Coil Ratings
Rated voltage
Rated current*
Coil
resistance
Coil inductance (H)
(ref. value)
Must
operate

voltage
Must
release

voltage
Max.
voltage
Power
consumption

(approx.)
50 Hz
60 Hz
Armature
OFF
Armature
ON
% of rated voltage
AC
24 V
43.5 mA
37.4 mA
253 Ω
0.81
1.55
80% max.
30% max.
110%
0.9 VA at 60 Hz
48 V
21.8 mA
18.8 mA
1,040 Ω
3.12
6.17
110 V
9.5 mA
8.2 mA
5,566 Ω
13.33
26.83
120 V
8.6 mA
7.5 mA
7,286 Ω
16.13
32.46
230 V
4.4 mA
3.8 mA
27,172 Ω
72.68
143.9
240 V
4.2 mA
3.7 mA
27,800 Ω
90.58
182.34
Rated voltage
Rated current*
Coil
resistance
Coil inductance (H)
(ref. value)
Must
operate

voltage
Must
release

voltage
Max.
voltage
Power
consumption

(approx.)
Armature
OFF
Armature
ON
% of rated voltage
DC
6 V
87.0 mA
69 Ω
0.25
0.48
70% max.
15% min.
110%
0.53 W
12 V
43.2 mA
278 Ω
0.98
2.35
24 V
21.6 mA
1,113 Ω
3.6
8.25
48 V
11.4 mA
4,220 Ω
15.2
29.82
Note:
1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of

    +15%/-20% for the AC rated current and ±10% for the DC coil resistance.

2. The AC coil resistance and inductance values are reference values only (at 60 Hz).

3. Operating characteristics were measured at a coil temperature of 23°C.

4. The maximum voltage is the maximum possible value of the voltage that can be applied to the relay coil.

    It is not the maximum voltage that can be applied continuously.
Contact Ratings
Number of poles
1 pole
2 poles
Load
Resistive load
(cosΦ = 1)
Inductive load
(cosΦ = 0.4; L/R = 7 ms)
Resistive load
(cosΦ = 1)
Inductive load
(cosΦ = 0.4; L/R = 7 ms)
Rated load
10 A at 250 VAC;
10 A at 30 VDC
7.5 A at 250 VAC;
5 A at 30 VDC
5 A at 250 VAC;
5 A at 30 VDC
2 A at 250 VAC;
3 A at 30 VDC
Rated carry current
10 A
5 A
Max. switching voltage
440 VAC, 125 VDC
380 VAC, 125 VDC
Max. switching current
10 A
5 A
Max. switching power
2,500 VA, 300 W
1,875 VA, 150 W
1,250 VA, 150 W
500 VA, 90 W
Failure rate (reference value) *
100 mA at 5 VDC
10 mA at 5 VDC
Note: P level: λ60 = 0.1 x 10-6/operation
*This value was measured at a switching frequency of 120 operations per minute.
Characteristics
Item
1 pole
2 poles
Contact configration
SPDT
Contact structure
Single
Contact resistance
100 mΩ max.
Operate (set) time
15 ms max.
Release (reset) time
AC: 10 ms max.; DC: 5 ms max.
(w/built-in diode: 20 ms max.)
AC: 15 ms max.; DC: 10 ms max.
(w/built-in diode: 20 ms max.)
Max. operating
frequency
Mechanical: 18,000 operations/hr
Electrical: 1,800 operations/hr (under rated load)
Insulation resistance
1,000 MΩ min. (at 500 VDC)
Dielectric strength *
5,000 VAC, 50/60 Hz for 1 min between coil and
contacts;

1,000 VAC, 50/60 Hz for 1 min between contacts

of same polarity
5,000 VAC, 50/60 Hz for 1 min between coil and
contacts;

3,000 VAC, 50/60 Hz for 1 min between contacts

of different polarity

1,000 VAC, 50/60 Hz for 1 min between contacts

of same polarity
Vibration resistance
Destruction: 10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude)
Malfunction: 10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude)
Shock resistance
Destruction: 1,000 m/s2
Malfunction: 200 m/s
2 when energized; 100 m/s2 when not energized
Endurance
Mechanical:
AC coil: 10,000,000 operations min.;

DC coil: 20,000,000 operations min. (at 18,000 operations/hr)

Electrical: 100,000 operations min. (at 1,800 operations/hr under rated load) (DC coil type)
Ambient temperature
Operating: -40°C to 70°C (with no icing or condensation)
Ambient humidity
Operating: 5% to 85%
Weight
Approx. 20 g
Note: Values in the above table are the initial values.
*These values are relay only. Prease refer to the “Products Related to Common Sockets and DIN Tracks Data Sheet” for connecting sockets.
Approved Standards
UL 508 (File No. E41643)
Model
Contact form
Coil ratings
Contact ratings
Operations
G2R-1-S (S)
SPDT
5 to 110 VDC
6 to 240 VAC
10 A, 30 VDC (resistive)
10 A, 250 VAC (general use)
100 × 103
TV-3 (NO contact only)
25 × 103
G2R-2-S (S)
DPDT
5 A, 30 VDC (resistive)
5 A, 250 VAC (general use)
100 × 103
TV-3 (NO contact only)
25 × 103
CSA 22.2 No.0, No.14 (File No. LR31928)
Model
Contact form
Coil ratings
Contact ratings
Operations
G2R-1-S (S)
SPDT
5 to 110 VDC
6 to 240 VAC
10 A, 30 VDC (resistive)
10 A, 250 VAC (general use)
100 × 103
TV-3 (NO contact only)
25 × 103
G2R-2-S (S)
DPDT
5 A, 30 VDC (resistive)
5 A, 250 VAC (general use)
100 × 103
TV-3 (NO contact only)
25 × 103
IEC/VDE (Certificate No. 40015012 EN 61810-1)
Contact form
Coil ratings
Contact ratings
Operations
1 pole
6, 12, 24, 48 VDC
24, 110, 120, 230,

240 VAC
5 A, 440 VAC (cosφ = 1.0)
10 A, 250 VAC (cosφ = 1.0)

10 A, 30 VDC (0 ms)
100 × 103
2 poles
6, 12, 24, 48 VDC
24, 110, 120, 230,

240 VAC
5 A, 250 VAC (cosφ =1.0)
5 A, 30 VDC (0 ms)
100 × 103
LR
Number of poles
Coil ratings
Contact ratings
Operations
1 pole
5 to 110 VDC
6 to 240 VDC
10 A, 250 VAC (general use)
7.5 A, 250 VAC (PF0.4)

10 A, 30 VDC (resistive)

5A, 30VDC (L/R=7ms)
100 × 103
2 poles
5 to 110 VDC
6 to 240 VDC
5 A, 250 VAC (general use)
2 A, 250 VAC (PF0.4)

5 A, 30 VDC (resistive)

3A, 30VDC (L/R=7ms)
100 × 103
Accessories (Order Separately)
Socket Characteristics
Model
Rated
carry

current
Dielectric strength
Insulation
resistance*
Remarks
P2RF-05-PU
10 A
Between contact terminals of same polarity: 1,000 VAC for
1 min
1,000 MΩ min.
 
Between coil and contact terminals: 4,000 VAC for 1 min
P2RF-08-PU
6 A
Between contact terminals of different polarity: 3,000 VAC
for 1 min
1,000 MΩ min.
 
Between contact terminals of same polarity: 1,000 VAC for
1 min
Between coil and contact terminals: 4,000 VAC for 1 min
P2RFZ-05(-E)
10 A
Between contact terminals of same polarity: 1,000 VAC for
1 min
1,000 MΩ min.
 
Between coil and contact terminals: 4,000 VAC for 1 min
P2RFZ-08(-E)
6 A
Between contact terminals of different polarity: 3,000 VAC
for 1 min
1,000 MΩ min.
 
Between contact terminals of same polarity: 1,000 VAC for
1 min
Between coil and contact terminals: 4,000 VAC for 1 min
P2R-05P
10 A
Between contact terminals of same polarity: 1,000 VAC for
1 min
1,000 MΩ min.
 
Between coil and contact terminals: 4,000 VAC for 1 min
P2R-08P
5 A
Between contact terminals of different polarity: 3,000 VAC
for 1 min
1,000 MΩ min.
 
Between contact terminals of same polarity: 1,000 VAC for
1 min
Between coil and contact terminals: 4,000 VAC for 1 min
P2R-057P
10 A
Between contact terminals of same polarity: 1,000 VAC for
1 min
1,000 MΩ min.
 
Between coil and contact terminals: 5,000 VAC for 1 min
P2R-087P
5 A
Between contact terminals of different polarity: 3,000 VAC
for 1 min
1,000 MΩ min.
 
Between contact terminals of same polarity: 1,000 VAC for
1 min
Between coil and contact terminals: 5,000 VAC for 1 min
P2R-05A
10 A
Between contact terminals of same polarity: 1,000 VAC for
1 min
1,000 MΩ min.
 
Between ground terminals: 1,500 VAC for 1 min
Between coil and contact terminals: 4,000 VAC for 1 min
P2R-08A
5 A
Between contact terminals of different polarity: 3,000 VAC
for 1 min
1,000 MΩ min.
 
Between contact terminals of same polarity: 1,000 VAC for
1 min
Between ground terminals: 1,500 VAC for 1 min
Between coil and contact terminals: 4,000 VAC for 1 min
* The insulation resistance was measured with a 500-VDC insulation resistance meter at the same places as those used for
   measuring the dielectric strength.