When your order, specify the rated voltage.
Classification
Model
Rated voltage
Input (bifurcated contact)
SPST-NO
G7T-1122S (see note 2)
12 VDC
24 VDC
100/110 VAC
200/220 VAC
Output (single contact)
SPST-NO
G7T-1112S (see note 2)
12 VDC
24 VDC
SPST-NC
G7T-1012S
12 VDC
24 VDC
SPDT
G7T-112S
12 VDC
24 VDC
Note: 1. When ordering, add the rated voltage to the model number. Rated voltages are given in the coil ratings table in
              Specifications.
           2. The G7T-1122S and G7T-1112S are approved by UL and CSA. Contact your OMRON representative for the coil ratings of other models. The G7T-112S cannot be used in place of the G7TC. The G7T-112S can only be used with the P7TF-05 Socket.
           3. "Input" and "output" indicate the I/O relationship to a PLC. Input Relays are mainly suitable for input signals to a PLC or other device. Output Relays are mainly suitable to switching loads that receive output signals from a

PLC or other device. The Input and Output Relays have different switching p
erformances. Select a suitable Relay for the application.
Accessories
Socket
Applicable Relay
Model
All G7T I/O Relay and the G3TA models.
P7TF-05
P70 Indicator Module
Remove the transparent style strip of the Socket and mount this module. It will function as an operation indicator with surge suppression.
Model
Applicable Relay coil voltage
Remarks
For AC Relay
P70A
100/110 VAC
Surge suppressing system with varistor
200/220 VAC
For DC Relay
P70D
12/24 VDC
Surge suppressing system with diode
Note: 1. Order the Indicator Module that is suited to the Relay coil voltage.
           2. The Indicator Module for DC Relays has a multiple power supply common to 12 and 24 VDC.

           3. Input current (reference values):

                 100/110 VAC: 1.14 to 1.38 mA

                 200/220 VAC: 1.40 to 1.71 mA

                 12/24 VDC: 4.83 to 5.90 mA