Product Category

Miniature Limit Switch

HL-5000

Economical, Miniature Limit Switch Boasting Rigid Construction

Approved Standards

Agency

Standard

File No.

CCC (CQC)

GB/T14048.5

-


Ratings

Rated voltage

Non-inductive load (A)

Inductive load (A)

Resistive load

Lamp load

Inductive load

Motor load

NC

NO

NC

NO

NC

NO

NC

NO

125 VAC
 250 VAC

5
 5

1.5
 1

0.7
 0.5

3
 3

2
 1.5

1
 0.8

12 VDC
 24 VDC
 125 VDC
 250 VDC

5
 5

3
 3

4
 4

3
 3

0.4
 0.4

0.2
 0.2

-

-

-










Note: 1. The above figures are for steady-state currents.
          2. Inductive loads have a power factor of 0.4 min. (AC) and a time constant of 7 ms max. (DC).
          3. Lamp load has an inrush current of 10 times the steady-state current.
          4. Motor load has an inrush current of 6 times the steady-state current.

Inrush current

NC

24 A max.

NO

12 A max.

Approved Standard Ratings

CCC (GB/T14048.5)

Applicable category and ratings

AC-15 3 A/250 VAC

Characteristics

Degree of protection

IP65

Durability *

Mechanical

10,000,000 operations min. (under rated conditions)

Electrical

See the following Electrical Durability.

Operating speed

5 mm/s to 0.5 m/s

Operating frequency

Mechanical

120 operations/min

Electrical

30 operations/min

Insulation resistance

100 MΩ min. (at 500 VDC)

Contact resistance

25 mΩ max. (initial value)

Dielectric strength

1,000 VAC, 50/60 Hz for 1 min between terminals of the same polarity

1,500 VAC, 50/60 Hz for 1 min between current-carrying metal parts and ground

1,500 VAC, 50/60 Hz for 1 min between each terminal and non-current-carrying metal part

Rated frequency

50/60 Hz

Vibration resistance

Malfunction

10 to 55 Hz, 1.5-mm double amplitude

Shock resistance

Destruction

1,000 m/s2 max.

Malfunction

300 m/s2 max.

Ambient operating temperature

-5°C to +65°C (with no icing)

Ambient operating humidity

35% to 95%RH

Weight

Approx. 130 to 190 g

Note: 1. The above figures are initial values.
          2. The above characteristics may vary depending on the model. 

* The values are calculated at an operating temperature of +5°C to +35°C, and an operating humidity of 40% to 70%RH.