Product Category

Alternate Operation Relay

61F-AN

Increases Motor Life and Enables Operating Only One Pump When Cleaning Tanks or as an Emergency Measure for Pump Failures.

Ratings

Supply voltage

100, 110, 200, 220 VAC; 50/60 Hz

Operating voltage range

85% to 110% of rated voltage

Power consumption

3 VA

Contact Ratings (with G2RK Keep Relay)

Item

Resistive load (cosΦ = 1)

Inductive load (cosΦ = 0.4, L/R = 7 ms)

Max. load

3 A at 250 VAC

1.5 A at 250 VAC

Carry contact

0.125

Max. operating current

0.125

Max. switching capacity

750 VA

375 VA

Characteristics

Response time

Operate: 25 ms max.
 Release: 30 ms max.

Minimum pulse width

Min. ON time: 40 ms min.
 Min. OFF time: 200 ms min.

Insulation resistance

100 MΩ min. at 500 VDC (between each terminal and power supply)

Dielectric strength

2,000 VAC, 50/60 Hz for 1 min (between each terminal and power supply)

Vibration resistance

10 to 55 Hz, 1-mm double amplitude

Shock resistance

10 G (approx. 98 m/s2)

Life expectancy

Mechanical: 1,000,000 operations (at operating frequency of 1,800 operations/hour)
 Electrical: 100,000 operations min.
 (rated load)

Ambient temperature

Operating: -10 to 55°C

Ambient humidity

Operating: 45% to 85% RH

Weight

Approx. 215 g