load | 5.5 | 23.0 | ||||||||
5.5 | 3G3MX2- A2055-V1 | Heavy load | 5.5 | 30.8 | ||||||
Light load | 7.5 | 37.0 | ||||||||
7.5 | 3G3MX2- A2075-V1 | Heavy load | 7.5 | 39.6 | 3G3AX- AL2220 | 0.18 | 50 | |||
Light load | 11 | 48.0 | ||||||||
11 | 3G3MX2- A2110-V1 | Heavy load | 11 | 57.1 | ||||||
Light load | 15 | 68.0 | ||||||||
15 | 3G3MX2- A2150-V1 | Heavy load | 15 | 62.6 | ||||||
Light load | 18.5 | 72.0 | 3G3AX- AL2330 | 0.09 | 85 | |||||
Single- phase 200-V Class | 0.1 | 3G3MX2- AB001-V1 | Heavy load | 0.1 | 1.3 | 3G3AX- AL2025 | 2.8 | 12 | -10 to 50°C 20% to 90% | At an altitude of 1,000 m max.; indoors (without corrosive gases or dust) |
Light load | 0.2 | 2.0 | ||||||||
0.2 | 3G3MX2- AB002-V1 | Heavy load | 0.2 | 3.0 | ||||||
Light load | 0.4 | 3.6 | ||||||||
0.4 | 3G3MX2- AB004-V1 | Heavy load | 0.4 | 6.3 | ||||||
Light load | 0.55 | 7.3 | ||||||||
0.75 | 3G3MX2- AB007-V1 | Heavy load | 0.75 | 11.5 | 3G3AX- AL2055 | 0.88 | 25 | |||
Light load | 1.1 | 13.8 | ||||||||
1.5 | 3G3MX2- AB015-V1 | Heavy load | 1.5 | 16.8 | ||||||
Light load | 2.2 | 20.2 | 3G3AX- AL2110 | 0.35 | 50 | |||||
2.2 | 3G3MX2- AB022-V1 | Heavy load | 2.2 | 22.0 | ||||||
Light load | 3.0 | 24.0 | ||||||||
3-phase 400-V class | 0.4 | 3G3MX2- A4004-V1 | Heavy load | 0.4 | 1.8 | 3G3AX- AL4025 | 7.7 | 12 | -10 to 50°C 20% to 90% | At an altitude of 1,000 m max.; indoors (without corrosive gases or dust) |
Light load | 0.75 | 2.1 | ||||||||
0.75 | 3G3MX2- A4007-V1 | Heavy load | 0.75 | 3.6 | ||||||
Light load | 1.5 | 4.3 | ||||||||
1.5 | 3G3MX2- A4015-V1 | Heavy load | 1.5 | 5.2 | ||||||
Light load | 2.2 | 5.9 | ||||||||
2.2 | 3G3MX2- A4022-V1 | Heavy load | 2.2 | 6.5 | 3G3AX- AL4055 | 3.5 | 25 | |||
Light load | 3.0 | 8.1 | ||||||||
3.0 | 3G3MX2- A4030-V1 | Heavy load | 3.0 | 7.7 | ||||||
Light load | 4.0 | 9.4 | ||||||||
4.0 | 3G3MX2- A4040-V1 | Heavy load | 4.0 | 11.0 | 3G3AX- AL4110 | 1.3 | 50 | |||
Light load | 5.5 | 13.3 | ||||||||
5.5 | 3G3MX2- A4055-V1 | Heavy load | 5.5 | 16.9 | ||||||
Light load | 7.5 | 20.0 | ||||||||
7.5 | 3G3MX2- A4075-V1 | Heavy load | 7.5 | 18.8 | ||||||
Light load | 11 | 24.0 | 3G3AX- AL4220 | 0.74 | 60 | |||||
11 | 3G3MX2- A4110-V1 | Heavy load | 11 | 29.4 | ||||||
Light load | 15 | 38.0 | 3G3AX- AL4330 | 0.36 | 90 | |||||
15 | 3G3MX2- A4150-V1 | Heavy load | 15 | 35.9 | ||||||
Light load | 18.5 | 44.0 |