General-purpose Relays

MK-S

New Super MK Relays. Models with Latching Lever Added to the Series.

Ratings
Coil Ratings
Rated voltage
Rated current
Coil
resistance
Must operate
voltage
Must release
voltage
Max. voltage
Power
consumption
50 Hz
60 Hz
AC
6 V
443 mA
385 mA
3.1 Ω
80% max. of
rated voltage
30% min. of rated
voltage at 60 Hz

25% min. of rated

voltage at 50 Hz
110% of rated
voltage
Approx. 2.3 VA
at 60 Hz

Approx. 2.7 VA

at 50 Hz
12 V
221 mA
193 mA
13.7 Ω
24 V
110 mA
96.3 mA
48.4 Ω
100 V
26.6 mA
23.1 mA
760 Ω
110 V
24.2 mA
21.0 mA
932 Ω
200 V
13.3 mA
11.6 mA
3,160 Ω
220 V
12.1 mA
10.5 mA
3,550 Ω
230 V
10.0 mA
11.5 mA
4,250 Ω
240 V
11.0 mA
9.6 mA
4,480 Ω
DC
6 V
224 mA
26.7 Ω
15% min. of rated
voltage
Approx. 1.4 W
12 V
112 mA
107 Ω
24 V
55.8 mA
430 Ω
48 V
28.1 mA
1,710 Ω
100 V
13.5 mA
7,390 Ω
110 V
12.3 mA
8,960 Ω
125 V
10.8 mA
11,576 Ω
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/−20% for AC rated current and ±15% for DC coil resistance.
          2. Performance characteristic data are measured at a coil temperature of 23°C.

          3. The maximum voltage is one that is applicable instantaneously to the Relay coil at 23°C and not continuously.

          4. For DC-operated Relays with the LED indicator built-in, add an LED current of approx. 5 mA to the rated current.
Contact Ratings
Load
Resistive load (cosφ = 1)
Inductive load (cosφ = 0.4)
Contact mechanism
Single
Contact material
AgSnIn
Rated load
NO
10 A, 250 VAC
10A, 30 VDC
7 A, 250 VAC
NC
5 A, 250 VAC
5 A, 30 VDC
Rated carry current
10 A
Max. switching voltage
250 VAC, 250 VDC
Max. switching current
10 A
Max. switching power
NO
2,500 VAC
300 WDC
1,750 VAC
NC
1,250 VAC
150 WDC
Characteristics
Contact resistance
100 mΩ max.
Operate time
AC: 20 ms max.
DC: 30 ms max.
Release time
20 ms max. (40 ms max. for built-in Diode Relays)
Max. operating frequency
Mechanical: 18,000 operations/h
Electrical: 1,800 operations/h (under rated load)
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,500 VAC 50/60 Hz for 1 min between coil and contacts
1,000 VAC 50/60 Hz for 1 min between contacts of same polarity and terminals of the

same polarity

2,500 VAC 50/60 Hz for 1 min between current-carrying parts, non-current-carrying

parts, and opposite polarity
Insulation method
Basic insulation
Impulse withstand voltage
4.5 kV between coil and contacts (with 1.2 × 50 μs impulse wave)
3.0 kV between contacts of different polarity (with 1.2 × 50 μs impulse wave)
Pollution degree
3
Rated insulation voltage
250 V
Vibration resistance
Destruction: 10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude)
Malfunction: 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Shock resistance
Destruction: 1,000 m/s2 (approx. 100 G)
Malfunction: 100 m/s
2 (approx. 10 G)
Endurance
Mechanical: 5,000,000 operations min. (at 18,000 operations/h under rated load)
Electrical: 100,000 operations h. (at 1,800 operations/h under rated load)
Failure rate P level
(reference value)
10 mA at 1 VDC
Ambient temperature
Operating: -40 to 60°C (with no icing or condensation)
Ambient humidity
Operating: 5% to 85%
Weight
Approx. 90 g
Note: 1. The values given above are initial values.
           2. P level: λ60 = 0.1 × 10-6/operation

           3. Ambient temperature of models with LED indicator is −25 to 60°C.
Approved Standards
UL508 (File No. E41515)
Coil ratings
Contact ratings
Operations
6 to 110 VDC
6 to 240 VAC
N.O. contact
10 A, 250 V AC 50/60 Hz (Resistive)
10 A, 30 V DC (Resistive)

7 A, 250 V AC 50/60 Hz (General Use)
100,000
N.C. contact
10 A, 250 V AC 50/60 Hz (Resistive)
10 A, 30 V DC (Resistive)

7 A, 250 V AC 50/60 Hz (General Use)
100,000
CSA Standard: CSA C22.2 No. 14 (File No. LR35535)
Coil ratings
Number of Poles
Contact ratings
Operations
6 to 125 VDC
6 to 240 VAC
2
10 A, 250 V AC (Resistive)
10 A, 30 V DC (Resistive)

7 A, 250 V AC (General Use)
100,000
3
10 A, 250 V AC (Resistive) Same Polarity
10 A, 30 V DC (Resistive) Same Polarity

7 A, 250 V AC (General Use) Same Polarity
100,000
IEC Standard/TÜV Certification: IEC61810-1 (Certification No. R50104853)
Coil ratings
Contact ratings
Operations
6, 12, 24, 48, 100, 110 VDC
6, 12, 24, 100, 110, 200, 220, 240 VAC
N.O. contact
10 A, 250 V AC 50/60 Hz (Resistive)
10 A, 30 V DC (Resistive)

7 A, 250 V AC 50/60 Hz (General Use)
100,000
N.C. contact
5 A, 250 V AC 50/60 Hz (Resistive)
5 A, 30 V DC (Resistive)

7 A, 250 V AC 50/60 Hz (General Use)
100,000
Note: When Relays are mounted on the PF083A-E or PF113A-E, the maximum carrying current is 9 A.