Ratings

Rated voltage

Non-inductive load (A)

Inductive load (A)

Resistive load

Lamp load

Inductive load

Motor load

NC

NO

NC

NO

NC

NO

NC

NO

125 VAC

1

1

1

0.7

1

1

1

1

30 VDC

1

1

1

1

1

1

1

1

Note: 1. The above current ratings are for steady-state current.
            2. Inductive loads have a power factor of 0.4 min. (AC) and a time constant of 7 ms max. (DC).
            3. Lamp loads have an inrush current of 10 times the steady-state current.
            4. Motor loads have an inrush current of 6 times the steady-state current.

D4CC-3, D4CC-4, 1 A at 30 VDC 

Inrush current

NC

5 A max.

NO

2.5 A max.

Characteristics

Degree of protection

IP67

Durability *1

Mechanical

10,000,000 operations min.

Electrical

200,000 operations min. (1 A at 125 VAC, resistive load)

Operating speed

0.1 mm/s to 0.5 m/s (in case of plunger)
 1 mm/s to 1 m/s (in case of roller lever)

Operating
 frequency

Mechanical

120 operations/min

Electrical

30 operations/min

Rated frequency

50/60 Hz

Insulation resistance

100 MΩ min. (at 500 VDC)

Contact resistance (initial)

100 mΩ max.

Dielectric
 strength

Between terminals of same polarity

1,000 VAC, 50/60 Hz for 1 min

Between current-carrying metal
 parts and ground

1,500 VAC, 50/60 Hz for 1 min

Between each termi-nal and non-
 current-carrying metal part

1,500 VAC, 50/60 Hz for 1 min

Vibration
 resistance

Malfunction

10 to 55 Hz, 1.5-mm double amplitude *2

Shock
 resistance

Destruction

1,000 m/s2 max.

Malfunction

500 m/s2 max. *2

Ambient operating temperature

-10°C to +70°C (with no icing)

Ambient operating humidity

35% to 95%RH

Weight

Approx. 120 g (in the case of D4CC-1002)

Note: The above figures are initial values.                                      
 1. The values are calculated at an operating temperature of +5°C to +35°C, and an operating humidity of 40% to 70%RH. Contact your OMRON sales representative for more detailed information on other operating environments.
 2. Excluding plastic rod models.

Leakage Current for Switches with Indicators

The leakage current and resistance of Switches with indicators are as follows: 

Item Model

D4CC-2[][][]

D4CC-4[][][]

Voltage

125 VAC

30 VDC

Leakage current

1.0 mA

1.0 mA

Resistive value

150 k Ω

30 k Ω