Safety Network Controller
NE0A-SCPU01
New Lineup for Safety Applications with Up to 12 Inputs
Certified Standards
Certification body | Standard |
TÜV Rheinland | EN ISO 13849-1 EN ISO 13849-2 IEC 61508 EN 62061 EN 61131-2 IEC 61326-3-1 |
UL | UL508 ISA12.12.01 UL1998 IEC 61508-3 |
Specifications
Communications power supply voltage | 11 to 25 VDC supplied via communications connector | |
Internal circuit power supply voltage (V0) *1 | 20.4 to 26.4 VDC (24 VDC - 15%/+10%) | |
I/O power supply voltage (V1, V2) *1 | ||
Current consumption | Communications power supply | 24 VDC, 15 mA |
Internal circuit power supply | 24 VDC, 110 mA | |
I/O power supply * 2 | 24 VDC, 80 mA (Input) 80 mA (Output) | |
Overvoltage category | II | |
Noise immunity | Conforms to IEC61131-2. | |
Vibration resistance | 10 to 57 Hz: 0.35 mm, 57 to 150 Hz: 50 m/s2 | |
Shock resistance | 150 m/s2 : 11 ms | |
Mounting method | DIN Track (IEC 60715 TH35-7.5/TH35-15) | |
Ambient operating temperature | - 10 to 55 ° C | |
Ambient operating humidity | 10% to 95% (with no condensation) | |
Ambient storage temperature | - 40 to 70 ° C | |
Degree of protection | IP20 | |
Serial I/F | USB version 1.1 | |
Weight | 440 g max. |
*1. V0-G0: Internal control circuit
V1-G1: For external input device, test output
V2-G2: For external output device
*2. Not including power consumption for external devices.
V1-G1: For external input device, test output
V2-G2: For external output device
*2. Not including power consumption for external devices.
Safety Input Specifications
Input type | Sinking inputs (PNP) |
ON voltage | 11 VDC min. between each terminal and ground |
OFF voltage | 5 VDC max. between each terminal and ground |
OFF current | 1 mA max. |
Input current | 4.5 mA |
Safety Output Specifications
Output type | Sourcing outputs (PNP) |
Rated output current | 0.5 A max./output |
ON residual voltage | 1.2 V max. between each output terminal and V2 |
Leakage current | 0.1 mA max. |
Test Output Specifications
Output type | Sourcing outputs (PNP) |
Rated output current | 60 mA |
ON residual voltage | 1.2 V max. between each output terminal and V1 |
Leakage current | 0.1 mA max. |
DeviceNet Communications Specifications
Communications protocol | DeviceNet compliant | |||
Connection form | Multi-drop system and T-branch system can be combined (for trunk line and branch lines) | |||
Communications speed | 500/250/125 kbps | |||
Communications media | Special cable, 5 conductors (2 for communications, 2 for power supply, 1 for shielding) | |||
Communications distance | Communications speed | Max. network length | Branch length | Total branch length |
500 kbps | 100 m max. (100 m max.) | 6 m max. | 39 m max. | |
250 kbps | 250 m max. (100 m max.) | 78 m max. | ||
125 kbps | 500 m max. (100 m max.) | 156 m max. | ||
Note: Figures in parentheses ( ) indicate values when a thin cable is used. | ||||
Communications power supply | 11 to 25 VDC | |||
No. of connectable nodes | 63 | |||
Safety I/O communications | Safety Slave function Max. no. of connections: 2 (one each for inputs and outputs) Multi-cast inputs can be used to enable communications with up to 15 Safety Masters. Connection type: Single-cast, multi-cast | |||
Standard I/O communications | Standard Slave function Max. no. of connections: 2 Connection type: Poll, bit-strobe, COS, cyclic | |||
Message communications | Max. message length: 502 bytes |