Performance Specifications
Inverter 3G3RX2
3-phase 200-V Class
Very Low Duty (VLD)/Low Duty (LD)/Normal Duty (ND)
3G3RX2-A2[][][][][]
A2004
A2007
A2015
A2022
A2037
Applicable motor
(4-pole) capacity (kW)
VLD
0.75
1.5
2.2
3.7
5.5
LD
0.75
1.5
2.2
3.7
5.5
ND
0.4
0.75
1.5
2.2
3.7
Output
Rated output
current (A)
VLD
4.4
8.0
10.4
15.6
22.8
LD
3.7
6.3
9.4
12.0
19.6
ND
3.2
5.0
8.0
11.0
17.5
Overload
current rating
VLD
110% 60 sec / 120% 3 sec
LD
120% 60 sec / 150% 3 sec
ND
150% 60 sec / 200% 3 sec
Rated output voltage
3-phase (3-wire) 200 to 240 V (depending on receiving voltage)
Rated
capacity

(
kVA)
200 V
VLD
1.5
2.8
3.6
5.4
7.9
LD
1.3
2.2
3.3
4.2
6.8
ND
1.1
1.7
2.8
3.8
6.1
240 V
VLD
1.8
3.3
4.3
6.5
9.5
LD
1.5
2.6
3.9
5.0
8.1
ND
1.3
2.1
3.3
4.6
7.3
Input
Rated input
current (A) *1
VLD
5.2
9.5
12.4
18.6
27.1
LD
4.4
7.5
11.2
14.3
23.3
ND
3.8
6.0
9.5
13.1
20.8
Rated input AC voltage
Control power supply: Power supply single phase 200 to 240 V/allowable
variation range 170 to 264 V,

50 Hz (allowable variation range: 47.5 to 52.5 Hz)/60 Hz (allowable variation

range: 57 to 63 Hz)
Main circuit power supply: 3-phase (3-wire) 200 to 240 V/allowable variation
range 170 to 264 V,

50 Hz (allowable variation range: 47.5 to 52.5 Hz)/60 Hz (allowable variation

range: 57 to 63 Hz)
Power supply
equipment

capacity (
kVA) *2
VLD
2.0
3.6
4.7
7.1
10.3
LD
1.7
2.9
4.3
5.4
8.9
ND
1.5
2.3
3.6
5.0
7.9
Carrier frequency operating
range *3
VLD
0.5 to 10.0 kHz
LD
0.5 to 12.0 kHz
ND
0.5 to 16.0 kHz
Motor start torque *4
200%/0.3 Hz
Braking
Regenerative braking
Equipped with BRD circuit (with a discharging resistor separately installed)
Minimum resistance that
can be connected (Ω)
50
50
35
35
35
Dimension
Height (mm)
255
255
255
255
255
Width (mm)
150
150
150
150
150
Depth (mm)
140
140
140
140
140
Protective construction
IP20 *5 / UL open type
Approximate mass (kg)
3
3
3
3
3
3G3RX2-A2[][][][][]
A2055
A2075
A2110
A2150
A2185
Applicable motor
(4-pole) capacity (kW)
VLD
7.5
11
15
18.5
22
LD
7.5
11
15
18.5
22
ND
5.5
7.5
11
15
18.5
Output
Rated output
current (A)
VLD
33.0
46.0
60.0
80.0
93.0
LD
30.0
40.0
56.0
73.0
85.0
ND
25.0
32.0
46.0
64.0
76.0
Overload
current rating
VLD
110% 60 sec / 120% 3 sec
LD
120% 60 sec / 150% 3 sec
ND
150% 60 sec / 200% 3 sec
Rated output voltage
3-phase (3-wire) 200 to 240 V (depending on receiving voltage)
Rated
capacity

(
kVA)
200 V
VLD
11.4
15.9
20.8
27.7
32.2
LD
10.4
13.9
19.4
25.3
29.4
ND
8.7
11.1
15.9
22.2
26.3
240 V
VLD
13.7
19.1
24.9
33.3
38.7
LD
12.5
16.6
23.3
30.3
35.3
ND
10.4
13.3
19.1
26.6
31.6
Input
Rated input
current (A) *1
VLD
39.3
54.8
71.4
95.2
110.7
LD
35.7
47.6
66.7
86.9
101.2
ND
29.8
38.1
54.8
76.2
90.5
Rated input AC voltage
Control power supply: Power supply single phase 200 to 240 V/allowable
variation range 170 to 264 V,

50 Hz (allowable variation range: 47.5 to 52.5 Hz)/60 Hz (allowable variation

range: 57 to 63 Hz)
Main circuit power supply: 3-phase (3-wire) 200 to 240 V/allowable variation
range 170 to 264 V,

50 Hz (allowable variation range: 47.5 to 52.5 Hz)/60 Hz (allowable variation

range: 57 to 63 Hz)
Power supply
equipment

capacity (
kVA) *2
VLD
15.0
20.9
27.2
36.3
42.2
LD
13.6
18.1
25.4
33.1
38.6
ND
11.3
14.5
20.9
29.0
34.5
Carrier frequency operating
range *3
VLD
0.5 to 10.0 kHz
LD
0.5 to 12.0 kHz
ND
0.5 to 16.0 kHz
Motor start torque *4
200%/0.3 Hz
Braking
Regenerative braking
Equipped with BRD circuit (with a discharging resistor separately installed)
Minimum resistance that
can be connected (Ω)
16
10
10
7.5
7.5
Dimension
Height (mm)
260
260
260
390
390
Width (mm)
210
210
210
245
245
Depth (mm)
170
170
170
190
190
Protective construction
IP20 *5 / UL open type
Approximate mass (kg)
6
6
6
10
10
3G3RX2-A2[][][][][]
A2220
A2300
A2370
A2450
A2550
Applicable motor
(4-pole) capacity (kW)
VLD
30
37
45
55
75
LD
30
37
45
55
75
ND
22
30
37
45
55
Output
Rated output
current (A)
VLD
124
153
185
229
295
LD
113
140
169
210
270
ND
95.0
122
146
182
220
Overload
current rating
VLD
110% 60 sec / 120% 3 sec
LD
120% 60 sec / 150% 3 sec
ND
150% 60 sec / 200% 3 sec
Rated output voltage
3-phase (3-wire) 200 to 240 V (depending on receiving voltage)
Rated
capacity

(
kVA)
200 V
VLD
43.0
53.0
64.1
79.3
102.2
LD
39.1
48.5
58.5
72.7
93.5
ND
32.9
42.3
50.6
63.0
76.2
240 V
VLD
51.5
63.6
76.9
95.2
122.6
LD
47.0
58.2
70.3
87.3
112.2
ND
39.5
50.7
60.7
75.7
91.5
Input
Rated input
current (A) *1
VLD
147.6
182.1
220.2
272.6
351.2
LD
134.5
166.7
201.2
250.0
321.4
ND
113.1
145.2
173.8
216.7
261.9
Rated input AC voltage
Control power supply: Power supply single phase 200 to 240 V/allowable
variation range 170 to 264 V,

50 Hz (allowable variation range: 47.5 to 52.5 Hz)/60 Hz (allowable variation

range: 57 to 63 Hz)
Main circuit power supply: 3-phase (3-wire) 200 to 240 V/allowable variation
range 170 to 264 V,

50 Hz (allowable variation range: 47.5 to 52.5 Hz)/60 Hz (allowable variation

range: 57 to 63 Hz)
Power supply
equipment

capacity (
kVA) *2
VLD
56.3
69.4
83.9
103.9
133.8
LD
51.3
63.5
76.7
95.3
122.5
ND
43.1
55.3
66.2
82.6
99.8
Carrier frequency operating
range *3
VLD
0.5 to 10.0 kHz
LD
0.5 to 12.0 kHz
ND
0.5 to 16.0 kHz
Motor start torque *4
200%/0.3 Hz
Braking
Regenerative braking
Equipped with BRD circuit
(with a discharging resistor

separately installed)
Regenerative braking unit separately
installed
Minimum resistance that
can be connected (Ω)
5
---
---
---
---
Dimension
Height (mm)
390
540
550
550
700
Width (mm)
245
300
390
390
480
Depth (mm)
190
195
250
250
250
Protective construction
IP20 *5 / UL open type
Approximate mass (kg)
10
22
33
33
47
*1. The rated input currents shown in the table are the values when the rated current is output. The values vary depending on impedance on the power supply (wiring, breaker, input reactor option, etc.)
*2. The power supply equipment capacities shown in the table are the values when 220 V rated current is output. The values vary depending on impedance on the power supply (wiring, breaker, input reactor option, etc.)

*3. The setting of rated values for carrier frequencies [bb101]
/[bb201] are internally limited in accordance with the description. Also, it is recommended to set values equivalent to or above (maximum output frequency for driving ×10) Hz for the setting of carrier frequencies [bb101]/[bb201]. Also, in the case of induction motor (IM) control, for items other than those subject to V/f control, it is recommended to set carrier frequency at 2 kHz or more. In the case of synchronous motor (SM)/permanent magnet motor (PMM) control, it is recommended to set carrier frequency at 8 kHz or more.
*4. The value of the sensor-less vector control applied to the ND rating in the Standard motor. Torque characteristics may vary depending on the control method and the motor used.
*5.
Based on self declaration.
3-phase 400-V Class
Very Low Duty (VLD)/Low Duty (LD)/Normal Duty (ND)
3G3RX2-[][][][][]
A4007
A4015
A4022
A4037
A4055
A4075
Applicable motor
(4-pole) capacity (kW)
VLD
1.5
2.2
3.7
5.5
7.5
11
LD
1.5
2.2
3.7
5.5
7.5
11
ND
0.75
1.5
2.2
3.7
5.5
7.5
Output
Rated output
current (A)
VLD
4.1
5.4
8.3
12.6
17.5
25.0
LD
3.1
4.8
6.7
11.1
16.0
22.0
ND
2.5
4.0
5.5
9.2
14.8
19.0
Overload
current rating
VLD
110% 60 sec / 120% 3 sec
LD
120% 60 sec / 150% 3 sec
ND
150% 60 sec / 200% 3 sec
Rated output voltage
3-phase (3-wire) 380 to 500 V (depending on receiving voltage)
Rated
capacity

(
kVA)
400 V
VLD
2.8
3.7
5.8
8.7
12.1
17.3
LD
2.1
3.3
4.6
7.7
11.1
15.2
ND
1.7
2.8
3.8
6.4
10.3
13.2
500 V
VLD
3.6
4.7
7.2
10.9
15.2
21.7
LD
2.7
4.2
5.8
9.6
13.9
19.1
ND
2.2
3.5
4.8
8.0
12.8
16.5
Input
Rated input
current (A) *1
VLD
4.9
6.4
9.9
15.0
20.8
29.8
LD
3.7
5.7
8.0
13.2
19.0
26.2
ND
3.0
4.8
6.5
11.0
17.6
22.6
Rated input AC voltage
Control power supply: Power supply single phase 380 to 500 V (allowable
variation range 323 to 550 V),

50 Hz (allowable variation range: 47.5 to 52.5 Hz)/60 Hz (allowable variation

range: 57 to 63 Hz)
Main circuit power supply: 3-phase (3-wire) 380 to 500 V (allowable variation
range) 323 to 550 V,

50 Hz (allowable variation range: 47.5 to 52.5 Hz)/60 Hz (allowable variation

range: 57 to 63 Hz)
Power supply
equipment

capacity (
kVA) *2
VLD
3.7
4.9
7.5
11.4
15.9
22.7
LD
2.8
4.4
6.1
10.1
14.5
20.0
ND
2.3
3.6
5.0
8.3
13.4
17.2
Carrier frequency range *3
VLD
0.5 to 10.0 kHz
LD
0.5 to 12.0 kHz
ND
0.5 to 16.0 kHz
Motor start torque *4
200%/0.3 Hz
Braking
Regenerative braking
Equipped with braking resistance circuit
(with a discharging resistor separately installed)
Minimum resistance that
can be connected (Ω)
100
100
100
70
70
35
Dimen-
sion
Height (mm)
255
255
255
255
260
260
Width (mm)
150
150
150
150
210
210
Depth (mm)
140
140
140
140
170
170
Protective construction
IP20 *5 / UL open type
Approximate mass (kg)
3
3
3
3
6
6
3G3RX2-[][][][][]
A4110
A4150
A4185
A4220
A4300
A4370
Applicable motor
(4-pole) capacity (kW)
VLD
15
18.5
22
30
37
45
LD
15
18.5
22
30
37
45
ND
11
15
18.5
22
30
37
Output
Rated output
current (A)
VLD
31.0
40.0
47.0
62.0
77.0
93.0
LD
29.0
37.0
43.0
57.0
70.0
85.0
ND
25.0
32.0
39.0
48.0
61.0
75.0
Overload
current rating
VLD
110% 60 sec / 120% 3 sec
LD
120% 60 sec / 150% 3 sec
ND
150% 60 sec / 200% 3 sec
Rated output voltage
3-phase (3-wire) 380 to 500 V (depending on receiving voltage)
Rated
capacity

(
kVA)
400 V
VLD
21.5
27.7
32.6
43.0
53.3
64.4
LD
20.1
25.6
29.8
39.5
48.5
58.9
ND
17.3
22.2
27.0
33.3
42.3
52.0
500 V
VLD
26.8
34.6
40.7
53.7
66.7
80.5
LD
25.1
32.0
37.2
49.4
60.6
73.6
ND
21.7
27.7
33.8
41.6
52.8
65.0
Input
Rated input
current (A) *1
VLD
36.9
47.6
56.0
73.8
91.7
110.7
LD
34.5
44.0
51.2
67.9
83.3
101.2
ND
29.8
38.1
46.4
57.1
72.6
89.3
Rated input AC voltage
Control power supply: Power supply single phase 380 to 500 V (allowable
variation range 323 to 550 V),

50 Hz (allowable variation range: 47.5 to 52.5 Hz)/60 Hz (allowable variation

range: 57 to 63 Hz)
Main circuit power supply: 3-phase (3-wire) 380 to 500 V (allowable variation
range) 323 to 550 V,

50 Hz (allowable variation range: 47.5 to 52.5 Hz)/60 Hz (allowable variation

range: 57 to 63 Hz)
Power supply
equipment

capacity (
kVA) *2
VLD
28.1
36.3
42.6
56.3
69.9
84.4
LD
26.3
33.6
39.0
51.7
63.5
77.1
ND
22.7
29.0
35.4
43.5
55.3
68.0
Carrier frequency range *3
VLD
0.5 to 10.0 kHz
LD
0.5 to 12.0 kHz
ND
0.5 to 16.0 kHz
Motor start torque *4
200%/0.3 Hz
Braking
Regenerative braking
Equipped with braking resistance circuit
(with a discharging resistor separately installed)
Minimum resistance that
can be connected (Ω)
35
24
24
20
15
15
Dimen-
sion
Height (mm)
260
390
390
390
540
550
Width (mm)
210
245
245
245
300
390
Depth (mm)
170
190
190
190
195
250
Protective construction
IP20 *5 / UL open type
Approximate mass (kg)
6
8.5
8.5
8.5
22
31
3G3RX2-[][][][][]
A4450
A4550
B4750
B4900
B411K
B413K
Applicable motor
(4-pole) capacity (kW)
VLD
55
75
90
110
132
160
LD
55
75
90
110
132
160
ND
45
55
75
90
110
132
Output
Rated output
current (A)
VLD
116
147
176
213
252
316
LD
105
135
160
195
230
290
ND
91.0
112
150
180
217
260
Overload
current rating
VLD
110% 60 sec / 120% 3 sec
LD
120% 60 sec / 150% 3 sec
ND
150% 60 sec / 200% 3 sec
Rated output voltage
3-phase (3-wire) 380 to 500 V (depending on receiving voltage)
Rated
capacity

(
kVA)
400 V
VLD
80.4
101.8
121.9
147.6
174.6
218.9
LD
72.7
93.5
110.9
135.1
159.3
200.9
ND
63.0
77.6
103.9
124.7
150.3
180.1
500 V
VLD
100.5
127.3
152.4
184.5
218.2
273.7
LD
90.9
116.9
138.6
168.9
199.2
251.1
ND
78.8
97.0
129.9
155.9
187.9
225.2
Input
Rated input
current (A) *1
VLD
138.1
175.0
209.5
253.6
300.0
376.2
LD
125.0
160.7
190.5
232.1
273.8
345.2
ND
108.3
133.3
178.6
214.3
258.3
309.5
Rated input AC voltage
Control power supply: Power supply single phase 380 to 500 V (allowable
variation range 323 to 550 V),

50 Hz (allowable variation range: 47.5 to 52.5 Hz)/60 Hz (allowable variation

range: 57 to 63 Hz)
Main circuit power supply: 3-phase (3-wire) 380 to 500 V (allowable variation
range) 323 to 550 V,

50 Hz (allowable variation range: 47.5 to 52.5 Hz)/60 Hz (allowable variation

range: 57 to 63 Hz)
Power supply
equipment

capacity (
kVA) *2
VLD
105.2
133.4
159.7
193.2
228.6
286.7
LD
95.3
122.5
145.2
176.9
208.7
263.1
ND
82.6
101.6
136.1
163.3
196.9
235.9
Carrier frequency range *3
VLD
0.5 to 10.0 kHz
0.5 to 8.0 kHz
LD
0.5 to 12.0 kHz
0.5 to 8.0 kHz
ND
0.5 to 16.0 kHz
0.5 to 10.0 kHz
Motor start torque *4
200%/0.3 Hz
180%/0.3 Hz
Braking
Regenerative braking
Regenerative braking unit separately installed
Minimum resistance that
can be connected (Ω)
10
10
---
---
---
---
Dimen-
sion
Height (mm)
550
550
700
700
740
740
Width (mm)
390
390
390
390
480
480
Depth (mm)
250
250
270
270
270
270
Protective construction
IP20 *5 / UL open type
IP00 / UL open type
Approximate mass (kg)
31
31
41
41
53
53
*1. The rated input currents shown in the table are the values when the rated current is output. The values vary depending on impedance on the power supply (wiring, breaker, input reactor option, etc.)
*2. The power supply equipment capacities shown in the table are the values when 220 V rated current is output. The values vary depending on impedance on the power supply (wiring, breaker, input reactor option, etc.)

*3. The setting of rated values for carrier frequencies [bb101]
/[bb201] are internally limited in accordance with the description. Also, it is recommended to set values equivalent to or above (maximum output frequency for driving ×10) Hz for the setting of carrier frequencies [bb101]/[bb201]. Also, in the case of induction motor (IM) control, for items other than those subject to V/f control, it is recommended to set carrier frequency at 2 kHz or more. In the case of synchronous motor (SM)/permanent magnet motor (PMM) control, it is recommended to set carrier frequency at 8 kHz or more.
*4. The value of the sensor-less vector control applied to the ND rating in the Standard motor. Torque characteristics
may vary depending on the control method and the motor used.
*5.
Based on self declaration.
Function Specifications
Inverter 3G3RX2
Item
Specifications
Control mode
(output to the motor)
Sine wave PWM control voltage output (line sine wave modulation)
Output frequency range *1
0.00 to 590.00 Hz
Frequency accuracy
Digital command ±0.01% and analog command ±0.2% (25°C±10°C) against the
maximum frequency
Frequency resolution
Digital setting: 0.01 Hz
Analog setting: maximum frequency/4000

(Ai1 terminal/Ai2 terminal: 12 bit/0 to +10 V or 0 to +20
mA, Ai3 terminal 12 bit/
-10 to +10 V)
Control mode
(frequency/voltage calculation) *2
IM
V/f control (fixed torque/reduced torque/free),
automatic boost control, cascade model

sensorless vector control, 0 Hz range
sensorless vector control, vector control with
sensor.
SM/PMM
Synchronous starting sensorless vector
control, IVMS starting smart
sensorless vector
control
Speed fluctuation *3
±0.5% (during sensorless vector control)
Acceleration or deceleration time
0.00 to 3600.00 sec (linear, S-shaped, U-shaped, reverse U-shaped, EL-S
shaped)
Display monitor
Output frequency, output current, output torque, trip history, I/O terminal status,
I/O power *4, P-N voltage.
Starting functions
Start after DC braking, frequency collection start, frequency entrainment start,
reduced voltage start, retry start
Stopping functions
Free-run stop, DC braking after deceleration stop or terminal DC braking (braking
power, operating speed adjustment)
Stall prevention function
Overload restraining function, overcurrent suppression function, overvoltage
suppression function
Protective function *5
Overcurrent error, Motor overload error, Braking resister Overload error,
Overvoltage error, Memory error,
Undervoltage error, Current detector error, CPU
error, External trip error, USP error, Ground fault error, Incoming over voltage

error, Instantaneous power failure error, Temperature detector error, Cooling fan

rotation speed reduction temperature error, Temperature error, Input open-phase

error, IGBT error, Output open-phase error,
Thermistor error, Brake error, Low-
speed range overload error, Controller overload error, RS485 communication

error, Operator keypad disconnection error.
Other functions
V/f free settings (7 points), Upper/lower limit frequency limiter, Frequency jump,
Curve acceleration/deceleration, Manual torque boost, Energy-saving operation,

Analog output adjustment function, Minimum frequency, Carrier frequency

adjustment, Motor electronic thermal function (free setting is also possible),

Inverter electronic thermal function, External start/end (volume/ratio), Frequency

input selection, Trip retry, Restart after instantaneous stop, Output of signals,

Initialization settings, PID control, Automatic deceleration at power shut-off, Brake

control function, and Auto-tuning for commercial switching function (online/offline).
Input
Fre-
quency
setting
Standard
operator

keypad
Parameter setting using arrow keys
External
signals *6
Ai1/Ai2 terminal (when changing
voltage)
Setting through input of 0 to 10 VDC voltage
(input impedance: 10 )
Ai1/Ai2 terminal (when changing
current)
Setting through input of 0 to 20 mA current
(input impedance: 100 Ω)
Ai3 terminal
Setting through input of -10 to +10 V voltage
(input impedance: 10
)
Multistage speed terminal (use
of input terminal function)
15 speed
Pulse string input
(A/B terminal, use of input

terminal function)
32 kHz × 2 at maximum
External port
Setting via RS485 serial communication (protocol: Modbus-RTU)
Normal
rotation/

reverse

rotation

Run/stop
Standard
operator

keypad
Execution with the RUN /STOP key
(normal rotation/reverse rotation can be switched by setting parameters)
External
signals
Normal rotation operation (FW)/reverse rotation (RV) (when an input terminal
function is assigned) 3-wire input available (when an input terminal function is

assigned)
External port
Setting via RS485 serial communication (protocol: Modbus-RTU (maximum:
115.2 kbps)
Input terminal function
11 terminals (input of pulse string is available on terminal A and B)
FW (Normal rotation)/RV (Reverse rotation), CF1-4 (Multistage speed 1-4), SF1-7
(Multistage speed bit 1-7), ADD (Addition of frequency), SCHG (Switching of

frequency command), STA (3-wire start)/STP (3-wire stop)/F_R (3-wire normal/

reverse), AHD (Retention of analog command), FUP (Increase of speed via

remote operation/FDN (Deceleration via remote operation), UDC (Deletion of data

via remote operation), F-OP (Forced command switching), SET (Second control),

RS (Reset), JG (Jogging), DB (External current braking), 2CH (2-stage

acceleration/deceleration), FRS (Free-run stop), EXT (External abnormality), USP

(Prevention of restart after restoration of power), CS (Commercial switching), SFT

(Soft-lock), BOK (Brake check), OLR (Overload restriction switching), KHC

(Clearance of integrated input power), OKHC (Clearance of integrated output

power), PID (PID1 disabled), PIDC (PID1 integration reset), PID2 (PID2 disabled),

PIDC2 (PID2 integration reset), SVC1-4 (PID1 multistage target values 1-4), PRO

(PID gain switching), PIO (PID output switching), SLEP (SLEEP condition

satisfied)/WAKE (WAKE condition satisfied), TL (Torque restriction enabled),

TRQ1, 2 (Switching of torque limit 1, 2), PPI (Switching of P/PI control), CAS

(Switching of control gain), FOC (Preparatory excitation), ATR (Torque control

enabled), TBS (Torque bias enabled), LAC (Cancellation of acceleration/

deceleration), Mi1-11 (General-purpose input 1-11), PCC (Clearance of pulse

counter), ECOM (Start of
EzCOM), PRG (Program run), HLD (Acceleration/
deceleration stop), REN (Operation permission signal), PLA (Pulse string input

A), and PLB (Pulse string input B)
Backup power supply
terminal
P+/P-: DC24V input (allowable input voltage: 24 V±10%)
STO input terminal
2 terminals (simultaneous input)
Thermistor input terminal
1 terminal (possible to switch between positive temperature coefficient/negative
temperature coefficient resistance element)
Output
Output terminal
function
Transistor output 5 terminal, 1a contact relay 1 point, 1c contact relay 1 point
RUN (During operation), FA1-5 (Reached signal), IRDY (Operation ready
completion), FWR (During normal rotation operation), RVR (During reverse

rotation operation), FREF (Frequency command operator keypad), REF

(Operation command operator keypad), SETM (Second control under selection),

AL (Alarm signal), MJA (Severe failure signal), OTQ (Over torque) *7, IP (During

instantaneous power failure), UV (Under insufficient voltage), TRQ (During torque

limitation), IPS (During power failure deceleration), RNT (RUN time over), ONT

(Power on time over), THM (Electronic thermal warning), THC (Electronic thermal

warning), WAC (Capacitor life advance notice), WAF (Fan life advance notice), FR
(Operation command signal), OHF (Cooling fin heating advance notice), LOC/

LOC2 (Low-current signal), OL/OL2 (Overload advance notice), BRK (Brake

release), BER (Brake abnormality), ZS (Zero-speed detection signal), OD/OD2

(PID deviation excessive), FBV/FBV2 (PID feedback comparison),
NDc
(Communication disconnection), Ai1Dc/Ai2Dc/Ai3Dc (Analog disconnection Ai1/

Ai2/Ai3), WCAi1/WCAi2/WCAi3 (Window comparator Ai1/Ai2/Ai3), LOG1-7

(Logical operation result 1-7), MO1-7 (General output 1-7), and OVS (Receiving

overvoltage).
Relay and alarm relay
(16, AL)
EDM output terminal
Output for STO diagnosis
Monitor output terminal
*8
Possible to output through selection from monitor data of parameters
EMC filter switching *9
Possible to enable the EMC noise filter (switching method is different depending
on the model)
External access to PC
USB Micro-B
Use
environ-

ment
Ambient temperature
*10
ND (normal duty)
-10 to 50°C
LD (low duty)
-10 to 45°C
VLD (very low duty)
-10 to 40°C
Storage temperature
*11
-20 to 65°C
Humidity
20-90%RH (location free of condensation)
Vibration *12
5.9 m/s2 (0.6 G) 10 to 55 Hz: 3G3RX2-A2004 to A2220 / 3G3RX2-A4007 to A4220
2.94 m/s
2 (0.3 G) 10 to 55 Hz: 3G3RX2-A2300 to A2550 / 3G3RX2-A4300 to
A413K
Use location *13
1000 m altitude or lower (location free from corrosive gas, oil mist, and dust)
Expected Life time
Smoothing capacitor 10 years
Designed life of cooling fan 10 years (models equipped with a cooling fan) free
from dust
Memory element on the control circuit board
Applicable standards *14
Conformance to UL/cUL standards, EU Directives and UK legislation, RCM, Functional Safety SIL3/PLe, KC
Painting color
Black
Operating, display
LCD Operator *15
Number of option slots
3 ports
Other options
Braking resistor, AC reactor, DC reactor, noise filter, EtherCAT Communication,
PG
*1. The output frequency range depend on the control and motor used. When running the inverter exceeding 60 Hz, check the maximum allowable frequency with the manufacturer of the motor.
*2. When the control mode is changed, unless the motor constant is appropriately configured,
you cannot obtain the desired starting torque or the inverter may trip.
*3. The variable range of motor speed may vary depending on your system or the environment where the motor is
used. Please contact us for details.
*4. Both the input power and output power are reference values, which are not appropriate for us
e in calculation of efficiency values, etc. To obtain an accurate value, use an external device.
*5. The IGBT error [E030] is generated by the protective function not only for short circuit protection but also when IGBT is damaged. Depending on the operating conditions of the inverter, the
overcurrent error [E001] may occur, instead of the IGBT error.
*6. At the factory default setting, when voltage and current on Ai1/Ai2 terminal is changed
using a switch, with input of voltage at 9.8 V and current at 19.8 mA, the maximum frequency is commanded. To change characteristics, make adjustments using the analog start/end function.
*7. The threshold for signal output varies depending on the motor to be combined with the i
nverter, parameter adjustment, etc.
*8. The output data of analog voltage monitor and analog current monitor are reference v
alues for connecting an analog meter. Due to the meter to be connected and variation in analog output circuit, the maximum output value may slightly vary from 10 V or 20 mA. To change characteristics, make adjustments using the Ao1 adjustment and Ao2 adjustment functions. Some monitor data cannot be output.
*9. To enable the EMC filter, connect with a power supply grounded at a neutral point. Othe
rwise, the leakage current may increase.
*10. Use
the 400 V class inverter at an input voltage of 500 VAC or below. If input voltage exceeds 500 VAC due to fluctuation of power, use the inverter at 40°C or lower ambient temperature.
*11. The storage temperature is the temperature during transport.

*12. To be in accordance with the testing method specified in JIS C 60068-2-6: 2010 (IEC 60068-2-6:2007)

*13. When the inverter is used in a location at 1000 m or higher altitude, air pressure redu
ces approximately 1% every 100 m elevation. Perform 1% current der- ating and conduct evaluation for every 100 m elevation.
*14. For insulation distance, comply with UL and CE standards

*15. When a clock function is used, the optional battery (CR2032, 3 V) is required. When y
ou purchase, this LCD operator does not come with the battery.
Communication Unit
The EtherCAT Communication Unit is an interface unit. When installed to an RX2 series high-function general-purpose inverter, it provides support for 100-Mbps EtherCAT.
Common Specifications
Item
Specifications
Model
3G3AX-RX2-ECT
Power supply
Supplied from the inverter
Protective structure
Open type (IP20)
Ambient operating temperature
-10 to 50°C
Ambient storage temperature
-20 to 65°C
Ambient operating humidity
20% to 90% (with no condensation)
Vibration *1
5.9 m/s2 (0.6 G), 10 to 55 Hz
Application environment
Indoors (There should be no corrosive gas, oil mist, or metal dust.)
Weight
100 g max. (Shipping weight: approx. 200 g)
Applicable standards
Conformance to EU Directives and UK legislation, UL/cUL, CSA, KC, RCM
*1. When using the EtherCAT Communication Unit with the inverters listed below, install the unit where it is not subjected to vibration or shock. Vibration or shock can cause communication errors or malfunctions.
Applicable models: 3G3RX2-A2300 to A2550, 3G3RX2-A4300 to B413K
EtherCAT Communications Specifications
Item
Specifications
Communications standard
IEC 61158 Type12, IEC 61800-7 CiA 402 drive profile
Physical layer
100BASE-TX (IEEE802.3)
Connector
RJ45 × 2 (shielded type)
ECAT IN: EtherCAT input
ECAT OUT: EtherCAT output
Communications media
Category 5 or higher (cable with double, aluminum tape and braided shielding) is
recommended.
Communications distance
Distance between nodes: 100 m max.
Process data
Fixed PDO mapping
User PDO mapping
Mailbox (CoE)
Emergency messages, SDO requests, and SDO responses
Synchronization mode
FreeRun mode *1
LED display
L/A IN (Link/Activity IN) × 1
L/A OUT (Link/Activity OUT) × 1
RUN × 1
ERR × 1
CiA402 drive profile
Velocity mode
*1. In FreeRun mode, slaves perform I/O processing, i.e., refresh I/O data asynchronously with the communications cycle of the master. The communications cycle is determined by the cycle time of the master. For the communications response time of the EtherCAT Communication Unit, refer to the EtherCAT Communication Unit User’s Manual (Cat.No. I663) for details.
Note that
FreeRun mode in the synchronization mode has a different meaning from free-run stop of an Inverter.
Version Information
The following table gives the relationship between unit versions of EtherCAT Communication Unit and the corresponding Sysmac Studio versions.
EtherCAT Communication Unit version
Sysmac Studio
Ver. 1.0 or later
Ver. 1.47 or higher