Proximity Sensor Ideal for High Temperatures and Cleaning Processes
E2EH
Proximity Sensor Ideal for the Food and Beverage Industry
E2EH-X[]D[] DC 2-Wire Models
Size |
M12 |
M18 |
M30 |
|
Shielded |
Shielded |
|||
Model |
E2EH-X3D[] |
E2EH-X7D[] |
E2EH-X12D[] |
|
Sensing distance |
3 mm |
7 mm |
12 mm |
|
Set distance *1 |
0 to 2.4 mm |
0 to 5.6 mm |
0 to 9.6 mm |
|
Differential travel |
15% max. of sensing distance |
|||
Detectable object |
Ferrous metal (The sensing distance decreases with non-ferrous metal. Refer to Datasheet.) |
|||
Standard sensing object |
Iron, 12 × 12 × 1 mm |
Iron 21 × 21 × 1 mm |
Iron 36 × 36 × 1 mm |
|
Response frequency *2 |
500 Hz |
300 Hz |
100 Hz |
|
Power supply voltage (operating |
12 to 24 VDC, ripple (p-p): 10% max. |
|||
Leakage current |
0.8 mA max. |
|||
Control output |
Load current |
3 to 100 mA |
||
Residual voltage *3 |
Polarity Models: 3 V max. |
|||
Indicators |
D1 Models: Operation indicator (red), Setting indicator (yellow) |
|||
Operation mode (with sensing object |
D1 Models: NO |
|||
Protection circuits |
Surge suppressor, Load short-circuit protection |
|||
Ambient temperature range |
Operating: 0 to 100°C |
|||
Ambient humidity range |
35% to 95% |
|||
Temperature influence |
±10% max. of sensing distance at 23°C in the temperature range of 0 to 70°C. |
|||
Voltage influence |
± 10% max. of sensing distance at rated voltage in the 15% rated voltage range. |
|||
Insulation resistance |
50 MΩ min. (at 500 VDC) between current-carrying parts and case |
|||
Dielectric strength |
1,000 VAC, 50/60 Hz for 1 min between current-carrying parts and case |
|||
Vibration resistance |
Destruction: 10 to 55 Hz 1.5-mm double amplitude for 2 hours each in X, Y and Z directions |
|||
Shock resistance |
Destruction: 1,000 m/s2, 10 times each in X, Y and Z directions |
|||
Degree of protection |
IEC IP67, DIN 40050-9 IP69K *4 |
|||
Connection method |
Pre-wired Models (Standard cable length 2 m), Connector Models |
|||
Weight |
Pre-wired Models |
Approx. 80 g |
Approx. 145 g |
Approx. 220 g |
Connector Models |
Approx. 30 g |
Approx. 55 g |
Approx. 125 g |
|
Materials |
Case, clamping nut |
Stainless steel (SUS316L) |
||
Sensing surface |
PBT |
|||
Cable |
Heat-resistant PVC cable (Pre-wired model) |
|||
Accessories |
Instruction manual |
1. Use the yellow indicator on D1 Models as a guide.
2. The response frequency is an average value. Measurement conditions are as follows: standard sensing object, a distance of twice the standard sensing object, and a set distance of half the sensing distance.
3. The residual voltage of each E2EH-X@D@ DC 2-Wire Model is 5 V. When connecting to a device, make sure that the device can withstand the residual voltage. (Refer to Data Sheet.)
4. IP69K Degree of Protection Specification IP69K is a protection standard against high temperature and high-pressure water defined in the German standard DIN 40050,
Part 9. The test piece is sprayed with water at 80°C at a water pressure of 80 to 100 BAR using a specified nozzle shape at a rate of 14 to 16 liters/min.
The distance between the test piece and nozzle is 10 to 15 cm, and water is sprayed horizontally for 30 seconds each at 0°, 30°, 60°, and 90° while rotating the test piece on a horizontal plane.
E2EH-X[]C[]/B[] DC 3-Wire Models
Size |
M12 |
M18 |
M30 |
|
Shielded |
Shielded |
|||
Model |
E2EH-X3C[]/B[] |
E2EH-X7C[]/B[] |
E2EH-X12C[]/B[] |
|
Sensing distance |
3 mm±10% |
7 mm±10% |
12 mm±10% |
|
Set distance *1 |
0 to 2.4 mm |
0 to 5.6 mm |
0 to 9.6 mm |
|
Differential travel |
15% max. of sensing distance |
|||
Detectable object |
Ferrous metal (The sensing distance decreases with non-ferrous metal. Refer to Datasheet.) |
|||
Standard sensing object |
Iron, 12 × 12 × 1 mm |
Iron 21 × 21 × 1 mm |
Iron 36 × 36 × 1 mm |
|
Response frequency *2 |
500 Hz |
300 Hz |
100 Hz |
|
Power supply voltage (operating |
12 to 24 VDC, ripple (p-p): 10% max. |
|||
Current consumption |
10 mA max. |
|||
Control output |
Load current |
100 mA max. |
||
Residual voltage |
2 V max. (Load current: 100 mA, Cable length 2 m) |
|||
Indicators |
Operation indicator (yellow) |
|||
Operating mode |
C1 Models: NO |
|||
Protection circuits |
Power supply reverse polarity protection, Surge suppressor, Load short-circuit protection, Reversed output polarity protection |
|||
Ambient temperature range |
Operating: 0 to 100°C |
|||
Ambient humidity range |
35% to 95% |
|||
Temperature influence |
±10% max. of sensing distance at 23°C in the temperature range of 0 to 70°C. |
|||
Voltage influence |
10% max. of sensing distance at rated voltage in the 15% rated voltage range. |
|||
Insulation resistance |
50 MΩ min. (at 500 VDC) between current-carrying parts and case |
|||
Dielectric strength |
1,000 VAC, 50/60 Hz for 1 min between current-carrying parts and case |
|||
Vibration resistance |
Destruction: 10 to 55 Hz 1.5-mm double amplitude for 2 hours each in X, Y and Z directions |
|||
Shock resistance |
Destruction: 1,000 m/s2, 10 times each in X, Y and Z directions |
|||
Degree of protection |
IEC IP67, DIN 40050-9 IP69K |
|||
Connection method |
Pre-wired Models (Standard cable length 2 m), Connector Models |
|||
Weight |
Pre-wired Models |
Approx. 80 g |
Approx. 145 g |
Approx. 220 g |
Connector Models |
Approx. 30 g |
Approx. 55 g |
Approx. 125 g |
|
Materials |
Case, |
Stainless steel (SUS316L) |
||
Sensing surface |
PBT |
|||
Cable |
Heat-resistant PVC cable (Pre-wired Model) |
|||
Accessories |
Instruction manual |
1. The response frequency is an average value.
Measurement conditions are as follows: standard sensing object, a distance of twice the standard sensing object, and a set distance of half the sensing distance.
Resistance to Detergents, Disinfectants, and Chemicals
- Performance is assured for typical detergents and disinfectants, but performance may not be maintained for some detergents and disinfectants. Refer to the following table when using these agents.
- The E2EH passed testing for resistance to detergents and disinfectants performed using the items in the following table. Refer to this table when considering use of detergents and disinfectants.
Category |
Product name |
Concentration |
Temperature |
Time |
Chemical |
Sodium hydroxide (NaOH) |
1.5% |
70 ° C |
240h |
Potassium hydroxide (KOH) |
1.5% |
70 ° C |
240h |
|
Phosphoric acid (H3PO4) |
2.5% |
70 ° C |
240h |
|
Sodium hypochlorite (NaClO) |
0.3% |
25 ° C |
240h |
|
Hydrogen peroxide (H2O2) |
6.5% |
25 ° C |
240h |
|
Alkaline foam detergent |
P3-topax-66s (Manufactured by Ecolab) |
3.0% |
70 ° C |
240h |
Acidic foam detergent |
P3-topax-56 (Manufactured by Ecolab) |
5.0% |
70 ° C |
240h |
Disinfectant |
P3-oxonia active 90 (Manufactured by Ecolab) |
1.0% |
25 ° C |
240h |
Test Conditions
After the test is completed, check that no problems exist with the following product characteristics.
(1) Appearance (no damage that will affect the product characteristics)
(2) Operation Check (ON/OFF)
(3) Insulation resistance: 50 MΩ min. (at 500 VDC)
(4) Dielectric strength (1,000 VAC for 1 minute)
(5) Water resistance (IP67)