Enclosed Switch

SHL

Subminiature Enclosed Switch (Measuring 48 x 17.5 x 45 mm) with High Sealing Property

Approved Standards

Agency

Standard

File No.

Approved models

UL

UL508

E76675

General-purpose models listed on Data Sheet.

CSA

CSA C22.2 No. 14

LR45746

TÜV Rheinland

EN60947-5-1

J50062486

All SHL models listed in this datasheet.

CCC (CQC)

GB/T14048.5

Contact your OMRON
 representative for details.

Ask your OMRON representative for information
 on approved models.

Ratings

Rated voltage

Non-inductive load (A)

Inductive load (A)

 

Resistive load

Lamp load

Inductive load

Motor load

 

NC

NO

NC

NO

NC

NO

NC

NO

 

125 VAC
 250 VAC
 480 VAC

10
 10
 2

1.5
 1.5
 -

3
 2
 -

2.5
 1.5
 -

 

8 VDC
 14 VDC
 30 VDC
 125 VDC
 250 VDC

10
 10
 5
 0.4
 0.2

2
 2
 1.5
 0.4
 0.2

5
 5
 1.5
 0.05
 0.03

2
 2
 1.5
 0.05
 0.05

 

Inrush current

NC

15 A max.



NO

15 A max.













 

Note: 1. The above figures are for steady-state currents.
          2. Inductive loads have a power factor of 0.4 min. (AC) and a time constant of 7 ms max. (DC).
          3. Lamp load has an inrush current of 10 times the steady-state current.
          4. Motor load has an inrush current of 6 times the steady-state current.

Micro load models

Rated voltage

Non-inductive load (A)

Resistive load

NC

NO

125 VAC

0.1

8 VDC
 14 VDC
 30 VDC

0.1
 0.1
 0.1

Approved Standard Ratings

TÜV (EN60947-5-1), CCC (GB/T14048.5)

Model

Category and rating

I the

SHL-[]55

AC-15 2 A/125 V
 DC-12 2 A/48 V

5 A
 5 A

SHL-[]55-01

AC-14 0.1 A/125 V
 DC-12 0.1 A/48 V

0.5 A
 0.5 A

SHL-[]55-L

AC-15 2 A/125 V

5 A

SHL-[]55-01L

AC-14 0.1 A/125 V

0.5 A

SHL-[]55-01L2

DC-12 0.1 A/12 V

0.5 A

SHL-[]55-L3

DC-12 2 A/24 V

5 A

SHL-[]55-01L3

DC-12 0.1 A/24 V

0.5 A

SHL-[]55-L4

DC-12 2 A/24 V

5 A

SHL-[]55-01L4

DC-12 0.1 A/24 V

0.5 A

SHL-[]55-L5

DC-12 2 A/48 V

5 A

SHL-[]55-01L5

DC-12 0.1 A/48 V

0.5 A

Note: "AC-15 2 A/125 V" indicates the following.
          Application category: AC-16
          Rated operating current (Ie): 2 A
          Rated operating voltage (Ue): 125 V

UL/CSA

A300

Rated voltage

Carry current

Current (A)

Volt-amperes (V)

Make

Break

Make

Break

120 VAC
 240 VAC

10 A

60
 30

6
 3

7,200

720

Characteristics (For SHL-W155)

Degree of protections *1

IP67 (EN60947-5-1)

Durability *2

Mechanical

10,000,000 operations min.

Electrical

500,000 operations min.

Operating speed

0.1 mm/s to 0.5 m/s (hinge lever models)

Operating
 frequency

Mechanical

120 operations/min

Electrical

30 operations/min

Rated frequency

50/60 Hz

Insulation resistance

100 MΩ min. (at 500 VDC)

Contact resistance

15 mΩ max. (initial value for the built-in switch when tested alone)

Dielectric
 strength

Between terminals of the same
 polarity

1,000 VAC, 50/60 Hz for 1 min

Between each terminal and
 non-current-carrying metal
 part

2,000 VAC, 50/60 Hz for 1 min/Uimp at 2.5 kV (EN60947-5-1)

Rated insulation voltage (Ui)

150 V (EN60947-5-1)

Pollution degree (operating environment)

3 (EN60947-5-1)

Short-circuit protective device (SCPD)

10 A fuse type gI or gG (IEC60269)

Conditional short-circuit current

100 A (EN60947-5-1)

Conventional enclosed thermal current (Ithe)

5 A (EN60947-5-1)

Protection against electric shock

Class II (grounding not required with double insulation)

OFF reverse voltage

1,000 VAC max., 300 VDC max. (EN60947-5-1)

Vibration
 resistance

Malfunction

10 to 55 Hz, 1.5-mm double amplitude

Shock
 resistance

Destruction

1,000 m/s2 max.

Malfunction

300 m/s2 max.

Ambient operating temperature

-10°C to +80°C (with no icing)

Ambient operating humidity

35% to 95%RH

Weight *3

Approx. 62 to 72 g

Note: 1. The figures at the left are initial values.
          2. The ratings at the left may vary depending on the model. Contact your OMRON representative for further details.
 1. The head section of the plunger type SHL-D(Q)[][] is excluded.
 2. Durability values are calculated at an operating temperature of +5°C to +35°C, and an operating humidity of 40% to 70%RH.
 3. The values are for the plunger-type models.