Product Category

Key-type Selector Switches

A22NK

22-mm dia. Key-type Selector Switches. Control panel miniaturization through a more compact design and modified wiring direction. Addition of Push-In Plus terminal blocks for easy wiring.

Certified Safety Standard Ratings

UL 508 (File No. E76675), CSA C22.2 No.14

6 A 240 VAC, 10 A 120 VAC 

TÜV (EN60947-5-1)

AC-15 3 A 240 VAC
 DC-13 4 A 24 VDC 

CCC (GB/T14048.5)

AC-15 3 A 240 VAC
 DC-13 4 A 24 VDC 

Application Standards

UL1059 and UL486E (Push-In Plus terminal block type) 

Ratings

Contacts (Standard Load)

Rated insulation voltage

600 V

Rated carry current

10 A

Rated voltage

24 V

120 V

240 V

380 V

440 V

AC at 50/60 Hz

Resistive load (AC-12)

10 A

10 A

6 A

2A

2 A

Inductive load (AC-15)

10 A

6 A

3 A

1.9 A

1.6 A

DC

Resistive load (DC-12)

8 A

2.2 A

1.1 A

---

---

Inductive load (DC-13)

4 A

1.1 A

0.55 A

---

---

Note: 1. The above ratings were obtained by conducting tests under the following conditions.
             (1) Ambient temperature: 20 ±2°C
             (2) Ambient humidity: 65% ±5% RH
             (3) Operating frequency: 30 operations/minute
          2. Minimum applicable load: 10 mA at 5 VDC. 

Characteristics

Item

Key-type Selector Switches

Allowable operating
 frequency

Mechanical

30 operations/minute max.

Electrical

30 operations/minute max.

Insulation resistance

100 MΩ min. (at 500 VDC)

Contact resistance

100 mΩ max. (initial value)

Dielectric strength

Between terminals
 of same polarity

2,500 VAC at 50/60 Hz for 1 min. (initial value)

Between each
 terminal and ground

2,500 VAC at 50/60 Hz for 1 min. (initial value)

Vibration resistance

Malfunction

10 to 55 Hz, 1.5-mm double amplitude (malfunction within 1 ms)

Shock resistance

Malfunction

1,000 m/s2 max. (malfunction within 1 ms)

Durability

Mechanical

500,000 operations min. (Switches with 3 positions: 300,000 operations min.)

Electrical

500,000 operations min. (Switches with 3 positions: 300,000 operations min.)
 (250 VAC, 3 A, with an inductive load having power factor cos θ = 0.4)

Ambient operating temperature*1

-25 to 70°C

Ambient operating humidity

35% to 85% RH

Ambient storage temperature*1

-40 to 80°C

Degree of protection*2

Conforming to IP66, NEMA13

Electric shock protection class

Class II

PTI (tracking characteristic)

175

Degree of contamination
 (application environment)

3 (EN 60947-5-1)

Weight

Approx. 65 g (for 1NC/1NO)

*1. With no icing or condensation.
 *2. Degree of protection from the front of the panel. 

Operating Characteristics (for SPST-NO/SPST-NC)

Item

Key-type Selector Switches

Manual reset

Automatic reset

Total travel force (torque) (maximum TTF)

0.6 N·m

0.6 N·m

Total travel (TT)

2 positions: Approx. 90°, 3 positions: Approx. 45°

Resetting force (torque) (RF)

0.5 N·m max.

---

Examples of Linked Contact Blocks (Screw terminal block type)

 image


Key-type Selector Switches

2 positions

3 positions

Linking example

image

image

Note: If you increase the number of Contact Blocks, evaluate the Switch under actual working conditions before permanent installation and use the Switch within a number of switching operations that will not adversely affect the Switch’s performance.